INSTALLATION
4.3
Inputs
CAUTION
The control inputs are powered by the soft starter. Do not apply external
voltage to the control input terminals.
NOTE
Cables to the control inputs must be segregated from mains voltage and
motor cabling.
B4 B5 10 11 12 13 14 15
21 22
B4, B5 Motor thermistor input
10, 11 Reset input
11, 12 Start/stop input
13, 14 Programmable input A (default = Input Trip (N/O))
13, 15 Programmable input B (default = Input Trip (N/O))
USB port
Motor Thermistor
Motor thermistors can be connected directly to the EMX4e. The soft starter will trip
when the resistance of the thermistor circuit exceeds approximately 3.6 k
Ω
or falls
below 20
Ω
.
The thermistors must be wired in series. The thermistor circuit should be run in
screened cable and must be electrically isolated from earth and all other power and
control circuits.
NOTE
The thermistor input is disabled by default, but activates automatically
when a thermistor is detected. If thermistors have previously been
connected to the EMX4e but are no longer required, use the Thermistor
Reset function to disable the thermistor. Thermistor Reset is accessed via
the Setup Tools.