5.6 ELECTRICAL CONNECTION
We need to have an outlet of 230 v - 50 Hz with earth connection, capable of
supporting at least 490 W of power during the ignition, and with its own circuit
breaker.
The system must be suitable for the electrical power of the stove.
The stove is supplied with a power cable that needs to be connected to a
230V 50Hz outlet.
The connection of the outlet to the back of the stove is shown in the figure.
Ensure that the main switch of the stove is at 0, and then connect the power cord first behind the stove and then
into an electrical outlet on the wall. The main switch located on the back wall will be activated only when the stove
is lit; otherwise, it is advisable to remove the cable from the stove.
Maximum electrical absorption while ignition (6 min)
490 Wat
Electrical absorption (Wat)
120 Wat
Voltage and supply frequency
230 V / 50Hz
By law, the installation requires an earth connection and residual-current circuit breaker (RCCB). Make sure the
power cord, in its definitive position, does not make contact with hot parts.
The outlet must be single-phase, neutral and with earth connection.
If the voltage is not sinusoidal (such as generators or other equipment), some errors of the
stove could taken place.