Product Features
49
© 2017, ATEÏS, member of PAX ProAV Group
(Switch Mode) shall only require up to 4 channel amplifier and the amplifiers will act as a backup
amplifier in case of other amplifiers break down.
Security
In accordance with EN54-16, ISO 7240-16 and BS5839/8, full monitored supervision from paging
microphone capsule to the end of loudspeaker line.
Enhanced loudspeaker line surveillance for A/B zone wiring.
The IDA8C-SW supports redundant network cabling, wired as a redundant loop.
Connectivity
Up to 48 simultaneous audio channels per local network.
Up to 256 zones in a local network, and up to 8,192 zones in a global network.
4 channel audio distribution for EVAC, Paging, BGM & Backup.
3.1.5.1
Front Panel
Fireman Microphone Active LED:
Display the status of the fireman microphone, there are two states of this LED:
Status
Frequency
Activity
Permanent
Active, Fireman microphone is allowed to paging.
Blinking
°
°
Zones are busy, fireman microphone is not allowed to paging.
Blinking
°
°°°
Pre chime is playing.
Fireman Microphone Input:
A DIN connector for fireman microphone connection.
Fireman Microphone Hook:
An U-shape hook to place the fireman microphone.
Monitoring Speaker:
A built-in speaker to play chime when paging or monitor signal from main controller.
Function
Activity
Warning Tone
A buzzer sound is generated when some faults is detected in system.
Source Monitoring
Monitor audio sources of IDA8C. The source to be monitored can be selected via
Ateis Studio software.
If a fault is detected when speaker is monitoring a source, then the source monitoring will be
interrupted and play a buzzer sound for the fault.
Bypass Mode LED:
This LED will light up if the IDA8C is in bypass mode or not.