Accessories
Connection to mutual chimneys
Examples of connection to chimneys
If you decide to connect boilers
ATTACK Plus
to mutual or separate chimney with natural exhaust,
mutual or separate chimney has to be projected exclusively by specialized worker in conformity with
valid norms for appliances with hermetic chamber, equipped with fan.
Moreover, it is necessary to keep following characteristics of mutual / separate chimneys:
- dimensionised by calculation method given in valid norms
- proof against flue gas, resistant against smoke and heat, proof against condensed water
- circular or quadrilateral diameter, vertical , without reductions
- with pipe, that takes hot flue gas out, they are adequately remote or isolated from flammable materials
- with connection to single appliance on 1 floor
- with connection to same appliances (or different, but all appliances only with forced flue gas outlet or
only with natural flue gas exhaust)
- without mechanical means for suction in main pipes
- with underpressure in all their length, in conditions of stationary operation.
- in their platform they have collection tank for solid material or eventual condense water, equipped with
metal door with airtight closing.
Connection to condense water outlet
Boiler is equipped with internal syphon for condence water outlet. By first installation, mount inspection
connection
(A)
. Mount flexible pipe of condense outlet
(B)
to outlet of boiler´s syphone by extending it
for 3cm approximately and fit it by fixing bolt. Fill syphone for 0,5l of water (2) approximately and
connect flexible pipe to outlet device (3).
Outlet of condense water
16
C
83
C
43
C
43