Installation
&
Servicing
instructions
AT
AG
A200SOV
25
10.4 Activating the factory setting (green key function)
To re-activate the factory settings, proceed as follows (this will undo all changed settings):
- Select P6 81, according to the procedure described in chapter 10.4;
- Select b7;
- Press OK. The screen is showing ‘off’;
- Select ‘on’;
- Press OK.
The screen then shows P6 81 and the factory settings are active again.
Parameter-chapter
PARA
Factory
Description
Range
518
5
Gradient speed CH
0 - 15
520
5
Do not change
0 - 10 K
532
24
Do not change
10 - 40
541
max.
Maximum power CH in %
Can only be reduced. 0 = low load
0 - max
555
Do not change
651*
1
Do not change
1 - 3
652*
0
Quick selection CH installation:
CH Tmax: 85°C; Gradient: 5; Heating line 24
1
CH Tmax: 70°C; Gradient: 5; Heating line 19
2
CH Tmax: 60°C; Gradient: 4; Heating line 15
3
CH Tmax: 50°C; Gradient: 3; Heating line 11
4
This parameter copies the choosen value over CH Tmax., P518 en P532.
It is a quick selection, where the separate values will be independantly adjustable.
After selection this parameter will always show 0.
680
0
Service-parameter.
Do not change
0 - 10
681
off
Green button function
Dependant of the level the factory settings at selection
b7 and OK will be set back,
P651 excluded.
on - off
682
Dynamic functions:
off
b0:
Do not change
on - off
b1 until b6: no function
off
b7: confirmation Service-parameter
on - off
683
0%
Correction factor fan speed for HP-system
See table at flue lenghtes
. The adjusted value will increase the fan range with that
percentage. Write down this value on the sticker on the boiler.
0 - 20%
684
Do not change
* Note
When an adjustment is made and it is confirmed with OK the boiler will restart and
the de-aerationprogramm will start.
Parameter-chapter
Table 6