![AUMA ACE C 01.2 Profinet Series Manual Download Page 98](http://html1.mh-extra.com/html/auma/ace-c-01-2-profinet-series/ace-c-01-2-profinet-series_manual_3016379098.webp)
Service conditions
Suitable for use in areas with high salinity, almost permanent condensation, and
high pollution.
KS
Standard:
Corrosion protection
Suitable for use in areas with extremely high salinity, permanent condensation,
and high pollution.
KX
Option:
Double layer powder coating
Two-component iron-mica combination
Coating
AUMA silver-grey (similar to RAL 7037)
Standard:
Colour
Available colours on request
Option:
Accessories
For actuator controls mounted separately from the actuator, including plug/socket connector.
Connecting cable on request.
Recommended for high ambient temperatures, difficult access, or in case of heavy vibration during
service.
Cable length between actuator and actuator controls is max. 100 m. An MWG is required for position
feedback.
Wall bracket
AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC)
AUMA Assistant App (Commissioning and Diagnostic Tool for Android devices)
Programming software
Further information
Approx. 12 kg (including Ex-plug/socket connector with screw-type terminals)
Weight
ATEX Directive: (2014/34/EU)
Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Directives
14.3.
Tightening torques for screws
Table 42:
Tightening torques for screws
Tightening torque [Nm]
Threads
Strength class
A2-80/A4-80
A2-70/A4-70
10
7.4
M6
24
18
M8
48
36
M10
82
61
M12
200
150
M16
392
294
M20
1,057
1,015
M30
2,121
1,769
M36
98
SAEx 07.2 – SAEx 16.2/SAREx 07.2 – SAREx 16.2 Control unit: electronic (MWG)
Technical data
ACExC 01.2 Non-Intrusive HART