3.11 Setting the Profibus DP address
The bus address is set on the Profibus DP interface board.
.
Loosen screws and remove cover (figure F-1)
.
Set the required bus address using rotary switches S2 and S3
(figure F-2). (Factory setting: slave address 2)
Switch (S2) for setting the units digit.
Switch (S3) for setting the tens digit.
Example: The address ‘65’ is set as follows:
(S2) to position 5 = (5 * 1 = 5)
(S2) to position 6 = (6 * 10 = 60)
13
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Short instructions bus connection
Profibus DP
Figure F-1
Screws
Profibus DP interface
board
Figure F-2: Profibus DP interface board
Rotary switch S3
Rotary switch S2