125
124
2 lives with 1 neutral connection (2 1N a.c. 400 V / 50 Hz):
The voltage between the phases and the neutral is 230 V a.c. Between the
lives there is a voltage of 400 V. If there is not a voltage of 400 V between
the lives, two wires have been taken from the same live in the meter
cupboard and the hob must be connected with two neutral wires, as
indicated above under 2 lives with 2 neutrals.
Install a connecting bridge between the connection points 4-5.
Your groups must be fused with at least 16 A (2x). The connecting power
cable must have a minimum core cross section of 2,5 mm
2
.
3 lives with 1 neutral connection (3 1N a.c. 400 V / 50 Hz):
The voltage between the phases and the neutral is 230 V a.c. There is a
voltage of 400 V between the lives. Fit a connecting bridge between the
connection points 4-5. Phase 3 carries no load. Your groups must be fused
with at least 16 A (3x). The connecting power cable must have a
minimum core cross section of 2,5 mm
2
.
electrical connection
INSTALLATION GUIDE
INSTALLATION GUIDE
The appliance can be connected in the following ways:
1 phase connection (1 1N a.c. 230 V / 50 Hz):
The voltage between live and neutral is 230 V a.c.
Install connecting bridges between connection points 1-2 and 4-5.
Your group must be protected by a fuse of at least 32 A. The connecting
power cable must have a minimum core cross section of 6 mm
2
.
2 lives with 2 neutrals connection (2 2N a.c. 230 V / 50 Hz):
The voltage between live and neutral is 230 V a.c. There may be a
voltage of 0 V between the phases if they are connected to the same phase in
the meter cupboard but also 400 V if they are connected to 2 different
phases. Your groups must be fused with at least 16 A (2x). The connecting
power cable must have a minimum core cross section of 2,5 mm
2
.
electrical connection