background image

 

 

4.  Address coding: When a horn/strobe is coded, it is unnecessary to disassemble the wire connecting it 

with the host machine; online coding may be done. The specific method is as follows: Open the cover 

of the coding setup window, insert the output plug (a four-pin connector) of the coder into the address 

coding  socket  (the  socket  J2  in  Fig.2)  of  the  horn/strobe,  set  the  coder  with  the  coding  function, 

compile the correct address code and press the RUN key to complete the address coding. (Note: See 
the User’s Manual of the coder for detailed operation information.) 

  Warning: 

It is necessary to have “online coding” done when the system is powered off 

or related equipment may be damaged. 

5. 

Usage:  Do  not  connect  the  power  supply  until  the  address  of  the  horn/strobe  has  been  set  and 

confirmed and the fire alarm control panel has been properly connected. After the fire alarm control 

panel is successfully reset, the red status indicator (see Fig.3 for its location) of the  horn/strobe will 

blink.  After  the  horn/strobe  receives  an  operation  signal,  the  status  indicator  will  remain  lit  and  the 

horn/strobe will give both horn/strobe alarm signals. After the system is muted or reset, the horn/strobe 

will stop outputting horn/strobe alarm signals and the status indicator will start to blink again. 

VI. Installation and debugging 

A  special  base  is  necessary  during  the  installation  of  a  horn/strobe.  As  shown  in  Fig.4,  the  external 

dimensions of the special base are 142×84×10mm (L×B×H). The  horn/strobe is subject to a four-wire 

non-polarity connection: Terminals 1 and 2 are respectively connected with the ter24V and GND 

of the DC power supply terminals 3 and 4 are respectively connected with the terminals L1 and L2 of the 

signal bus of the fire alarm control panel. See Fig.5.

 

 Fire Alarm Control 

Panel 

+24V

GND

L1

L2

1 2 3 4

 

Fig.4                                                                                    Fig.5 

Specific installation and debugging methods: 

1. 

Use  two  M4  screws  to  fix  the  matched mounting  base  on  the  designated position  via  the  mounting  holes 

shown in Fig.4 (the installation may be done horizontally or vertically. Choose any two of the six mounting 

holes for installation) as instructed in the construction drawing and make sure the matched mounting base 

has been firmly installed. 

2. 

Disconnect the power supply of the fire alarm control panel and connect all the bases correctly in the way 

shown in Fig.5, which is a construction drawing. 

Note: When there are a lot of horns/strobes in a system, it is necessary to consider the loading capacity of 

the  power  supply  of  the  fire  alarm  control  panel.  An  external  DC24V  auxiliary  power  supply  might  be 

necessary at this time. Please follow the construction design drawings.       

3. 

Make sure the type of the horn/strobe matches the type given on the construction drawings. Use a coder to 

code the horn/strobe according to the address code marked on the construction drawings. 

Reviews: