ELECTRICAL INSTALLATION
710-02408-00H
CSXi
Page 3
3.1
Power Terminations
L1/1, L2/3, L3/5, T1/2, T2/4, T3/6
mm2 (AWG)
A1, A2, A3, 01, 02, B4,
B5, 13, 14, 23, 24 mm2
(AWG)
007 - 030
037 - 055
075 - 110
007 - 110
1
0
4
2
7
.A
10 - 35
(8 - 2)
1
0
4
2
8
.A
14 (0.55)
mm (inch)
25 - 50
(4 -
1/10)
1
0
4
2
8
.A
14 (0.55)
mm
(inch)
N.A.
26
(1.02)
11
(0.43)
Ø 8.5
(0.33)
10
4
29
.A
mm
(inch)
0.14 - 1.5
(26 - 16)
1
0
4
2
8
.A
6 (0.24)
mm (inch)
Torx (T20)
3 Nm
2.2 ft-lb
Torx (T20)
4 Nm
2.9 ft-lb
N.A.
N.A.
7 mm
3 Nm
2.2 ft-lb
7 mm
4 Nm
2.9 ft-lb
N.A.
3.5 mm
0.5 Nm max
4.4 in-lb max
3.2
Control Voltages
CSX
i
soft starters can be supplied in either of two control voltage configurations:
CSXi-xxx-xx-C1 .... 110-240 VAC (+ 10% / - 15%) or 380-440 VAC (+ 10% / - 15%)
CSXi-xxx-xx-C2 .... 24 VAC/VDC (± 20%)
WARNING
Always apply control voltage before (or with) mains voltage.
CAUTION
With 24 VAC/VDC use contacts rated for low voltage and low current (gold flash or similar).
3.3
Control Circuits
Two-wire
Three-wire
Start/stop. To reset a trip, open then close 02.
Start.
Stop. To reset a trip, open then close 02.
3
Electrical Installation