Atal AT-VL-03T User Manual Download Page 2

 

Parameter Setup (

V.2W2KPV105

After power off and remove the backboard and clapboard from the main part as shown in 

fig. 2

. There are 4 Dipswitches in the circuit board as following:

 

DIP1: ON-Parameter setup                                                                          OFF- User operation                                                      Leaving Factory

OFF 

DIP2: ON- Fahrenheit                                                                                  OFF- Celsius                                                                    Leaving Factory

OFF 

DIP3

ON- The analog output is direct proportion linearization             

OFF- The analog output is PID adjustment (Please refer to Item -23 at table below)                                                        Leaving Factory

OFF 

DIP4

ON- with an analog output                                                              OFF- without an analog output                                      Leaving Factory

ON 

Dipswitch 

up

 is 

on

 and Dipswitch 

down

 is 

off.

       

                                   

 

Press

 switch

 key to switching parameters and press

▼▲

keys to setting.    After setup, DIP1 must be put to OFF. 

Display 
on LCD 

Parameter 

Range of setup 

Default 

-00 

Device Version 

 

1105 

-01 

Device ID 

1~255 

-02 

Device Baud Rate 

4800,9600,14400,19200,38400 

19200 

-03 

Device Stop and Parity Bits 

1-None 1Stop;

 

2-None 2Stop;

   

3-Odd 1Stop; 4-Even 1Stop 

-04 

The slight temp. difference of starting / closing analog output 

just for DIP3=OFF,DIP4=ON, -23=1

 

0.5~3.0C/0.9~4.5F 

1.0C/2.0F 

-05 

Adjusting the brightness of 3-lights 

0~1023 

50 

-06 

CO2 modification Aim 

0~ The maximum of 

CO

2

 measurement and setting 

(Please refer to Item -22) 

-07 

Temp. modification Aim 

0~60C/32~140F

 

25.0C/77F 

-08 

Humidity modification Aim 

5~95%RH 

50%RH 

-09 

The lowest voltage of the analog output (just for DIP3=OFF) 

0~the highest analog output 

2.0 

-10 

The highest voltage of the analog output (just for DIP3=OFF) 

the lowest analog output~10.0 

10.0 

-11 

Response rate of analog output (just for DIP3=OFF) 

1~200 

(the smaller the value, the quicker the response)

 

20 

-12 

0: analog output is 0 when CO2 detecting value < setting value 
1:analog output is the setting lowest voltage when CO2 detecting value < setting value                  (just for DIP3=OFF) 

-13 

When it used as a transmitter, analog output linearize with CO

2, 

 

the output voltage which corresponds with 0ppm 

0~9.0 
(corresponding 0~9V

 

0.0 

e.g. the setting value is 2.0 and CO

measuring range is 0~2000ppm, DC 2V output corresponds with 0ppm and DC10V with 

2000ppm 

-14 

Preheating time for 

CO

2

 sensor 

(before 

CO

2

 sensor steady, no analog output) 

1~600 seconds 

60s 
 

-15 

State of the monitor when power on again after power broken. 
0

Turn off after power on again    1

Turn on after power on again      2

  Keep on previous state before power broken 

-16 

CO2 Elevation Calibration 
Warning: if you change this item, please wait a few seconds after   
the icon "

——

" disappear on the LCD, then the new setting will   

prevail. 
press

or

more than 20 seconds to perform CO2 Elevation   

Calibration. 

0~

5000

Feet 

-17 

CO2 ABC Logic 
Warning: if you change this item, please wait a few seconds after   
the icon "

——

" disappear on the LCD, then the new setting will   

prevail. 
press

or

more than 20 seconds to perform CO2 ABC Logic 

1-Enable 
2-Disable 

-18 

CO2 Single Calibration 
Warning: if you change this item, please wait a few seconds after   
the icon "

——

" disappear on the LCD, then the new setting will   

prevail. Press

or

more than 20 seconds to perform CO2   

Single Calibration 
Please note: 
1. Make sure to place the CO2 controller in an environment   
where CO2 concentration is stable. 
2. After CO2 single point calibration process is completed, please   
keep the CO2 controller in the same environment until the     
CO2 measurement value displayed turns into the target CO2   
value of CO2 single point calibration. 
3. If CO2 concentration of the calibration environment is not   
stable, or if the CO2 controller is moved away before its CO2     
measurement display reaches the target value, then there might   
be serious distortion to future CO2 measurements. 

0~50000 

450 

-19 

CO2 

modification;

  CO

2

 

reading  calibration  at  a  certain  point 

between  the  monitor  and  a  standard 

CO

2

  gas  sample.  The 

calibration can only be used in a small range. 

-500~500PPM 

0 PPM 
 

-20 

Temp modification 

-118.0~100.0C/-212~212F 

-21 

Humi. modification 

-100~100 

-22 

The maximum of 

CO

2

 measurement and setting 

1000~20000ppm 

2000 

-23 

Temp. controlling 

’s feasibility

just for DIP3=OFF,DIP4=ON

 

0: PID anolog output; 
1: PID anolog output when detect temp.< (setting temp. 
-  temp.  differential);  Anolog  output  maximum  when 
detect temp.>(setting temp.-temp. differential) 

Note: The numbers blinking indicates it being setup, the numbers stop to blink to indicate the parameter confirmed.   

RESET: 

Put the DIP1 to ON and press 

switch 

key for about 25 seconds until the monitor is off, then all the setting values return to the factory default..

 