13. Open Window Detection

Ensuring you don’t waste energy on heating the outside world, 
the heater is equipped with optional open / aclosed window 
detection. The heater recognises sudden drops in temperature 
when a window or a door is opened and turns the heating 
off to save energy. When the window is closed, the heater 
will automatically detect a temperature rise, and switch itself 
back on. Once enabled in the setup menu, the open window 
detection is fully automatic and does not require any human 
intervention to be activated.

Setting-up Open Window Detection

The system has been factory set to default time and 
temperature values. If necessary, all values can be adjusted. 
When the heating is on, open window detection sensor will 
automatically switch the heater off when it detects a fall in 
temperature of 2

o

C in less than 10 minutes (this temperature 

can be changed in menu 7 and time in menu 6). If a 
temperature rise of 2

o

C

 in less than 30 seconds is detected, 

the heater will switch itself back on (this temperature can be 
changed in menu 9 and time in menu 8).

14. Setup Menu

1. Press and hold TEMP and MODE together for 5 seconds.

2. The display will enter the setup menu.

3. Use TEMP and MODE to change a value.

4. Use TIME to scroll between the settings.

01 - Temperature calibration

The temperature reading has been factory calibrated but if 
for any reason it needs adjusting (better accuracy required, 
to suit different position in the room etc.), the reading can be 
recalibrated in 0.5 degrees steps.

02 - Change between degrees Celsius or Fahrenheit

03 - Set minimum temperature

(3.5 deg = frost protection) When this is set, the heater will 
operate in any mode should the room temperature fall below 
the set temperature.

04 - set maximum temperature

When this is set, the maximum temperature in any mode 
cannot exceed the limit.

05 - open window detection 0 = off, 1 = on

06 - 600 - open window detection time 600 seconds

07 - 2 - temperature drop of 2

o

C in the detection time

08 - 30 - closed window detection time of 30 seconds

09 - 2 -

o

 temperature rise of 2

o

C in the detection time

Summary of Contents for LST 500W

Page 1: ...s provided and has not been connected to an unsuitable electricity supply or subject to misuse neglect damage or modified or repaired by any person not authorised by the Company This guarantee is offered to you as an extra benefit and does not affect your legal rights The correct electricity supply voltageisshownontheratinglabelattachedtotheappliance Reasonablecarehasbeentakentoensurethatthisguide...

Page 2: ...e pole switch having 3mm gap on each pole A switched Fused Connection unit to BS 1363 Part 4 is a recommended mains supply connection accessory to ensure compliance with safety requirements applicable to fixed wiring installation Note When switched on for the first time the appliance may emit a slight smell This is purely the evaporation of a fluid used in the manufacturing process WARNING This ap...

Page 3: ...3 ...

Page 4: ... TEMP and MODE to set the temperature To amend the set temperature when in Boost mode simply activate the display by pressing any button Press TEMP then use TEMP and MODE to change the temperature Once the temperature is set you can leave the display to return to the main screen and the settings will be saved After 15 minutes the LST will return to previous operating mode 5 MAN Manual Mode In manu...

Page 5: ...ture press PROG to set temperature To add another programme repeat steps 2 10 The LST has a 7 day timerwith up to 6 programming steps available for each day In the programming you can set a start time and a temperature for each programme Each programme has to be used 9 Advance mode Press PROG from PROG mode to bring forward the next programme To clear advance mode press PROG 10 Heat symbol on the ...

Page 6: ...o C in less than 30 seconds is detected the heaterwill switch itself back on this temperature can be changed in menu 9 and time in menu 8 14 Setup Menu 1 Press and hold TEMP and MODE together for 5 seconds 2 The display will enter the setup menu 3 Use TEMP and MODE to change a value 4 Use TIME to scroll between the settings 01 Temperature calibration The temperature reading has been factory calibr...

Page 7: ... Operated Cut out Check that the fuse in the spur unit has not blown This can be done by replacing the fuse with another suitable fuse Should none of the above remedies work then telephone the helpline number shown in these instructions UK ONLY Do not attempt to repair the heater CUSTOMER HELPLINE Should you need any advice on the use of your new Atlantic Heat product please contact our Helpline A...

Reviews: