Atal AT-VL-03T User Manual Download Page 1

 

  AT-VL-03T

                                         

 

  Carbon Dioxide Monitor & Air Alert     

                                       

User manual

                                                                                                                                         

 

                                                 

                                                                         

         

         

 

Important safety information Warning 

 

Always turn off power before mounting, removing, and cleaning the monitor.   

 

Read all of the information in this manual before mounting the monitor. 

 

Notice the supply power voltage of the monitor: 24VAC/DC. do not confuse it and do not install on voltages   

higher than marked the monitor. 

 

Do not touch the circuit board or components with electrifying, to avoid danger for users. 

Mounting (see Fig.1) 

 

Find the 2 clips on either side of the indicator; depress them with a non-edge tool to remove the main part   

and the clapboard from the wall plate. 

 

Mount the wall plate first on the wall, 1.2-1.3 meters above the floor. Place the indicator against the wall at   

desired location; make sure wires can be feed through opening on wall plate.   

 

Connect wires to terminal strips (see fig.1). Make sure wiring connection correct and secure. 

 

Attach the main with clapboard to the wall plate. 

Buttons and LCD 

 

 

 
 
 
 
 

Operation   

1.    After electrifying

OFF 

displayed on the right bottom of LCD

which means monitor is OFF. 

2.    Press 

power

  button  for  about 1  second  to turn  it on.  The measured  temperature and  the  measured  humidity  display  on  the upper  line of LCD.  The

 

measurement of CO

2

 displays on the bottom line of LCD. If no humidity detection, the measurement of humidity shall not display. 

3. 

If the monitor is used for the first time or is used again after long time laying up, it should be powered and turned on for 48 hours at least, to make the 

CO

2

 measurement in self calibration.   

4. 

switch 

button: can be switched three different CO

2

 alert values and 1 temperature set value displayed on top left of LCD and it marks by 1, 2, 3 and 4.   

1

  Setting value is the boundary between green light and orange light (the first point) .The default setting is 1000ppm. 

If CO

2

 measurement

  the setting value, the green light would be bright.     

2

  Setting value is the boundary between orange light and red light (the second point). The default setting is 1400ppm. 

If the first setting value< CO

2

 measurement and 

  the setting value, the orange light would be bright     

If CO

2

 measurement > the setting value, the red light would be bright.   

3

    Setting the CO

2

 value which used to control the analog output (just for DIP3 = OFF, DIP4 = ON). 

If CO

2

 measurement>the third setting ,the controller will be have the analog output. 

4

  Temperature value setting (effective when DIP3=OFF and DIP4=ON, also parameter18=1), setting range: 5~50

/ 41~122

 

Control way:

   

when measured temp.

≥ (setting temp. + temp. differential), the analog output is maximum; 

when (setting temp. + temp. differential) >measured temp.> (setting temp. - temp. differential) , the analog output keeps on last status ; 

when measured temp.

≤ (setting temp. - temp. differential), the analog output is controlled by CO

2

 level. 

There will be no analog output when the CO2 monitor is switched off by pressing 

‘power’ button. 

5. 

Preset CO

2

 setting value: choose the first or second or third point of CO

2

 by press button of 

switch 

in circle, 

then set the value by press 

  or 

  with 1ppm adjusting each time. When press 

  or 

  for more than 

3 seconds, the setting value would change quickly with 10ppm each time.   

Preset temperature setting value: choose the temperature setting value by press button of 

switch

 , then set 

the  value  by  press 

  or 

  with  0.5

  adjusting  each  time.  When  press 

  or 

  for  more  than  3 

seconds, the setting value would change quickly. As you adjust the value, it would blink up to confirm it.   

6. 

Lock the settings: press 

  and 

  simultaneously for 5 seconds until    appearing in the top right corner. 

Then you cannot adjust the set values.         

7.

 

Unlock the setting: press the 

  and 

  simultaneously for 5 seconds until      disappears.

 

8.

 

The number of scale bar      are corresponding with 0

10V analog output. One scale bar indicates 1VDC of 

analog output.

 

 

 

 

 

switch setting

 

up 

down 

turn on/off 

Fig. 2 

 

 

            AT-VL-03T

 

 

 

0-10VDC

 

AT-VL-03T 

   

 

 

 

Fig. 1 

 

O N

O N

voltage of analog output 

CO

2

 

 

temperature 

 

lock mode 

 

 

 

 

 