12 

MANU3610-01 

 ATS NETWORK TEST 

 
ATS NETWORK TEST is a two-part test.  The first allows the network wiring between the terminal and the host 
to be checked for open connections or wiring errors.  This test requires that the ATS RS232 Communication 
Adapter, which is plugged into the host, be unplugged and pins 2 & 3 of the adapter jumped together (a metal paper 
clip should do the trick).  Secondly, a local test can be performed on the terminal communication circuitry.  This 
test will work for both RS232 and RS485 installations (RS485 installations require an ATS 232/485 Converter and 
power supply).  To enter NETWORK TEST, press the ENTER key at the “

ATS NETWORK TEST

” prompt.  

The following message appears: 

SWITCH TEST SWITCH  

TO USE POSITION 

 

Place the switch on the back of the terminal into the Use position. The Series 3610 performs a network test in 
which the terminal sends data up to the host, via the network cabling. Since a temporary jumper was installed in the 
ATS RS232 Communication Adapter, the data will be looped back to the terminal. The following should appear: 
 

NETWORK TEST PASS 

ENTER TO RETEST 

 

To perform the local communication loop back, place the Test/Use switch back to the Test position and press the 
ENTER key. The following message should appear: 
 

NETWORK TEST PASS 

ENTER TO RETEST 

 
Remove the jumper from the RS232 Communication Adapter and secure it back into the host port.  Press the 
CLEAR key to advance to the next test. 
 

ATS BATTERY TEST 

 
The ATS BATTERY TEST checks the terminal battery backup option if installed.  To enter this test, press the 
ENTER key at the “

ATS BATTERY TEST

” prompt.  The following message should appear: 

 

BATTERY TEST PASS 

ENTER TO RETEST 

 

Note: If the battery backup option is not installed the battery test will fail. 

Press the CLEAR key to advance to the ATS DI-DO TEST. 
 

ATS DI-DO TEST 

 
The ATS DI-DO TEST is a two-part test that checks the terminal DATA IN/DATA OUT port connection by 
performing a loop back communication test on the port circuitry.  To enter the ATS DI-DO TEST: 
 
1. 

Press the ENTER key at the “ATS DI-DO TEST” prompt.  The following message should appear: 

 

SWITCH TEST SWITCH 

TO USE POSITION 

 
2. 

The enclosure must be opened to place the test switch into the Use position. 
Since no loop back jumper is installed during this phase of testing the following message will appear: 

 

DI-DO TESTING 

 

DI-DO TEST FAILED 

ENTER TO RETEST 

Summary of Contents for Accu-Time 3610 Series

Page 1: ...M ME EN NT TA AL LL LY Y S SE EA AL LE ED D T TI IM ME E A AN ND D D DA AT TA A C CO OL LL LE EC CT TI IO ON N T TE ER RM MI IN NA AL L Accu Time Systems Inc 420 Somers Road Ellington CT 06029 Tel 860...

Page 2: ...this manual may be reproduced or distributed in any form or by any means or stored in any database or retrieval system without Accu Time s prior written permission Accu Time Systems Inc makes no warr...

Page 3: ...3 MANU3610 01 ACCU TIME SERIES 3610 TABLE OF CONTENTS Introduction 1 Features 2 Specifications 3 Installation 4 ACCU RATE Diagnostics 9 Maintenance 14 Troubleshooting Guide 15 MANU3610 01 01...

Page 4: ...s can provide users with the flexibility to create a variety of options Reliability A Real Time Clock RTC provides 12 or 24 hour time formats with quartz precision An optional uninterruptible power su...

Page 5: ...ard RS232 or RS485 compatible On board ACCU RATE terminal set up and diagnostics package Custom keypad legends with software defined function keys Large 20 key tactile 4x5 matrix keypad 4 line x 20 ch...

Page 6: ...DI DO port and Auxiliary Serial Interface port Enclosure Molded fiberglass polyester sealed environmental housing for indoor outdoor use NEMA 4X approved Power 10 to 17VDC 12VDC 250 milliamps Nominal...

Page 7: ...lity up to 110 and down to 10 Fahrenheit With a second heater option the temperature range expands to 25 Fahrenheit The terminal should be mounted on a vibration free area Select a location which has...

Page 8: ...one before tightening the connector Power When terminal power is being supplied locally insure that a conventional 110VAC wall outlet 220VAC in Europe and other areas check local electrical code requi...

Page 9: ...e use of ATS Series 1000 Network Controllers allows up to five hundred and twelve 512 terminals on a single host communication port 12 VDC POWER SUPPLY MULTI CLOCK RS485 INSTALLATION COMMADAPTER DB25...

Page 10: ...the Series 3610 The supplied rubber tubing should be installed if the seal tight connectors do not properly secure either cable Place the jumper located at JP1 on the I O board to the NC position Figu...

Page 11: ...D P GND VDC P GND JP1 JP2 DC POWER RS232 485 Communication Board J1 J2 Figure 2 If power is not supplied through the communication cable plug power into PJ1 Ensure that the jumper JP1 is placed in the...

Page 12: ...he CLEAR key the user can step through the selections NOTE Test mode may be exited at any time by placing the Test Use switch back to the Use position and pressing the CLEAR key SELECTIONS ATS TEST MO...

Page 13: ...The message KEY INPUT ACCEPTED is displayed Each time the ENTER key is pressed an internal test of the terminal s communication port is performed If an error is detected the message COMM PORT FAIL wi...

Page 14: ...ed press the ENTER key to store the value and advance to the next parameter Address To change the terminal address 1 Press the CLEAR key to increment the address values from 01 to 32 2 When the desire...

Page 15: ...S ENTER TO RETEST To perform the local communication loop back place the Test Use switch back to the Test position and press the ENTER key The following message should appear NETWORK TEST PASS ENTER T...

Page 16: ...ARING MEMORY The green Valid LED will blink and the terminal will execute its power up sequence and return to the beginning of the Test Mode ATS AUX PORT TEST The ATS AUX PORT TEST will automatically...

Page 17: ...n device The only required procedure is periodic cleaning of the badge reader To clean the badge reader swipe a pre moistened isopropyl alcohol cleaning card through the reader several times Low usage...

Page 18: ...to the terminal blanking out Solution Check output of 12 volt DC power pack Solution Check for proper AC outlet voltage Possible cause Terminal does not go blank after unplugging the battery connector...

Page 19: ...supervisor Possible cause Keypad connector is unplugged Solution Test keypad in the ACCU RATE test mode If all solutions have been explored and the problem still exists contact the Accu Time Product S...