4.1.2 RTD sensor
For a three-wire RTD with standard DIN color code, the two red wires should be 
connected to the terminals 9 and 10. The white wire should be connected to 
terminal 8.
For a two-wire RTD, the wires should be connected to terminals 8 and 9. Jump 
a wire between terminals 9 and 10.
Set controller input type, Inty, to P100 (1° resolution) or P10.0 (0.1° resolution).
4.2 Power to the controller
This controller can be powered by 12-30V DC or 12-18V AC.  The power input 
cables are connected to terminal 1 & 2. For DC power source, terminal 1 is 
positive and 2 is negative. For AC power source, a diode is needed to be wired 
in serial with the AC power source to the controller terminals (to convert AC to 
DC).  
4.3 Control output connection

Two control output options are offered by this controller. (1) The SSR control 

output provides an 8V DC signal that can control up to 4 SSRs in parallel. (2) 
The J2 relay output can be used to turn on a contactor or a solenoid valve. It  
can also drive a small heater directly if the heater draws <3 Ampere. F o r 
application that needs two control outputs, such as one for heating and other for 
cooling, J1 relay can be used for the second output with on/off control mode. 
Please note J1 can’t be used for main control output. Both J1 and J2 can be 
used as alarm output if they are not used as control output.

4.3.1 Connecting the load through SSR
Connect the terminal 7 to the negative input and terminal 6 to the positive input 

of the SSR. Set the system output configuration, outy, to 2, 3 or 6 - depending 
on the control mode used. See Figure 10 for details.

4.3.2 Connecting the load through the built-in relay
J1 relay is for alarm output only. Assuming the controller and the load are 

powered by a 12V DC source, jump a wire between terminals 2 and 14. Connect 
terminal 13 to one lead of the load and terminal 1 to the other lead of the load. 
Set the system output configuration, o uty, to 1, 4, or 5 - depending on the 
control mode used. Please see Figure 

11, 12 and 13 

for examples.

4.4 For first time users without prior experience with PID controllers,  the 
following notes may prevent you from making common mistakes:

4.4.1 The power to the heater does not flow through terminal 1 and 2 of the 
controller. The controller consumes less than 2 watts of power. It only 
provides a control signal to the relay. Therefore, 20 gauge wires are sufficient  
for providing power to terminal 1 and 2. Thicker wires may be more difficult to 
install.
4.4.2 The J1, J2 relay are  “dry single pole switches”. They do not provide 
power by themselves. Figure

 

11 shows how it is wired when providing a 12V 

output (or when output has the same voltage as the power for controller). If 
the load of relay requires a different voltage than that for the controller, an 
additional power source will be needed (Please see the alarm wiring of Figure 
10 and controller output J2 of Figure 12 for examples)

.

4.4.3 SSR output power does not come from the input of the SSR. The output 
of the SSR is a single pole switch between terminal 1 and 2 of the SSR. The 
input of the SSR is for control, or triggering, the SSR. (Please note we are 
talking about the SSR itself, not the SSR control output of the controller). 
Figure 10 shows how the SSR output should be wired. When switching a 
North American 240V AC power, the heater will be live even when the SSR is 
off. User should install a double-pole mechanical switch to the power input.

5. Parameter Setting 

For safety reasons, the controller parameters are divided into three groups 
with different pass codes. You should only give the code to those who have 
the responsibility and knowledge of how to properly change it. Code 0089 
contains the parameters for system configuration that may need to change 
during the initial set up. Code 0036 contains the parameters for tuning 
performance. Code 0001 is for controlling temperature and alarm settings.

The system configuration parameter s  are listed in table 1.

 

To change the  

parameters, press       , enter code “0089” and press       again. Then, follow 
the flow chart in Figure 3.

SET

SET

Figure 3. System setup flow chart

Note 2. The value of outy determines the control mode. When it is set to: 
0 - Relay J1, J2 as alarm output; SSR output disabled; 
1 - Relay J1 as alarm output; J2 as PID controlled relay contact output; SSR
    output disabled;. 
2 - Relay J1, J2 as alarm output; SSR PID control output; 
3 - Relay J1, J2 as alarm output; SSR On/off control output; 

Table 1. System configuration parameters 

(1) Press         to enter setting mode

 

(2) Press       

     and        to enter parameters

 

(3) Press        to confirm

 

(4) Press        or       to select the new parameter. 

>

SET

SET

Table 2. Temperature sensor code

Note 1. The controller is preset for K type thermocouple input. If any other type 
of sensor is used, the Inty value needs to be changed to the corresponding  
symbol as shown in Table 2.

Description

Setting Range

Initial  Note

Inty

Inty

Input Sensor Ty pe

See table2 

K

1

outy

outy

Control Output Mode

0, 1, 2, 3, 4, 5, 6

2

2

Hy

Hy

Hy steresis Band

0~9999

3

3

Atdu

Atdu

Autotune Offset

0~200(deg)

10

4

PSb

PSb

Input Offset

-100~100(deg)

0

5

rd

rd

Control Function

0: heating 1: Cooling

0

CorF

CorF

Display  Unit

0: °C  1:°F     

1

End

End

Ex it

Code

Description

Working Temperature Range

t

t

TC, Ty pe T

-200~400 °C; -320~752 °F

r

r

TC, Ty pe R

-50~1600 °C; -58~2900 °F

j

J

TC, Ty pe J

-200~1200 °C; -320~2200 °F

WRE

WRE

TC, WRe3/25

0~2300 °C; 32~4200 °F

b

b

TC, Ty pe B

350~1800 °C; 660~3300 °F

s

s

TC, Ty pe S

-50~1600 °C; -58~2900 °F

k

k

TC, Ty pe K

-200~1300 °C; -320~2400 °F

e

e

TC, Ty pe E

-200~900 °C; -320~1650 °F

P10

.

0

P10.0

RTD, Pt100

-99.9~600.0 °C; -99.9~999.9 °F

P100

P100

RTD, Pt100

-200~600 °C; -320~1100 °F

Cu50

Cu50

RTD, Cu50

-50.0~150.0 °C; -60~300 °F

Sy mbol

               

Operation Mode

0089

Enter Code

Parameter Display

Output mode selection

inty

X

    

XXXX

X

XXXX

outy

atdu

psb

Hysteresis Band

Input offset

SET

SET

SET

SET

SET

SET

SET

X

rd

Heating/Cooling

SET

X

corf

Display Unit(C/F)

end

SET

SET

SET

SET

SET

Input Sensor  Selection

XXXX

SET

SET

XXXX

HY

SET

Autotune offset

SET

2018.07

P2/5

5.1 System Configuration Parameters (accessed by code 0089)