SYL-2372 PID TEMPERATURE CONTROLLER 

INSTRUCTION MANUAL 

Version 1.7 (June 2021) 

 

Caution

  

 

This  controller  is  intended  to  be  used  with  proper  safety  equipment  under 
normal  operating  conditions.  Failure  or  malfunction  of  the  controller  may 
result  in  personal  injury  or  damage  to  the  equipment  or  other  property, 
devices (limit or safety controls) or systems (alarm or supervisory) intended 
to  warn  of  or  protect  against  failure  or  malfunction  of  the  controller.  To 
prevent harm to you and to the equipment, this item must be incorporated 
into  and  maintained  as  a  part  of  the  control  system  under  the  appropriate 
environment. 

 

Installing  the  rubber  gasket  supplied  will  protect  the  controller  front  panel 
from dust and water splash (IP54 rating). Additional protection is needed  for 
higher IP rating. 

 

This  controller  carries  a  90-day  warranty.  This  warranty  is  limited  to  the 
controller only. 
 

1.

 

Specifications 

Input type 

Thermocouple (TC): K, E, S, N, J, T, B, WRe5/ 26; 
RTD (Resistance Temperature Detector): Pt100, Cu50 
DC Voltage: 0~5V, 1~5V, 0~1V, -100~100mV, -
20~20mV, -5~5V, 0.2~1V 
DC current: 0~10mA, 1~10mA, 4~20mA. (Use external 
shunt resistor for higher current) 

Input range 

Please see section 4.7 for detail. 

Accuracy 

±  0.2% Full scale: RTD, linear voltage, linear current and 
thermocouple input with ice point compensation or Cu50 
copper compensation. 
0.2% Full scale or ±  2 ºC: Thermocouple input with 
internal automatic compensation. 
Note: For thermocouple B, the measurement accuracy of 
±  0.2% can only be guaranteed when input range is 
between 600~1800 ºC. 

Response time 

 0.5s (when FILt = 0) 

Display resolution 

1° C, 1° F; or 0.1° C 

Control mode 

Fuzzy logic enhanced PID control 
On-off control 
Manual control 

Output mode 

Zero crossing SSR, 100-400VAC/2A 

Alarm output 

Relay contact (NO): 250VAC/1A, 120VAC/3A, 24V/3A 

Alarm function 

Process high alarm, process low alarm, deviation high 
alarm, and deviation low alarm 

Manual function 

Automatic/Manual bumpless transfer 

Power supply 

85~260VAC/50~60Hz 

Power 
consumption 

 5 Watt 

Ambient 
temperature 

0~50ºC, 32~122ºF 

Dimension 

48 x 48 x 100mm (W x H x D) 

Mounting cutout 

45 x 45mm 

 
 

2.

 

Available Configurations 

All the models listed in Table 1 are 1/16 DIN size with dual-alarm outputs. 

 
Table 1. Controller models. 

Model 

Output mode 

Ramp/soak option 

SYL-2372 

Zero crossing SSR  

No 

SYL-2372P 

Zero crossing SSR  

Yes 

 

3.

 

Terminal Wiring 

 

 
 
 
 
 
 
 
 
 

 

Figure 1. Wiring diagram. 

 

3.1 Sensor connection 

Please refer to Table 3 for the input sensor type (Sn) setting codes. The initial 
setting for input is for a K type thermocouple. Set Sn to the right sensor code if 
another sensor type is used. 

 
3.1.1 Thermocouple 

The thermocouple should be connected to terminals 4 and 5. Make sure that 
the polarity is correct. There are two commonly used color codes for the K type 
thermocouple.  US  color  code  uses  yellow  (positive)  and  red  (negative). 
Imported  DIN  color  code  uses  red  (positive)  and  green/blue  (negative).  The 
temperature reading will decrease as temperature increases if the connection 
is reversed. 
 
When using ungrounded thermocouple that is in touch with a large conductive 
subject, the electromagnetic field picked up by the sensor tip might be too large 
for the controller to handle, the temperature display will change erratically. In 
that case, connecting the shield of thermocouple to terminal 5 (circuit ground of 
the  controller)  might  solve  the  problem.  Another  option  is  to  connect  the 
conductive subject to terminal 5.  
 

3.1.2 RTD sensor 

For a three-wire RTD with standard DIN color code, the two red wires should 
be connected to the terminals 3 and 4. The white wire should be connected to 
terminal 5. For a two-wire RTD, the wires should be connected to terminals 4 
and 5. Jump a wire between terminals 3 and 4. Set controller input type, Sn to 
21. 
 

3.1.3 Linear input (V, mV, mA or resistance)  

V and mA current signal inputs should be connected between terminals 2 and 
5.  Terminal  2  is  positive.  mV  signal  inputs  should  be  connected  between 
terminals 4 and 5. Terminal 4 is positive. For resistance inputs, short terminals 
3 and 4, then connect resistance inputs between terminals 4 and 5.   
 

3.2 Power to the controller 

The power cables should be connected to terminals 9 and 10. Polarity does not 
matter. This controller can be powered by 85-260V AC power source. Neither a 
transformer nor jumper is needed to wire it up. For the sake of consistency with 
the wiring example described later, we suggest you connect the hot wire to 
terminal 9 and neutral to 10. 
 
 

Instruction Manual

 

 

1
2
3

13 14 6

7
8
9

10

4
5

AL1 AL2

AC

85~260V

OUT

Model SYL-2372, SYL-2372P

RTD

R

R

W

TC

mA

V

-

+

+

Summary of Contents for SYL-2372

Page 1: ...16 DIN size with dual alarm outputs Table 1 Controller models Model Output mode Ramp soak option SYL 2372 Zero crossing SSR No SYL 2372P Zero crossing SSR Yes 3 Terminal Wiring Figure 1 Wiring diagram...

Page 2: ...tor It lights up when AL1 relay is on Display alarm 1 AL2 indicator It lights up when AL2 relay is on Display alarm 2 A M indicator The light indicates that the controller is in manual mode For the co...

Page 3: ...nge Initial Setting Remarks ALM1 Process high alarm 1999 9999 C or F 100 See 4 4 1 ALM2 Process low alarm 1999 9999 C or F 50 Hy 1 Deviation high alarm 0 9999 C or F 9999 Hy 2 Deviation low alarm 0 99...

Page 4: ...ong as 20 seconds Users can reduce the cycle time to avoid the delay 4 4 3 Control mode At At 0 on off control It works like a mechanical thermostat It is suitable for devices that do not like to be s...

Page 5: ...perature display resolution is 1 C F dP 1 temperature display resolution is 0 1 C The 0 1 degree resolution is only available for Celsius display The temperature will be displayed at the resolution of...

Page 6: ...er output User can switch from manual control mode to PID control mode A M 1 PID control mode Controller decides the percentage of power output User can switch from PID mode to manual mode A M 2 PID c...

Page 7: ...a 24V valve TC N 1 13 14 6 2 3 4 5 7 8 9 10 L 120VAC Fuse SYL 2372 S 24VAC Solenoid valve Figure 8 SYL 2372 with thermocouple input This is a typical wiring set up for a 24V gas hot water valve or a c...

Page 8: ...ire If the display shows ambient temperature the thermocouple is defective If it still displays oral check the input setting Sn to make sure it is set to the right thermocouple type If the Sn setting...