![ATIM Cloud Wireless ACW TH-O Series User Manual Download Page 16](http://html1.mh-extra.com/html/atim/cloud-wireless-acw-th-o-series/cloud-wireless-acw-th-o-series_user-manual_2999299016.webp)
15
ATIM_ACW-TH-O_UG_EN_V1.8
Once the configuration is complete, do not leave the module connected to USB. This
mode of operation is very energy intensive. When you remove the USB link without
disconnecting the battery, the module resets and automatically returns to normal
operation.
Frames format
a.
Sigfox and LoRaWAN
Type
Description
Frame format
octet 0
(dec)
octet 0
(hex)
octet 1
(hex)
octet 2
(hex)
octet 3
(hex)
octet 4
(hex)
octet 5
(hex)
Keep
Alive
Keep alive frame
1
01
Supply voltage
IDLE (mV)
Supply voltage TX
(mV)
64
Test
Test frame
5
05
Counter
TH
Temperature frame
23
17
Temperature code
Humidity code
TH
Over lower T°C threshold
passing alert
15
0F
Temperature code
Humidity code
TH
Over higher T°C threshold
passing alert
17
11
Temperature code
Humidity code
The sensor data is decoded as follows:
T(°C) =
Temperature𝐶𝑜𝑑𝑒 × 175.72
65536
− 46.85
H(%RH) =
Humidity𝐶𝑜𝑑𝑒 × 125
65536
− 6
The battery voltage of the products is good if Supply voltage is greater than 2.9V.