10.2 Three-wire system control mode
10.2.1 Parameter setting
According to the transducer, drag the motor’s rated nameplate data and conduct parameter setting for
parameters P0.07 and P0.08.
[P0.01]=0:
Parameter P0.01 is set up as 0. Select the panel potentiometer to confirm the frequency input.
[P0.03]=1:
Parameter P0.03 is set up as 1; select the external terminal control.
[P4.17]=2:
parameter P4.17 is set up as 2; select AO1 output as the voltage output.
[P4.19]=0:
parameter P4.19 is set up as 0, select AO2 output as frequency output.
[P4.08]=3:
parameter P4.08 is set up as 3, select external command mode as the three-wire mode 1.
[P4.00]=9:
parameter P4.00 is set up as 17, select input terminal 1 as three-wire operation control.
Other parameters are set up in accordance with the specific circumstance.
10.2.2 Basic wiring diagram
The basic wiring diagram of three-wire control mode is shown in Figure 10-2(for reference only)
Figure 10-2 The Basic Wiring Diagram of Three-wire Control Mode
10.2.3 Operating instructions
Close FWD, X1 and COM, forward motor(forward command); close REV, X1 and COM, reverse motor(reverse
command); disconnect FWD, X1 and COM simultaneously or disconnect one of them or close REV; close down
the transducer; disconnect FWD, X1 and COM simultaneously or disconnect one of them or close FWD, and
close down the transducer.
FWD
REV
COM
X1
Three phase breaker
TA
TB
Fault output
TC
AO1
AO2
GND
R
S
T
Voltmeter
Frequency
meter
U
V
W
E
M
5