V. Use and engineering application 

1.  Fig.2 is the schematic diagram of the terminals of a display panel. 

地址编码窗口

接线端子

 

Fig.2 

Definitions of terminals: 

1  --+24V  (positive  input  terminal 
of the power supply) 
2 -- GND (negative input terminal 
of the power supply) 
3  --  OFF  (terminal  for  the 
normally  closed  contact  of  the 
relay) 
4  --COM  (common  terminal  for 
relay contacts) 
5 -- ON (terminal for the normally 
open contact of the relay) 
6  -- 

  (earth  terminal  of 

the equipment)

 

7 --485A (485 bus input terminal) 
8 --485B (485 bus input terminal) 

2.  

Fig.3 shows the general functions and wiring diagram of the product. 

       

火灾自动

报警控制器

火警

查询

电源

机检

恢复

消音

按键(允/禁)

通讯

故障

消音

按键

火  灾  显  示  盘

传        真: 0755-86226632

服务热线: 0755-86221188

火警

查询

电源

机检

恢复

消音

按键(允/禁)

通讯

故障

消音

按键

火  灾  显  示  盘

传        真: 0755-86226632

服务热线: 0755-86221188

+24V

GND

485A

485B

 

Fig.3 

3.  

Functions and usage of the product:   

1

The displayed content 

 

Fig.4 Normal Monitoring Status 

 

If the display panel operates normally after startup, 

“The machine is operating normally,” as shown 

in Fig.4 will be displayed.  The current date and time are displayed at the top right corner of the 
screen. The time is synchronous with that of the host machine of the fire alarm control panel and is 
refreshed  by  it  (there  is  some  interval for  refreshing).  The  currently  supported  control  system is 
displayed  at  the  lower  right  corner  of  the  screen.  If 

“2100”  is  displayed,  it  means  that  a  2100 

control system is supported; if 9000 is displayed, it means that a 9000 control system is supported. 
The specific control system supported depends on the eighth digit of the address dial switch on the 
back  of  the  display  panel.  For  more  details,  see  10)  Setup  of  address  parameters  and  control 
system. 
The  display  panel  can  display  99  fire  alarm  messages  or  feedback messages.  When  set  to  the 
floor display mode, each display panel can display all the fire alarms of the floor. When there are 
multiple fire alarms, the equipment will display them in an automatic rolling way. See Fig.5 for the 

Address coding 

window

 

Connecting 

terminal

 

The machine is operating 

normally.

 

Summary of Contents for ATL-982

Page 1: ...y be connected with each RS 485 bus The display panels can display fire alarm messages or feedback messages only rather than fault messages action messages or other messages A fire alarm control panel may be used for setting the display area of a display panel The set display panel can display the fire alarm messages of the designated area floor display only Note See the User s Manual of the fire ...

Page 2: ...ormally after startup The machine is operating normally as shown in Fig 4 will be displayed The current date and time are displayed at the top right corner of the screen The time is synchronous with that of the host machine of the fire alarm control panel and is refreshed by it there is some interval for refreshing The currently supported control system is displayed at the lower right corner of th...

Page 3: ...Page 3 of 6 interface ...

Page 4: ...ressed the fire alarm tone will be eliminated the MUTE indicator will be lit and the normally closed contact of the relay will be closed After receiving another fire alarm another horn strobe alarm signal may be triggered and the MUTE indicator will go out automatically Note After receiving a MUTE command from an automatic fire alarm control panel the display panel can also realize the muting func...

Page 5: ...ch on the main board on the back of the display panel see Fig 2 for its location The JP3 dial switch has eight dial digits in all wherein the first to the seventh digits are used for setting the address see Fig 6 and Fig 7 and the eighth digit for choosing the 2100 control system or the 9000 control system If the JP3 dial switch is pulled to the ON position the 9000 control system will be chosen s...

Page 6: ... the circuit of the equipment suffers short circuit open circuit wrong wiring and other defects The display panel is a precise electronic product and therefore needs to be managed by a specific person No other persons are allowed to operate it without permission Please wipe the surface of the equipment with alcohol VII Fault analysis and troubleshooting Fault phenomenon Possible cause Troubleshoot...

Reviews: