Audio Pole EN 54-24 User Manual Download Page 4

1.

Be sure to note the following polarities when multiple speakers are
used in the same location. Incorrect connections could result in no
bass output or decreased volume.

2.

Connect the correct (+) and (COM) polarity terminal as per mark on
the block.

Connections

3

4

Handling Precautions

Dimensions

4

Impedance Selection

The speaker comes with a factory wiring connected to the value 20 W
(100 V) of the transformer.
A lower value of the power can be set using the other available
terminals. Connection points are shown on the plate of the transformer
(Attention, 70 V and 100 V connections are not identical).

When several speakers are used, they must be connected in parallel
and their cumulative power must be less than the nominal power of the
amplifier.

Summary of Contents for EN 54-24

Page 1: ...CEILING SPEAKER POLE 116ENP USER MANUAL EN 54 24...

Page 2: ...source Avoid exposure to rain or moisture In the case of long period of storage prior to installation hold the speaker in protected environment 2 This symbol indicates that the disposal of this produc...

Page 3: ...er can easily be mounted in the ceiling with its spring clips A multi points output transformer allows an optimal fit for different powers and improves the sound quality by equalization effect POLE 11...

Page 4: ...cautions Dimensions 4 Impedance Selection The speaker comes with a factory wiring connected to the value 20 W 100 V of the transformer A lower value of the power can be set using the other available t...

Page 5: ...uired power by modifying if necessary the transformer connections 5 3 Pass the input cables through the hole in the dome by drilling the plastic protection cap then connect them to the terminal block...

Page 6: ...g Once the ceiling set pull down the spring clips Then check the proper stowage of the speaker Spring clips down Hole in the ceiling 5 To remove the speaker lift the spring clips and then let the spea...

Page 7: ...d based on EN 54 24 Frequency Response 95 Hz 20 kHz 10 dB Maximum Sound Pressure Level 91 dB 20 W 4 m 100 Hz 10 kHz pink noise according to EN 54 24 101 dB 20 W 1 m 100 Hz 10 kHz pink noise converted...

Page 8: ...luntary or accidental and suffered no deterioration or modification other than those described here or explicitly authorized by AUDIOPOLE 3 All modifications or repairs have been carried out by an aut...