Atal AT-VLS-101DE Quick Manual Download Page 2

 

 

 

PRODUCT DESCRIPTION   

 

Programmable regulators 

with Ethernet connection are designed to measure temperature and relative humidity of air, to measure 

concentration  of  CO

2

  in  the  air,  to  signal  alarms  and  control  of  external  devices.  Regulators  can  be  used  in  a  chemically  non-

aggressive environment. 

 

The  CO

2

  concentration 

is  measured  using  the  maintenance  free  sensor.

 

The  unique  patented  auto-calibration  procedure 

compensates aging of the sensing element and guarantees outstanding high reliability and long-term stability.  

 

The function of two output relays 

can be set using the device keyboard or from computer. It is possible to assign any input or 

computed  value  (dew  point  temperature,  absolute  humidity,  specific  humidity  mixing  ratio  and  specific  enthalpy)  to  each  relay. 
Setting of delay, hysteresis, audible alarm is enabled for each relay and it is possible to control output relay status via Ethernet too. 

The instrument may send a warning message if the measured value goes out of adjusted limits. Devices are equipped with four 
button keyboard and two-line LCD display. The visual indication of the concentration of CO

2

 is provided by three LEDs to the left 

side of the display. 

 

The  supported  Ethernet  communication  formats

:  www  pages  with  user-design  possibility,  Modbus  TCP  protocol,  SNMPv1 

protocol and SOAP. For setting of all parameters you can use 

TSensor

  software. 

 

type * 

 

 

measured values    

 

version 

 

 

 

 

mounting 

 

AT-VLS-104DE 

 

CO

 

 

probe on cable 

 

 

 

wall 

AT-VLS-101DE 

 

CO

2

 

 

 

ambient air 

 

 

 

wall   

AT-VLS-102DE 

 

T + RH + CO

2

 + CV  

ambient air  

 

 

 

wall   

AT-VLS-106DE 

 

T + RH + CO

2

 + CV  

probes on cable 

 

 

 

wall

 

f

  

*  T…temperature,  RH…relative humidity,  CO

2

…concentration CO

2

 in air,  CV…computed values   

 

 

 

INSTALLATION , OPERATION AND CONFIGURATION

 

 

The  mounting  holes  and  connection  terminals  are  accessible  after  unscrewing  the  four  screws  in  the  corners  of  regulator  and 
removing the lid. Devices have to be mounted on a flat surface to prevent deformation. For output relays connection choose cables 
with external diameter 4 to 6.5mm and wire cross-section 0.14 to 1.5mm

2

. Do not forget to insert attached plugs into unused cable 

glands. Unpack the external CO

2

 probe and connect it to the regulator. Pay attention to mounting the device and probes, because 

incorrect  choice  of  working  position  or  place  of  measuring  could  adversely  affect  accuracy  and  long-term  stability  of  measured 
values.  

 

Actual parameters settings of each relay can be displayed by pressing of „ ▲“ key. To change any parameter, press the „

Set

“ key, 

enter password (default 0000) and set required value. Then click on „

Set

“ and pressing „

Esc

“ key exit setup mode. To change the 

password and to set all other parameters (acoustic alarm, limits of CO

2

 indication, computed value selection etc.) is used 

Extended 

setting mode

 

For network device connection it is necessary to know new suitable IP address (you can get it automatically from DHCP server or 
from your network administrator) and to have TSensor software installed. After you connect Ethernet cable, power adapter or PoE 

splitter, you run 

TSensor 

program, set the new IP address, configure the device in accordance with your requirements and finally 

store the settings. The default IP address of each device is preset to 

192.168.1.213

 

After switching the device starts internal test. During this time (about 20 s) LCD display shows  

---- 

 instead of CO

2

 concentration 

value

.

 

 

Devices don´t require special maintenance. We recommend you periodical calibration for validation of measurement accuracy.  
 

ERROR STATES 

 

Device continuously checks its state during operation and if an error appears, it is displayed relevant code: 

Err 1

 – measured value 

(except of CO

2

 concentration) or calculated value is over the upper limit,  

Err 2 – 

measured or calculated value is below the lower 

limit or concentration CO

2

 measurement error occurred,  

Err 0, Err 3 

and 

Err 4

 – it is a serious error, please contact distributor of 

the device, 

Err 5, Err 6

 - there is problem with assigned value to output relay, 

Err 9 

– inserted password is not valid. 

 

SAFETY INSTRUCTIONS  

 

 

-   Humidity and temperature sensors of the regulator cannot be operate and store without a filter cap. 
-  Temperature and humidity sensors have not to be exposed to direct contact with water and other liquids. 

-   It is not recommended to use the humidity regulators for long time under condensation conditions. 
-   Take care when unscrewing the filter cap as the sensor element could be damaged. 
-  The regulator must be turned on for at least 24 hours in order to start the automatic calibration of the CO

2

 

sensor. 

-   Use  only  the  power  adapter  according  to  technical  specifications  and  approved  according  to  relevant 

standards.  

-  Don’t connect or disconnect devices while power supply voltage is on. 
-   Installation, electrical connection and commissioning should be performed by qualified personnel only. 

-   Devices contain electronic components, it needs to liquidate them according to currently valid conditions. 