INSTALLATION
4.6
Power Terminations
The power input and output terminals are at the bottom of the unit.
•
Models EMX4e-0024B~EMX4e-0135B use cage clamps. Use only copper
stranded or solid conductors, rated for 75 ºC or higher.
•
Models EMX4e-0184B~EMX4e-0580B use busbars. Use copper or
aluminium conductors, stranded or solid, rated for 60 ºC/75 ºC.
EMX4e-0024B~EMX4e-0135B
05
96
6.
E
Cable size:
6-70 mm
2
(AWG 10-2/0)
Torque: 4 Nm (2.9 ft-lb)
Torx T20 x 150
Flat 7 mm x 150
11
29
0
.A
14 mm (0.55 inch)
EMX4e-0184B~EMX4e-0250B
EMX4e-0352B~EMX4e-0580B
19 Nm (14.0 ft-lb)
66 Nm (49.0 ft-lb)
6 mm
20 mm
9 mm
(M8)
17045.
A
6 mm
34 mm
13 mm
(M12)
17047.
A
NOTE
If the installation requires large diameter cables, it is possible to complete
each termination with two smaller cables, one on each side of the busbar.
NOTE
Some units use aluminium busbars. When connecting power terminations,
we recommend cleaning the surface contact area thoroughly (using an
emery or stainless steel brush) and using an appropriate jointing
compound to prevent corrosion.