Auber Instruments DSPR300 Instruction Manual Download Page 7

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2021.05                                                                    

   

                                                              P7/9 

 

Table 5. Conditions of Relays Become Active or Inactive.   

Relay 
Mode 

Mashing Mode 

Boiling/Distilling Mode 

Active 

Inactive 

Active 

Inactive 

Process 

Alarm 

PV < AL or 

PV 

 AH 

AL 

 PV < 

AH 

PV < AL or 

PV > AH 

AL < PV < 

AH 

Deviation 

Alarm* 

PV 

 (SV 

+ AH), or 

PV < (SV - 

AL) 

(SV - AL) 

 PV < 

(SV + AH) 

NA 

NA 

Acceleration  PV < SV** 

PV 

 SV 

PV < bAST 

PV 

 bAST 

Timer*** 

PV < tSP, 

or Preset 

Mashing 

Timer (t) is 

reached 

PV > tSP 

PV < btSP, or 

Preset Boiling 

Timer (bt) is 

reached 

PV 

 btSP 

 

Note *: Deviation Alarms are not available in Boiling Mode because there is no 
temperature set point.  
 
Note **. The precise turning off point is determined by the AI program. 
 
Note ***: Timer function 

tF

 should be set to ON if user wants to set Relay 2 to 

Timer mode (

RL2

 = Time). If timer function 

tF

 was set of OFF, Relay 2 will remain 

active.    
 

Note 13: Lgc (Relay Logic

), determines relay status before and after the alarm 

conditions are met. It can be set to Logic Close (

RL-C

) or Logic Open (

RL-O

). 

When a relay is set to 

RL-C

, the relay is a NO relay, it stays open when it is 

inactive; the relay contacts close (pull-in) when alarm conditions are met. When 
a relay is set to 

RL-O

, the relay is essentially a NC relay, it stays closed when it 

is inactive; the relay contacts open up (drop-out) when alarm conditions are met. 
For most applications, the relay should be set to Logic Close (

RL-C

), which is 

the default setting. The Logic Open (

RL-O

) configuration is useful if user want to 

turn on a device when the temperature is not in the alarm zone.  
 

Note 14: LAt (Latching, Pulsing, or Non-Latching Relay Action),

 determines 

the relay actions when alarm conditions are met and/or then removed. It can be 
set to 

Y

 for Latching Mode, 

PUL

 for pulsing mode, or 

N

 for Normal Mode. 

 
When 

LAt

  is set  to 

Y

  (Latching  Mode),  the  relay  action  is  latched.  It  will  not 

release even if the alarm condition is removed. To release the relay, user must 
reboot the controller or use the Reset Key to cancel the relay action (see note 
20 for details).   
 
When 

LAt

 is set to 

PUL

 (Pulsing Mode), the replay action is a timed single pulse. 

When the alarm condition is met, relay will be activated only for a pre-determined 
period of time. User can set the pulse duration by the 

AP

 parameter in the menu 

of  alarm  settings;  it  ranges  from  1  to  100  seconds.  This  feature  is  useful  in 
situations where a user only need to ring the buzzer for a short time or want to 
drive an external load for a fixed amount of time duration.  
 
When 

LAt

 it is set to 

N

 (Non-Latching), the relay action  will follow the  alarm 

condition. The relay stops its action when the alarm condition is removed. 
 

Note  15:  SiL  (Relay  Silence, 

also  called

  Alarm  Suppression)

,  determines 

whether a relay action should be suppressed when controller is just powered up. 
When SiL is set to Y, Relay Silence is enabled; when SiL is set to N,  Relay 
Silence is disabled.  
 
Relay Silence/Alarm Suppression is only supposed to work when: 1) controller 
is just powered up, and 2) the condition that deactivates the Relay Silence is not 
met yet. This feature is available in all relay modes, however, the deactivation 
condition varies.  
 
 
Table 6. Conditions to Deactivate the Relay Silence/Alarm Suppression.  

Relay Mode 

Mashing Mode 

Boiling Mode 

Process Alarm 

PV ≥ SV

 

PV ≥ 

btSP 

Deviation Alarm 

PV ≥ SV

 

NA 

Acceleration 

PV ≥ SV

 

Mashing Set Point (SV) 

Timer* 

NA 

NA 

 
For example, if a controller is working in mashing mode and the relay is set as a 
process alarm, then alarm suppression will apply to the low limit alarm until the 
process temperature reaches the mashing temperature. For another instance, if 
a controller is working in boiling/distilling mode, Relay 1 

RL1

 = 

ACC

Lgc1

 = 

LC-

C

LAt1

 = N

.

 If 

SiL1

 = 

N,

 Relay 1 should pull-in when 

PV

 < 

bAST

 and drop-out 

when 

PV

 >= 

bAST

. But when 

SiL1

 = 

Y

, Relay 1 will not be activated when 

PV

 < 

bAST

 unless PV has reached mashing temperature.    

 
This feature is useful for the following two situations: A) When a relay is set as 

low limit alarm or deviation alarm, and you don’t want the relay to pull in when 

you just power up the controller as the start-up temperature will be in the alarm 
zone. B) When  Relay 2 is set to Timer Mode and it is supposed  to trigger a 
buzzer when the timer is up. Without Alarm Suppression, the relay would pull in 
when controller is just powered up before the timer starts counting. 
 

Note 16: Function Key 

There  are  two  function  k

eys  named  “

A

”  and  “

B

  which  can  be  used  to 

reset/cancel the action of the corresponding relays when they are activated. Key 

A

” on the lower left corner is for Relay 1, Key “

B

” on the lower right corner is for 

Relay 2. They only work in Latching Mode or Non-Latching Mode (

LAt

 = 

Y

 or 

N

), 

and they have no effect in Pulsing Mode (

LAt

 = 

PuL

). By default, Function Keys 

are disabled. To enable these two keys, set the parameter “

Key

”, which is the 

last parameter listed in the menu of system configuration, to “on” (

Key

 = 

on

).  

 
For a relay whose logic mode is set to Logic Close (

Lgc

 = 

RL-C

), press the 

function key when the relay is activated (close) will cancel the relay action, i.e., 
the relay will drop out (open). For a relay whose logic mode is set to Logic Open 
(

Lgc

  = 

RL-O

),  press  the  function  key  when  the  relay  is  activated  (open)  will 

cancel the relay action, i.e., the relay will pull in (close). 
 
 

7.3 Parameters in Alarm Settings 

 

In the menu of alarm settings, there are four sets of parameters for each relay: 

AH

AL

HY

 and 

AP

.  

 
Table 7. Alarm Parameters Listed in Alarm Setting Menu. 

Alarm Configuration (Alarm parameters part 2) 

Display 

Code

 

Description

 

Setting Range

 

Initial 

Setting

 

Remark

 

AH1 

AH1 

Alarm 1 high limit 

OFF, 1 ~ 9999 

OFF 

Note 17 

AL1 

AL1 

Alarm 1 low limit 

OFF, 1 ~ 9999 

OFF 

Note 18 

HY1 

HY1 

Alarm 1 hysteresis 

band 

0.1-100.0 

0.3 

Note 19 

AP1 

AP1 

Alarm 1 pulse length 

1-100 

Note 20 

AH2 

AH2 

Alarm 2 high limit 

OFF, 1 ~ 9999 

OFF 

Note 17 

AL2 

AL2 

Alarm 2 low limit  

OFF, 1 ~ 9999

 

OFF 

Note 18 

HY2 

HY2 

Alarm 2 hysteresis 

band 

0.1-100.0 

0.3 

Note 19 

AP2 

AP2 

Alarm 2 pulse length 

1-100 

Note 20 

 
 

Summary of Contents for DSPR300

Page 1: ...ill return back in 2 seconds after you stop the adjustment 4 AL1 indicator This red LED indicates the status of Relay 1 AL1 When it is on the relay is closed when it is off the relay is open 5 AL2 ind...

Page 2: ...splay mode 3 Parameter settings Press down and hold the knob for 5 seconds to enter the display mode 3 Please check section 6 for details 5 Operation 5 1 Operation mode selection This controller offer...

Page 3: ...zero see section 6 3 for details For how to set up the boiling mode please read section 6 3 6 Control Parameters Parameters are divided into four groups figure 5 MASH for mashing control BOIL for boil...

Page 4: ...ant End Figure 7 Flow chart of setting mashing parameters Note 6 Timer Function t tSP EO This timer function allows the controller to show the mashing time It makes a beeping sound when timed out and...

Page 5: ...termined by the bOUT When temperature rise to the bAST the output will automatically reduce to a lower level to prevent a messy boiling over The boiling over is caused by several factors including the...

Page 6: ...menu for system settings there are five pairs of parameters for configuring relays Table 4 Alarm Parameters in System Configuration System Configuration Alarm parameters part 1 Display Code Descriptio...

Page 7: ...Alarm Suppression is only supposed to work when 1 controller is just powered up and 2 the condition that deactivates the Relay Silence is not met yet This feature is available in all relay modes howev...

Page 8: ...Lgc1 RL_C LAt1 N AH1 200 AL1 100 and HY 3 temperature unit is F For the high limit alarm when the process temperature is greater and equal to 200 F the relay will pull in and when process temperature...

Page 9: ...Power supply for two buzzers is 120V AC AL1 buzzer is for temperature alarm AL2 buzzer is for timer alarm 10 Common sensor errors This regulator will display error message or incorrect temperature re...

Page 10: ...er Figure 5 Original AC sine wave is overlaid with SSVR output wave form The blue colored area shows the power output that has been blocked 2 Time proportional firing A fixed cycle time needs to be de...

Page 11: ...gnal drop to zero the AC power is blocked 3 Burst firing This method is similar to time proportional firing section 2 But in contrast to the time proportional mode where the SSR is fired once for each...

Page 12: ...eform overlaid The DSPR detects the frequency and phase of the AC power line so that the pulse width and firing time is synchronized with AC cycle Auber Instruments 5755 North Point Parkway Suite 99 A...

Reviews: