eco PDU PE Series User Manual
36
(Continued from previous page.)
When you have finished making your configuration settings, click
Save
.
Power ON Delay
Sets the amount of time the eco PDU waits after the Power Button
is clicked (see
, page 34), before it turns on the power
to the outlet.
Note:
The default delay time is 0 seconds; the maximum is 999 seconds.
When a series of outlets are scheduled to be powered up, they turn on in
sequence with a default delay of 10 milliseconds between each outlet.
Power OFF Delay Sets the amount of time the eco PDU waits after the Power Button
is clicked (see
, page 34), before it turns off the power
to the outlet.
For the
System after AC Back
option (see below), after the delay
time expires, the eco PDU waits another fifteen seconds, then
shuts the computer down.
The default delay time is 15 seconds. The maximum delay time is
999 seconds.
Remote Turn ON
Method
Use the drop-down menu to select one of the choices, below:
Wake on LAN:
This is a Safe Shutdown and Restart option. If this
is selected, when an Outlet is turned Off, the eco PDU first sends
a message to the computer telling it to prepare for a shutdown; it
then waits for the amount time set in the
Power Off Delay
field to
give the OS time to close down before the computer is powered
down to standby mode.
Likewise, when the Outlet is turned On, the eco PDU waits for the
amount time set in the
Power On Delay
field, then sends an
Ethernet message to the computer connected to the Outlet telling
the computer to turn itself On.
Note:
For Safe Shutdown and Restart, the computer must be running
Windows (98 or higher), or Linux, and the
Safe Shutdown
program
(available by download from our website), must be installed and running on
the computer.
System after AC Back:
This is a Safe Shutdown and Restart
option. If this is selected, when an Outlet is turned Off, the eco
PDU first sends a message to the computer telling it to prepare
for a shutdown; it then waits for the amount time set in the
Power
Off Delay
field to give the OS time to close down before the
computer is powered down.
When the Outlet is turned On, the eco PDU waits for the amount
time set in the
Power On Delay
field, then sends power to the
server. When the server receives the power, it turns itself on.
Note:
For Safe Shutdown and Reboot, the computer must be running
Windows (98 or higher), or Linux, and the
Safe Shutdown
program
(available by download from our website), must be installed and running on
the computer.
Kill the Power:
If this option is selected, the eco PFDU waits for
the amount time set in the
Power Off Delay
field, and then turns
the Outlet's power Off. Turning the power off performs a cold
(non-safe) shutdown.
MAC Address
In order to use either of the Safe Shutdown and Restart methods
the MAC address of the computer connected to the outlet must be
filled in here.
Summary of Contents for PE5324kJA
Page 10: ...eco PDU PE Series User Manual x This Page Intentionally Left Blank...
Page 24: ...eco PDU PE Series User Manual 14 PE5324kJA Front View 1 2 3 4 3 5 6 3 7 7 7...
Page 26: ...eco PDU PE Series User Manual 16 PE6324JA2 Front View 1 2 3 3 3 4 5 6 7 7 7...
Page 32: ...eco PDU PE Series User Manual 22 3 4 2 1 1...
Page 82: ...eco PDU PE Series User Manual 72 This Page Intentionally Left Blank...