Astria Sentinel36TEN Installation And Operation Instructions Manual Download Page 13

Astria.US.com

126733-01B

13

Figure 16 - Horizontal Termination Using Two 90° Elbows

Figure 17 - Offset with Wall Strap and 45° Elbows

VENTING INSTALLATION  

Continued

Venting with Two 90° Elbows

Vertical (V)

Horizontal (H

1

) + 

Horizontal (H

2

)

6' min.

8' max.

7' min.

10' max.

8' min.

15' max.

20' max.

20' max.

Vertical Termination Installation

Note:

 Vertical restrictor must be installed in all vertical installations.

1.  Determine route your vertical venting will take. If ceiling joists, 

roof rafters or other framing will obstruct venting system, consider 

an offset (see Figure 17) to avoid cutting load bearing members. 

Note: Pay special attention to these installation instructions for 

required clearances (air space) to combustibles when passing 

through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not 

pack air spaces with insulation. Also note maximum vertical rise 

of venting system and any maximum horizontal offset limitations.

2.  Set fireplace in desired location. Drop a plumb line down from 

ceiling to position of fireplace exit flue. Mark center point where 

vent will penetrate ceiling. Drill a small locating hole at this point.

3.  Drop a plumb line from inside of roof to locating hole in ceiling. 

Mark center point where vent will penetrate roof. Drill a small 

locating hole at this point.

45° Elbow

Wall Strap

Roof Flashing

Ceiling Firestop

Flat Ceiling Installation

1.  Cut an 11 

1

/

2

" square hole in ceiling using locating hole as a center 

point. Opening should be framed to 11 

1

/

2

" x 11 

1

/

2

" inside dimen-

sions, as shown in Figure 10 on page 11 using framing lumber 

the same size as ceiling joists. If area above ceiling is an insulated 

ceiling or an attic, nail firestop from top side. This prevents loose 

insulation from falling into required clearance space. If area above 

ceiling is a living space, install firestop below framed hole. Firestop 

should be installed with no less than three nails per side (see Figure 

15, page 12).

2.  Assemble desired lengths of pipe and elbows necessary to reach 

from fireplace flue up through firestop. Be sure all pipe and elbow 

connections are fully twist-locked (see Figure 9, page 11).

3.  Cut a hole in the roof using locating hole as a center point. (Cover 

any exposed open vent pipes before cutting hole in roof.) The 

11 

1

/

2

" x 11 

1

/

2

" hole must be measured on the horizontal; actual 

length may be larger depending on pitch of roof. There must be 

a 1" clearance from vent pipe to combustible materials. Frame 

opening as shown in Figure 10, page 11.

4.  Connect a section of pipe and extend up through hole.
 

Note: If an offset is needed to avoid obstructions, you must sup-

port vent pipe every 3 feet. Use wall straps for this purpose (see 

Figure 17). Whenever possible, use 45° elbows instead of 90° 

elbows. The 45° elbow offers less restriction to the flow of flue 

gases.

5.  Place flashing over pipe section(s) extending through roof. Secure 

base of flashing to roof and framing with roofing nails. Be sure 

roofing material overlaps top edge of flashing as shown in Figure 

17. There must be a 1" clearance from vent pipe to combustible 

materials.

6.  Continue to add pipe sections until height of vent cap meets the 

minimum building code requirements described in Figure 8 on 

page 9.

 

Note:

 You must increase vent height for steep roof pitches. Nearby 

trees, adjoining rooflines, steep pitched roofs and other similar 

factors may cause poor draft or down-drafting in high winds. 

Increasing vent height may solve this problem.

7.  Twist-lock vent cap onto last section of vent pipe.

Vent Termination Chart

Minimum Height

Roof Pitch

Feet Min.

Flat to 6/12

1

6/12 to 7/12

1.25

Over 7/12 to 8/12

1.5

Over 8/12 to 9/12

2

Over 9/12 to 10/12

2.5

Over 10/12 to 11/12

3.25

Over 11/12 to 12/12

4

Over 12/12 to 14/12

5

Over 14/12 to 16/12

6

Over 16/12 to 18/12

7

Over 18/12 to 20/12

7.5

Over 20/12 to 21/12

8.0

Summary of Contents for Sentinel36TEN

Page 1: ...OU D EXPLOSION Le non respect Des avertissements de s curit pourrait d entra ner des blessures graves la mort ou des dom mages mat riels Do not store or use gasoline or other flammable vapors and liqu...

Page 2: ...ON REFROIDIE NE LAISSEZ JAMAIS UN ENFANT DE TOUCHER LA VITRE L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre chaude et doit tre instal...

Page 3: ...with the National Safety Standards and is listed and tested by the PFS Corporation to ANSI Z21 50 CSA 2 22 standard as vented gas fireplace NOTICE Decorative product not for use as a heating appliance...

Page 4: ...vice person The appliance should be inspected before use and at least annually by a professional service person More frequent cleaning may be re quired due to excessive lint from carpeting bedding mat...

Page 5: ...Standards Institute Inc 1430 Broadway New York NY 10018 National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 PRODUCT IDENTIFICATION PRODUCT FEATURES These are a few facts that c...

Page 6: ...ions before deciding the exact location for your fireplace and termination cap When deciding the location of your fireplace follow these rules Do not connect this fireplace venting to a chimney flue s...

Page 7: ...36 42 42 41 36 48 42 21 1 8 36 25 1 8 42 Requires IHP 5 I D 8 O D Direct Vent Pipe 11 7 8 36 13 5 8 42 29 1 8 36 34 3 4 42 20 1 2 36 24 42 PRE INSTALLATION Continued NAILING FLANGE NAILING FLANGE GAS...

Page 8: ...s will help circulate the heat throughout the house FRAMING AND FINISHING Figures 5 and 5a show typical framing of this fireplace Figure 6 shows framing for corner installation All minimum clearances...

Page 9: ...S if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally L...

Page 10: ...nd vent assembly must be vented directly to the outside The venting system must NEVER be attached to a chimney serving a separate solid fuel burning appliance Each direct vent gas appliance must use a...

Page 11: ...Figure 12 page 12 Siding standoff must sit flush against exterior fascia material 6 Connecting Vent Cap with Horizontal Vent Pipe Slide wall firestop over vent pipe before connecting horizontal run to...

Page 12: ...l minimum and maximum dimensions which MUST be met Figure 16 page 13 shows a configuration for venting with horizontal termination using two 90 elbows with a chart of critical minimum and maximum dime...

Page 13: ...irestop below framed hole Firestop should be installed with no less than three nails per side see Figure 15 page 12 2 Assemble desired lengths of pipe and elbows necessary to reach from fireplace flue...

Page 14: ...2000 feet you may need to decrease the input rating by changing the existing burner orifice to a smaller size Reduce input 4 for each 1000 feet above sea level Check with your local gas company for p...

Page 15: ...re to between 11 and 14 of w c pressure If you do not reduce incoming gas pressure fireplace regulator damage could occur Install external regulator with the vent pointing down as shown in Figure 21 P...

Page 16: ...ing compressed air 4 Check all joints of gas supply piping system Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak Correct all leaks at once CONNECTING FIREPLACE TO GA...

Page 17: ...LASS DOOR CAUTION Do not operate this fireplace with a bro ken glass door panel or without the glass door panel securely in place For replacement part information see Replacement Parts page 33 CAUTION...

Page 18: ...ce lava rock around base of burner Make sure burner ports are not covered see Figure 30 page 19 4 Place ember flakes around front and sides of burner and on burner ports see Figure 31 page 19 This wil...

Page 19: ...ck for a leak Apply noncorrosive leak detection fluid to joints Bubbles forming show a leak Correct leaks at once CAUTION The gas supply shall be shut off prior to disconnecting the electrical power i...

Page 20: ...lide Switch ON REMOTE OFF Figure 35 Installing Receiver Batteries Included Figure 36 Adjusting the Receiver BATTERY LIFE Life expectancy of the alkaline batteries in the remote control should be at le...

Page 21: ...ition 4 Remove center brick control cover 5 Turn equipment shutoff valve clockwise to the OFF position see Figure 37 Do not force 6 Wait five 5 minutes to clear out any gas Then smell for gas includin...

Page 22: ...remove the adjustment screw see Troubleshooting page 24 BURNER FLAME PATTERN Burner flames will be steady not lifting or floating Flame patterns will be different from unit to unit and will vary depen...

Page 23: ...ION Wear gloves and safety glasses while handling or removing broken glass Do not remove if glass is hot Keep children and pets away from glass If glass has been broken carefully remove glass door see...

Page 24: ...and dirt inspect and clean any other possible obstructions 4 Contact your gas supplier to check pres sure 5 Have a qualified technician replace pilot line 6 Replace control valve Refer to Replace ment...

Page 25: ...blocked 3 Improper venting or excessive blockage 4 Excessive amounts of embers and pan material OBSERVED PROBLEM Gas odor even when gas control valve is off Gas odor during combustion Glass soots Dar...

Page 26: ...1 17 22 25 26 27 7 4 5 12 16 18 19 20 29 31 30 23 24 28 21 13 14 15 3 6 34 35 36 37 2 2 4 4 WARNING Contact an IHP dealer to obtain any of these parts Never use substitute materials not approved by IH...

Page 27: ...y 42 NG High Altitude 1 7 J7656 123210 01 Grate 36 1 J7657 123210 02 Grate 42 1 8 J7658 122652 01 Door Latch 2 9 Firebox Leg 4 10 Firebox Bottom 1 11 J7659 121431 01 Gasket 36 1 J7660 111913 02 Gasket...

Page 28: ...Astria US com 126733 01B 28 PARTS 8 15 1 2 3 4 5 7 24 6 9 4 5 10 16 14 12 13 17 25 13 11 18 19 22 23 20 21...

Page 29: ...NG 1 J7698 23100 Front Orifice 56 Propane LP 1 J7699 24771 Front Orifice 42 NG 1 J7698 23100 Front Orifice 56 Propane LP 1 11 Base 1 12 J7700 114027 01 Grommet SC 1 2 ID 1 1 16 OD 1 13 J7701 14399 90...

Page 30: ...Astria US com 126733 01B 30 PARTS REFRACTORY PARTS 1 2 4 5 6 3 Herringbone Brick Shown...

Page 31: ...095 01 Center Front Refractory 36 White 1 6 J7825 125130 01 Right Front Refractory 42 White 1 J7826 125094 01 Right Front Refractory 36 White 1 S e n t i n e l 4 2 H B o n e F 2 2 9 2 F 2 2 9 4 S e n...

Page 32: ...44 SENTINEL36TEP Rating 31 000 Btu hr Gas Type Propane LP Gas Only Ignition Electronic Manifold Pressure 10 w c Minimum Inlet Supply Pressure 11 w c Maximum Inlet Supply Pressure 13 w c Front Orifice...

Page 33: ...com SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition fireplace will not produce specified heat propane LP gas supply might be low propane LP units...

Page 34: ...____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______...

Page 35: ...ent riot fire flood or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjected...

Page 36: ...Keep receipt for warranty verification Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications pricesandalsotodiscontinuecolors sty...

Reviews: