3.11 Setting the Profibus DP address

The bus address is set on the Profibus DP interface board.

.

Loosen screws and remove cover (figure F-1)

.

Set the required bus address using rotary switches S2 and S3
(figure F-2). (Factory setting: slave address 2)

Switch (S2) for setting the units digit.
Switch (S3) for setting the tens digit.

Example: The address ‘65’ is set as follows:
(S2) to position 5 = (5 * 1 = 5)
(S2) to position 6 = (6 * 10 = 60)

13

Actuator controls AUMA MATIC AM/ AMExB/ AMExC

Short instructions bus connection

Profibus DP

Figure F-1

Screws

Profibus DP interface
board

Figure F-2: Profibus DP interface board

Rotary switch S3
Rotary switch S2

Summary of Contents for AM 01.1

Page 1: ...Certificate Registration No 12 100 104 4269 Actuator controls Short instructions bus connection AUMA MATIC AM 01 1 AM 02 1 AMExB 01 1 AMExC 01 1 Profibus DP...

Page 2: ...Fitting the cover 6 3 4 Remote position transmitter 7 3 5 AUMA MATIC on wall bracket 7 3 6 Test run 7 3 7 Mains and bus connection for Ex version with plug socket connector terminal board KP 8 3 8 Ma...

Page 3: ...instructions Correct transport proper storage mounting and installation as well as careful commissioning are essential to ensure a trouble free and safe oper ation The following references draw speci...

Page 4: ...Loosen screws 51 01 and remove socket carrier 51 0 from plug cover 50 0 Insert cable glands suitable for connecting cables The enclosure protection stated on the name plate is only ensured if suit abl...

Page 5: ...ce in the Profibus segment Only switch on the termination resistors position ON if the actuator is the final device within the Profibus DP segment 5 Actuator controls AUMA MATIC AM AMExB AMExC Short i...

Page 6: ...cable glands with the specified torque to ensure the required enclosure protection 6 Actuator controls AUMA MATIC AM AMExB AMExC Profibus DP Short instructions bus connection Figure B 3 Connection boa...

Page 7: ...ertaining to the actuator multi turn actuator SA R part turn actuator SG Check limit and torque switching Check limit and torque switching electronic position transmitter RWG or potentiometer option a...

Page 8: ...nected to one terminal Remove cable sheathing in a length of 120 140 mm Strip wires Controls max 8 mm motor max 12 mm For stranded wires use end sleeves according to DIN 46228 Connect bus cable Refer...

Page 9: ...ws Screws Screws Cross section max 6 mm 2 6 mm 2 1 5 mm 2 Material Pin socket carrier Araldite Polyamide Araldite Polyamide Araldite Polyamide Contacts Brass Ms Brass Ms Brass Ms tin plated 1 Suitable...

Page 10: ...e protection stated on the name plate is only ensured if suitable cable glands are used Seal cable entries which are not used with suitable plugs Cross sections for connection Control cables max 2 5 m...

Page 11: ...onnection diagram figure B 2 For Ex version with plug socket connector terminal board KP subclause 3 7 Connect cable B to terminal 6 cable A to terminal 7 The termination resistor for channel 2 is con...

Page 12: ...Profibus perform a potential compensation Cable specification cable type A for Profibus DP Characteristic impedance 135 to 165 Ohm at a frequency of 3 to 20 Mhz Cable capacity 30 pF per meter Core di...

Page 13: ...Factory setting slave address 2 Switch S2 for setting the units digit Switch S3 for setting the tens digit Example The address 65 is set as follows S2 to position 5 5 1 5 S2 to position 6 6 10 60 13...

Page 14: ...ED In end position OPEN switching off is always via limit seating This switch is used to inform the Profibus DP board about the type of seating is to be used to operate the actuator in end position CL...

Page 15: ...d to this input If the switch S1 1 is on the left side in position AI 3 the pin 5 AN 4 is connected to GND Input AN 3 can be used in the same way as AN 2 If the switch is on the right side in position...

Page 16: ...er with RWG are connected on this plug 16 Actuator controls AUMA MATIC AM AMExB AMExC Profibus DP Short instructions bus connection Pin Description 1 Channel 1 B cable bus termination 2 Channel 1 A ca...

Page 17: ...fluence When controlling via Profibus DP switching off is always realised by limit seating in en position OPEN Position1 Switching off by limit seating in end position CLOSED Position 2 Switching off...

Page 18: ...Profibus Nutzerorganisation Haid und Neu Str 7 D 76131 Karlsruhe Phone 49 721 96 58 590 Fax 49 721 96 58 589 Http www profibus com 6 Appendix B Connecting the cable shield for AUMA MATIC AMExB AMExC...

Page 19: ...tenance 3 Motor connection 10 N Name plate 8 O Overvoltage protection 6 P Parking frame 8 Plug socket connector 8 9 Power supply 4 Push to run operation 17 R Remote position transmitter RWG 7 S Safety...

Page 20: ...297 Sintra Tel 351 2 1910 95 00 Fax 351 2 1910 95 99 industra tyco valves com MEGA End stri Kontrol Sistemieri Tic Ltd Sti TR 06810 Ankara Tel 90 312 217 32 88 Fax 90 312 217 33 88 megaendustri megaen...

Reviews: