Product Features
133
© 2017, ATEÏS, member of PAX ProAV Group
button to start paging. The by-pass mode input contact can connect to a button for
triggering Bypass Mode Paging.
The Fireman microphone has a higher priority than PDC1 source.
Condition of Bypass Mode Switching:
There are two ways to switch the system state to Bypass Mode Paging:
Hardware monitoring:
In IDA8 devices, there are hardware monitored mechanisms to detect a micro controller
crash. The system switches to Bypass mode paging if a micro controller crash is detected.
Bypass mode input contact:
Connect the pin CMD and pin GND of the bypass-mode input to a button. This input contact
can trigger Bypass Mode Paging.
Cascade:
If the application uses multiple IDA8s and connects using the fiber-optic as a transmitting media for
Ateis Net, the additional wiring for Bypass Mode Paging cascade must be used. See the picture
below:
3.1.14 Security Mode
When the power of IDA8 system is under a low status (system can only use the battery to power supply),
the Security Mode provides users to choose to proceed with only the important paging schedule or
close down the system monitoring which under the standard/normal mode.
When IDA8 system is under the Security Mode, the system will operate with the listed two point of
description as below:
The paging function will only be activated when the checkbox of Security on Network Paging
component has been ticked. Please refer to
To change the system to Security Mode, user needs to connect the S Input Pin from the Fault
Define Security component, please refer to
component and the example
below,
The period of monitoring (amplifier/speaker line) function will be changed to 90 seconds/per
time.