Aube Technologies Non-programmable Heat Pump Controller TH146-N-DE Installation Manual Download Page 4

TH146-N-DE 

      400-280-000-G                    9/22/06                    4/8

Configuration Menu

Item

Parameters

Display

Options

Default

Description

1

Temperature scale

°C / °F

°C

Select the temperature display format.

2

Balance point low

-30°C to 10°C

(-22°F to 50°F)

-10°C

(14°F)

Set the bP L value (see section 4.2).

3

Balance point high

-5°C to 30°C

(23°F to 86°F)

5°C

(41°F)

Set the bP H value (see section 4.2).

4

Defrost point

-10°C to 15°C

(14°F to 59°F)

10°C

(50°F)

During defrost, auxiliary heating is activated when the outside 
temperature is below the defrost point (see section 4.3).

5

Installation type

Ad / nr

Ad

Set according to the type of heat pump installation (see section
4.4). 
Ad (add-on): Use this setting when the indoor coils are located
downstream of the auxiliary heat source. This is generally the
case for add-on installations.
nr (normal): Select this setting when the indoor coils are located
upstream of the auxiliary heat source. This is generally the case
for new installations.

6

Cycles per hour

2 to 6

4

Allows you to select the number of cycles per hour. It is recom-
mended to use the default setting except in exceptional cases.

7

“Smart fan”

On / OF

OF

On: “smart fan” is On (see section 4.5).
OF: “smart fan” is Off.

8

Interstage delay

5 to 90 min.

10 min.

Set the interstage delay (see section 4.6).

9

Outdoor

 temperature display

On / OF

On

Select between displaying the outdoor temperature or display-
ing the indoor humidity level.
On: Displays the outdoor temperature.
OF (Off): Displays the indoor humidity level.

NOTE

: To display the outdoor temperature, the outdoor sensor

must be connected.

10

Humidifier

operating mode

HE / Fn

HE

HE (Heat): The humidifier can operate only when heating is 
activated.
Fn (Fan): The humidifier can operate as long as the fan is run-
ning.

NOTE

: The humidifier is disabled when cooling is activated.

11

Automatic humidity

 adjustment

On / OF

OF

Allows you to place the humidity adjustment to automatic mode.
On (automatic): The humidity level is automatically regulated by 
the controller according to the outdoor temperature to avoid 
condensation or ice formation on windows (see item 12).
OF (manual): The user manually sets the humidity level (see 
item 12).

12

Humidity setpoint

5% to 60%

5%

Set the desired humidity level. This parameter is available only 
when the humidity control is placed in manual mode (see item 
11).

Humidity offset

-9% to 9%

0%

Allows the user to apply an offset to the automatic humidity con-
trol. For example, the user can enter a negative offset if there is 
still ice formation or condensation on the windows. This param-
eter is available only when the humidity control is placed in 
automatic mode (see item 11). 

NOTE

: Only the humidity setpoint or humidity offset (item 12) is available when the controller is placed in user mode (SW2 switch).

Summary of Contents for Non-programmable Heat Pump Controller TH146-N-DE

Page 1: ...e or air outlet or stagnant air behind a door Do not install the console on a wall hiding air ducts nor expose it to direct sunlight NOTE If this controller replaces an existing thermostat the wires t...

Page 2: ...num and position it such that its aperture faces the air flow Connect the sensor to controller terminals PS and CS no polarity For more information refer to the instructions provided with the sen sor...

Page 3: ...outdoor tem perature sensor is not connected to the controller The auxiliary heat is activated during defrost except under the fol lowing conditions When the outdoor temperature is above the defrost p...

Page 4: ...r temperature display On OF On Select between displaying the outdoor temperature or display ing the indoor humidity level On Displays the outdoor temperature OF Off Displays the indoor humidity level...

Page 5: ...ion Diagram New Installation TH146 AC144 03 AC146 410 CT241 Humidifier Heat Pump Compressor Fault CT280 HP 2H1C Auxiliary Heat Defrost Fan Valve Red Yellow Green Dual Energy 16 18 AWG 16 22 AWG 16 22...

Page 6: ...V Transformer Dual Energy AC144 03 AC146 410 CT241 RC845 Humidifier Auxiliary Heating System Heat Pump CT280 HP 2H1C Red Compressor Valve Defrost Fault Furnace Fan Limit Yellow Green 16 22 AWG 16 22...

Page 7: ...aced in manual mode or in auto matic mode see page 4 item 11 Manual Adjustment In manual mode the user sets the humidity level 5 to 60 Automatic Adjustment In automatic mode the controller sets the hu...

Page 8: ...functions Aube shall repair or replace it at Aube s option If the product is defective i return it with a bill of sale or other dated proof of purchase to the place from which you purchased it or ii c...

Reviews: