Astria Craftsman STP2 Installation And Operation Instructions Manual Download Page 8

Astria.US.com

126650-01B

8

Figure 13 - Pipe Connection

Hemmed 

End

LINEAL GAIN CHART

12 

3

/

8

Galvanized 

Outer Pipe

8'' Stainless 

Inner Pipe 

Lanced Side 

Up

VENTING INSTALLATION 

Continued

LINEAL GAIN

PART NO.

DESCRIPTION

GAIN

Craftsman STP2

See-Through 

Fireplace

54"

12-8DM

Flue Pipe

10 

5

/

8

"

18-8DM

Flue Pipe

16 

5

/

8

"

24-8DM

Flue Pipe

23 

5

/

8

"

36-8DM

Flue Pipe

34 

5

/

8

"

48-8DM

Flue Pipe

46 

5

/

8

"

RTL-8DM

RTTL-8DM

Round Top 

Termination

6"

ETL-8M

ETO-8DM

ETLO-8DM

Econo-Top

Termination

1" to 12"

FIRESTOP SPACERS FS-8DM

Firestop spacers are required at each point where the chimney pen-

etrates a floor or ceiling joist space. Their purpose is to establish 

and maintain the required clearance between the chimney and the 

combustible materials.
When penetrating a floor or ceiling at an angle, use firestop spacer 

number FS-8DM (see Replacement parts, page15 and Accessories, 

page 16).
When the pipe passes through a framed opening into a living space 

above, the firestop must be placed onto the ceiling from below as 

shown in Figure 14, page 8. When the pipe passes through a framed 

opening into an attic space above, the firestop must be placed on the 

attic floor as shown in Figure 15, page 8.

CHIMNEY PIPE

 WARNING: Label part number 900599-01 must 

be applied by the installer to all chimney pipe 

sections but is not required on sections that will 

be visible after the installation is complete. Label 

must wrap around the circumference of the pipe. 

See accessories, page 17 for Kit F2659.

The IHP chimney system is a snap-lock, double-wall pipe. It consists 

of a stainless steel inner flue pipe(s), a galvanized outer pipe and a 

wire spacer. Each section of pipe comes in lengths of 12", 18", 36" 

and 48". The actual lineal gain for each is measured after each section 

is fully connected. Lineal gain is the actual measurable length of a 

part after two or more parts are connected.

PIPE INSTALLATION

The pipe sections must be assembled independently as the chimney is 

installed. When connecting chimney directly to the firebox, the inner 

flue pipe section must be installed first with the lanced side up. The 

outer pipe section can then be installed over the flue pipe section 

with the hemmed end up. Press down on each pipe section until the 

lances securely engage the hem on the firebox starter. The wire will 

assure the proper spacing between the inner and outer pipe sections.
Continue to assemble chimney sections as outlined above, making 

sure that both the inner and outer pipe sections are locked together 

(see Figure 13). When installing double wall snap-lock chimney 

together, it is important to assure the joint between the chimney sec-

tions is locked. Check by pulling chimney upward after locking. The 

chimney will not come apart if properly locked. It is not necessary 

to add screws to keep the chimney together.

 WARNING: The opening in collar around chimney 

at top of fireplace must not be obstructed. Never use 

blown insulation to fill chimney enclosure.

Figure 14 - Firestop Spacer with Living Space Above Ceiling

Figure 15 - Firestop Spacer with Attic Space Above Ceiling

Existing 

Ceiling 

Frame

Firestop 

Spacer

Screws or 

Staples 

(Min. of 8)

Firestop 

Spacer

Screws or Staples 

(Min. of 8)

Existing 

Ceiling 

Frame

IMPORTANT NOTICE 

When penetrating a ceiling into an attic, a firestop thimble 

(38FST or FST30) is required to avoid intrusion by insulation and 

recommended to negotiate a joist (see Figure 15a, page 10).

Summary of Contents for Craftsman STP2

Page 1: ...r approved to ANS Z21 11 2 standard An INNOVATIVE HEARTH PRODUCTS LLC hood must be installed when using a vent free log heater see Ac cessories page 17 FOR CANADA The authority having jurisdiction suc...

Page 2: ...hazard The IHP warranty will be voided by and IHP disclaims any respon sibility for the following actions a Modification of the fireplace or any of the components manu factured by IHP unless otherwise...

Page 3: ...urn veryquickly DONOTusetreatedwood charcoal coal trash driftwoodorwoodsthathavebeendippedintar pitch pine tar creosote etc Wood products made with synthetic binders such as plywood produce ab normall...

Page 4: ...ce the risk of a chimney fire SAFETY Continued Figure 1 Dimensions WARNING Always leave glass doors fully opened or fully closed when operating fireplace WARNING Children and adults should be alerted...

Page 5: ...2 Common Location of Fireplace Existing Wall Projected Wall 12 30 4 cm to Perpendicular Wall MINIMUM CLEARANCE TO COMBUSTIBLES Back and sides of fireplace 1 minimum Adjacent wall 12 minimum Chimney ou...

Page 6: ...From Outer Pipes to Combustibles 1 2 5 cm Min To Combustibles 21 5 16 54 cm 42 5 8 108 cm 24 61 cm 12 31 cm Figure 7 Framing Firebox with Z Type Ember Protectors As Required by Design as Long as Ceil...

Page 7: ...age 16 Avoid installing outside air eyebrow in areas where inlet opening may be blocked by snow bushes or other obstacles It should also be located beyond the reach of children CAUTION Combustion air...

Page 8: ...r pipe and a wire spacer Each section of pipe comes in lengths of 12 18 36 and 48 The actual lineal gain for each is measured after each section is fully connected Lineal gain is the actual measurable...

Page 9: ...e19 Figure 18 Raise and Offset B A Screws Figure 16 Elbow Offset 20 FT 6 096m 20 FT 6 096m Return Elbow 12S 8DM Support Required Figure 17 Chimney Supports 2 5 1cm Minimum Straps 2 5 1cm Minimum Angle...

Page 10: ...tances such as neighboring hills tall trees or strong wind areas can cause down drafts in chimney system In such cases going beyond the minimum recommended height would be preferable to provide a bett...

Page 11: ...ed to cover exposed area and flashing base Secure in position by nailing through shingles see Figure 23 DO NOT NAIL THROUGH FLASHING CONE Nail Only Outer Perimeter of Flashing Storm Collar Underlap Sh...

Page 12: ...al may be used for facing glass tile brick etc as long as proper clearances are adhered to and firebox openings are not obstructed in any way see Figure 27 Use only heat resistant noncombustible morta...

Page 13: ...s line and refractory knockout hole with refractory cement or commercial furnace cement Install the gas appliance or cap off gas line if desired CAUTION All gas piping and connections must be tested f...

Page 14: ...e 30 Cabinet Glass Doors Cabinet Glass Doors WARNING FIREPLACESEQUIPPEDWITHDOORS SHOULD BE OPERATED ONLY WITH DOORS FULLY OPENORDOORSFULLYCLOSED IFDOORSARELEFT PARTLYOPEN GASANDFLAMEMAYBEDRAWNOUT OF T...

Page 15: ...s fireplace OPERATION AND MAINTENANCE GUIDELINES Continued REPLACEMENT PARTS See Page 16 Fireplace Accessories section for replacement parts Use only parts supplied from the manufacturer Normally all...

Page 16: ...1 side Platinum Finish J0455 DG368ST 36 See Thru WB Bi Fold Door 1 side Brushed Finish DOUBLE WALL PIPE F0895 12 8DM 12 Section Double Wall Pipe Snap Lock F0896 18 8DM 18 Section Double Wall Pipe Snap...

Page 17: ...SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE TOP TERMINATION WITH SLIP SECTION F0923 ETLO 8DM Square Top with Mesh and Slip Section ADJUSTABLE HOOD Required when installing a...

Page 18: ...8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock F0886 30E 8HT 30 Degree Hi Temp Offset and Return F0887 12S 8HT Hi Temp Chimney Support For...

Page 19: ...r propane gas Fuel products with abnormal burning characteristics including but not limited to fuel such as driftwood coal or plywood and wood products using a binder may burn at excessive temperature...

Page 20: ...ecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2013 IHP LLC P N 126650 01 Rev B 10 2015 P126650 01 1508 Elm Hill Pike Suite 108 Nashville TN 3...

Reviews: