Auber Instruments SYL-2362B Instruction Manual Download Page 1

 SYL-2362B PID TEMPERATURE CONTROLLER 

INSTRUCTION MANUAL 

Version 2.6

AUBER INSTRUMENTS

WWW.AUBERINS.COM

2018.07

P1/5

Instruction Manual

2. Specification

Input type

Thermocouple (TC): K, E, S, R, J, T, B, WRe3/25
RTD(Resistance temperature detector): Pt100, Cu50

Input range

See table 2

Display

Dual lines, four digits, °F or °C

Display resolution

1°C, 1°F; or 0.1°C, 0.1°F with Pt100

Accuracy

±0.2%  or ±1 unit of full input range

Control mode

PID, On-off. Limit, Manual

Output mode

Relay contact: 3A at 240VAC, SSR: 8VDC, 40 mA.

Alarm

Process high/low alarm

Power consumption

<2 Watt

Power supply

12-30V DC, 12-18V AC (with diode)

Sample rate

4 samples/sec

Operating condition

0 ~ 50 °C, 

85% RH

Mounting cutout

45 x 45 mm

Dimension

48x48x75mm (1/16 DIN)

 3. Front Panel and Operation 

Figure 1. Front panel

4. Terminal Wiring (back view) 

1. Features



The PID control with artificial intelligent enhancement for precision 
temperature control. 



Auto-tuning function can find the best PID parameter automatically. 



On/off control mode for refrigerator, motor and solenoid valve control 
application.



Bumpless transfer between Auto and Manual control.



Limit control for safety protection and special applications. 



The output can be set for SSR output control or relay contactor control by 
the user. 



Two contact relays can be configured as one PID and one alarm output, 
dual alarm outputs, or dual On/off control. 



Support 10 different types of commonly used temperature sensor inputs. 

 AL-1 Relay J1 output indicator

     AL-2 Relay J2 output indicator
     AT/M- On for manual mode. Blinking during auto-tuning process 
     OUT- SSR output indicator 

 Value increment/Select next parameter

 Value decrement/Select previous parameter

 Auto tuning/Digit shift

 Set/Confirm/Manual Auto switching/Reset (for Limit control mode) 

 Measured temperature, or, Process Value (PV) 

 Set temperature, or, Set Value (SV) 

6

7

8

9

10

11

12

13

14

1

2

3

4

5

+

-

SSR

J1

+ -

J2

RTD

TC

        Power

        Input

Figure 2. Wiring diagram

R

R

W

NO

NC

NC

NO

4.1 Sensor connection
4.1.1 Thermocouple
The thermocouple should be connected to terminals 9 and 10. Make sure that 
polarity is correct. There are two commonly used color codes for the K type 
thermocouple. US color code uses yellow (positive) and red (negative). 
Imported DIN color code uses red (positive) and green/blue (negative). The 
temperature reading will decrease as temperature increases if the connection 
is reversed.

to

 termin

al 11

+

-

    

Caution

 



 This controller is intended to control equipment under normal operating 
conditions. If failure or malfunction of it could lead to an abnormal operating 
condition that could cause personal injury or damage to the equipment or 
other property, other devices (limit or safety controls) or systems (alarm or 
supervisory) intended to warn of or protect against failure or malfunction of 
the controller must be incorporated into and maintained as part of the 
control system.



Installing the rubber gasket supplied will protect the controller front panel 
from dust and water splash (IP54 rating). Additional protection is needed  
for higher IP rating.



This controller carries a 90-day warranty. This warranty is limited to the 