INSTRUCTIONS
Register Description
Bits
Details
8
0 = Parameter(s) have changed since last
parameter read
1 = No parameters have changed
3
9
0 = Negative phase sequence
1 = Positive phase sequence
10 to 15
Reserved
40605
Current
0 to 13
Average rms current across all three phases
14 to 15
Reserved
40606
Current
0 to 9
Current (% motor FLC)
10 to 15
Reserved
40607
Motor
temperature
0 to 7
Motor thermal model (%)
8 to 15
Reserved
40608
Power
0 to 11
Power
12 to 13 Power scale
0 = Multiply power by 10 to get W
1 = Multiply power by 100 to get W
2 = Power (kW)
3 = Multiply power by 10 to get kW
14 to 15
Reserved
40609
% Power factor 0 to 7
100% = power factor of 1
8 to 15
Reserved
40610
Voltage
0 to 13
Average rms voltage across all three phases
14 to 15
Reserved
40611
Current
0 to 13
Phase 1 current (rms)
14 to 15
Reserved
40612
Current
0 to 13
Phase 2 current (rms)
14 to 15
Reserved
40613
Current
0 to 13
Phase 3 current (rms)
14 to 15
Reserved
40614
Voltage
0 to 13
Phase 1 voltage
14 to 15
Reserved
40615
Voltage
0 to 13
Phase 2 voltage
14 to 15
Reserved
40616
Voltage
0 to 13
Phase 3 voltage
14 to 15
Reserved
40617
Parameter list
version number
0 to 7
Parameter list minor revision
8 to 15
Parameter list major version
Modbus RTU Card (710-16499-00B)