7. Display Controller Operation

7.1. Guide for operation

When the heat pump connects to the power, the LED display shows a code for 3 seconds which indicates the heat
pump model.

7.2 The keys and their operations

7.2.1

button

Press

to start the heat pump unit, the LED display shows the desired water temperature for 5 seconds,

then shows the inlet water temperature and the operation mode.

Press

to stop the heat pump unit and show “OFF”

Notice : During the parameter checking and setting, press the

to quick-exit and save the current setting .

Press

again to turn on/off the machine.

7.2.2

button

Press

for 5 seconds to switch the heating mode and auto mode.

7.2.3

and

button

Lock/unlock the display:

Hold

and

for 5 seconds to lock/Unlock the display.

Water temperature setting:

Press

or

to set the water temperature directly.

7.

7.

7.

Start-up

Start-up

Start-up

of

of

of

the

the

the

Heat

Heat

Heat

Pump

Pump

Pump

Summary of Contents for PRO ELYO INVERBOOST NN 68821

Page 1: ...WEMBAD WARMTEPOMP Gebruiker en service manual BOMBA DE CALOR PARA PISCINA Manual del usuario y de servicio SCHWIMMBAD W RMEPUMPE Benutzer und Wartungshandbuch PISCINA POMPA DI CALORE Istruzioni per l...

Page 2: ......

Page 3: ...CO2 Regulation P1 ENGLISH P09 FRENCH P65 NEDERLAND P121 SPANISH P176 GERMANY P232 ITALY P289 PORTUGAL P343...

Page 4: ......

Page 5: ...s required to be checked for leaks shall establish and maintain records for each piece of such equipment specifying the following information a The quantity and type of fluorinated greenhouse gases in...

Page 6: ...d quipements qui doivent faire l objet d un contr le d tanch it tablissent et tiennent jour pour chaque pi ce de ces quipements des registres dans lesquels ils consignent les informations suivantes a...

Page 7: ...cht zijn op lekkage te controleren zullen registers aanmaken en bijhouden voor elk deel van dergelijke apparatuur dat de volgende informatie bevat a De hoeveelheid en het type van de ge nstalleerde ge...

Page 8: ...erificar fugas deber n establecer y mantener registros para cada pieza de dicho equipo especificando la siguiente informaci n A La cantidad y el tipo de gases fluorados de efecto invernadero instalado...

Page 9: ...und verwalten a Die Menge und Art der installierten fluorierten Treibhausgase b Die Mengen an fluorierten Treibhausgasen die w hrend der Installation Wartung oder Service oder aufgrund von Leckagen h...

Page 10: ...tura del relativo tipo e dimensioni Conservazione di registri 1 Gli operatori di attrezzatura che necessario per controllare la presenza di perdite deve stabilire e mantenere i record per ogni pezzo d...

Page 11: ...quipamentos que devem ser verificados quanto a vazamentos devem estabelecer e manter registros para cada pe a de equipamento especificando as seguintes informa es a Quantidade e tipo de gases fluorado...

Page 12: ...8...

Page 13: ...9 SWIMMING POOL HEAT PUMP PRO ELYO INVERBOOST NN User and Service manual...

Page 14: ...nection 6 Electrical Wiring 7 Start up of the Heat Pump 8 Troubleshooting 9 Exploded Diagram Thank you for using PRO ELYO INVERBOOST NN swimming pool heat pump for your pool heating it will heat your...

Page 15: ...Pump Water connection assembly 50 mm pcs 2 User and service manual Reducer connection 10 meters signal wire Waterproof box Winter cover Anti vibration base pcs 4 1 2 Dimension Model 71676 1 1 1 Descr...

Page 16: ...12 Models 71677 71678 71679 Models 71680 71681 1 1 1 Description Description Description...

Page 17: ...13 Models 71682 71683 68821 68822 68823 1 1 1 Description Description Description...

Page 18: ...st be stored and transferred in vertical position in its original packaging If it is not the case it cannot be operated until a minimum period of 24H has passed before the unit can have the electrical...

Page 19: ...78 Heating capacity Kw 2 41 1 5 3 13 2 0 3 87 2 7 5 1 3 15 Power consumption Kw 1 21 0 35 1 42 0 53 1 76 0 69 2 32 0 81 C O P 4 3 2 3 8 2 2 3 9 2 2 3 9 2 2 General data Compressor type MITSUBISHI INV...

Page 20: ...apacity Kw 5 8 3 6 7 58 4 3 10 4 5 9 12 74 7 4 Power consumption Kw 2 64 0 92 3 45 1 1 4 73 1 51 5 79 1 95 C O P 3 9 2 2 3 9 2 2 3 9 2 2 3 8 2 2 General data Compressor type MITSUBISHI INVERTER COMPRE...

Page 21: ...ty Kw 10 4 5 9 11 6 3 1 11 6 3 1 Power consumption Kw 4 73 1 51 4 77 0 6 4 77 0 6 C O P 3 9 2 2 5 2 2 45 5 2 2 45 General data Compressor type MITSUBISHI INVERTOR COMPRESSOR Voltage V 380V 50Hz or 60H...

Page 22: ...y Pass Kit The By Pass Kit is the essential accessory for the installation of your heat pump it is also a tool for the optimization of the heating of the water The valves allows the optimum flow of wa...

Page 23: ...Water Inlet outlet connection 1 Install the two joints like the picture shows 2 Screw them onto the water Inlet outlet connection Mains Cable wiring 1 Open the cover of the terminal box marked red on...

Page 24: ...e air inlet Such locations impair the continuous supply of fresh air resulting in reduced efficiency and possibly preventing sufficient heat output 5 1 Heat pump location The unit will work properly i...

Page 25: ...he heat exchanger For this reason equipment of this sort must always be fitted in the piping on the downstream side of the heat pump and it is recommended to install a check valve to prevent reverse f...

Page 26: ...heat pump will not start up if the water is not circulating 5 3 Typical arrangement This arrangement is only an illustrative example NOTE The factory supplies only the heat pump All other components i...

Page 27: ...et the temperature 28 C the heat pump will stop when the temperature at 29 C While it will restart when the temperature of the water down to 27 C Depending on the initial temperature of the water in t...

Page 28: ...water leak 5 6 Pressure gauge display R32 Examine the pressure gauge which indicates the refrigerant gas pressure of the unit the below table shows the normal value of the gas pressure R32 when the m...

Page 29: ...25 6 1 Inverter swimming pool heat pump wiring diagram Ref 71676 71677 71678 71679 71680 6 6 6 Electrical Electrical Electrical Wiring Wiring Wiring...

Page 30: ...26 6 2 Inverter swimming pool heat pump wiring diagram Ref 71681 6 6 6 Electrical Electrical Electrical Wiring Wiring Wiring...

Page 31: ...27 6 3 Inverter swimming pool heat pump wiring diagram Ref 71682 71683 6 6 6 Electrical Electrical Electrical Wiring Wiring Wiring...

Page 32: ...28 6 4 Inverter swimming pool heat pump wiring diagram Ref 68822 R410A 6 6 6 Electrical Electrical Electrical Wiring Wiring Wiring...

Page 33: ...ming pool heat pump wiring diagram Ref 68821 68823 R410A Above electrical wiring diagram only for your reference please subject machine posted the wiring diagram 6 6 6 Electrical Electrical Electrical...

Page 34: ...tolerance of acceptable voltage variation is 10 during operation The connections must be dimensioned according to the power of the device and the state of installation Models Circuit breaker Maximum l...

Page 35: ...the control panel photo1 The other end of the signal wire photo2 Open the cover of the terminal box and pass through it the cable of the remote screen photo3 4 Insert the wiring into the designated p...

Page 36: ...32 Dry contact timer connection Timer Dry contact pump connection 6 6 6 Electrical Electrical Electrical Wiring Wiring Wiring...

Page 37: ...ater temperature and the operation mode Press to stop the heat pump unit and show OFF Notice During the parameter checking and setting press the to quick exit and save the current setting Press again...

Page 38: ...equency limitation code 0 No frequency limit 1 Coil pipe temperature limit 2 Overheating or overcooling frequency limit 4 Drive Current frequency limit 8 Drive voltage frequency limit 16 Drive high te...

Page 39: ...D6 PAC PROELYO INVERBOOST NN 35 35 8Kw 68823 0CD7 PAC PROELYO INVERBOOST NN 35T 35 8Kw Product code parameter P Modbus Only Press for 5 second the first digital number flashes press or to choose the t...

Page 40: ...7 2 9 Press this button the light will be flash the heat pump will operate in Full output only 7 2 10 While you choose the Smart the heat pump will just operate in Medium output and Full output When i...

Page 41: ...ng and cooling switch Cooling only You can switch Heating only and Auto mode by pressing for 5 seconds no matter the unit is on or off Operation logic of Auto Mode Both lights are on Heat Light On 7 7...

Page 42: ...t 3 minutes after the filtration pump exit the standby mode to detect the water temp T1 again Cooling mode T1 Tset 1 last for 30 minutes T1 29 last for 30 minutes Filtration pump will enter standby mo...

Page 43: ...l be in Standby stop working until the water temperature drops to less 28 8 When you select the Powerful working mode T1 Tset 1 T1 29 Powerful mode frequency F10 F9 9 T1 Tset 1 T1 29 HP will be in Sta...

Page 44: ...quency F2 F1 7 T1 Tset T1 28 Smart mode frequency F5 8 When you select the Powerful working mode T1 Tset 1 T1 27 Powerful mode frequency F10 F9 9 T1 Tset 1 T1 27 Standby 10 Re start to cool water in s...

Page 45: ...or failure T6 TH3 PP06 1 The sensor in open or short circuit 2 The wiring of sensor is loose 1 Check or change the sensor 2 Re fix the wiring of the sensors Antifreeze protection in Winter PP07 Ambien...

Page 46: ...ystem has been blocked 4 Exhaust temp Sensor failure 1 Check the high pressure gauge if too low fill with some gas 2 Check the waterway system and filtration pump 3 Check the piping system if there wa...

Page 47: ...he current becomes larger 4 Compressor or driver board damaged 1 Program error turn off electricity supply and restart after 3 minutes 2 Change driver board 3 Check compressor sequence connection VDC...

Page 48: ...DC motor is damaged 2 Main board is damaged 3 The fan blade is stuck 1 Detect DC motor replace with a new one 2 Change a new main board 3 Find out the barrier and work it out PFC module thermal circu...

Page 49: ...ew one Ambient Temperature device failure on Driver board EE24 Ambient Temperature device failure Change driver board or main board Compressor phase failure EE25 Compressors U V W are connected to one...

Page 50: ...r 7 LED controller displays PP11 for water over cooling protection EE04 Water Overheating Protection PP11 Water Overcooling Protection For example as below Mode Output water temperature Set point temp...

Page 51: ...s show defects 3 Controller defect 1 Adjust the mode to proper running 2 Replace the defect LED wire controller and then check the status after changing the running mode verifying the water inlet and...

Page 52: ...48 9 1 Exploded Diagram Mode 71676 9 9 9 Exploded Exploded Exploded Diagram Diagram Diagram...

Page 53: ...3060123 Tube 16 1330900261 Left side panel 49 121000006 4 way valve 17 132000015 Fan blade 50 150000110 Drainage plug 18 1330900251 Front panel 51 117110012 Water inlet temp sensor T1 TH6 19 108010014...

Page 54: ...50 9 3 Model 71677 71678 71679 9 9 9 Exploded Exploded Exploded Diagram Diagram Diagram...

Page 55: ...on piping 16 1330900261 Left side panel 50 113070044 Exchanger to EEV 17 108010024 Fan shaft cover 51 113900082 Water connection sets 18 132000015 Fan blade 52 112100021 1 Water flow switch 19 1330900...

Page 56: ...16 1330900261 Left side panel 50 113070044 Exchanger to EEV 17 108010024 Fan shaft cover 51 113900082 Water connection sets 18 132000015 Fan blade 52 112100021 1 Water flow switch 19 133090025 Front...

Page 57: ...16 1330900261 Left side panel 50 113070041 Exchanger to EEV 17 108010024 Fan shaft cover 51 113900082 Water connection sets 18 132000015 Fan blade 52 112100021 1 Water flow switch 19 1330900251 Front...

Page 58: ...54 9 7 Model 71680 71681 9 9 9 Exploded Exploded Exploded Diagram Diagram Diagram...

Page 59: ...changer 17 1332600051 Left side panel 53 119000021 EEV 18 1332600031 Front panel 54 113080056 EEV to distribution piping 19 108170017 Fan grill 55 150000110 Drainage plug 20 108560036 Base tray 56 108...

Page 60: ...exchanger 17 1332600051 Left side panel 53 119000021 EEV 18 1332600031 Front panel 54 113080056 EEV to distribution piping 19 108170017 Fan grill 55 150000110 Drainage plug 20 108560036 Base tray 56...

Page 61: ...57 9 10 Model 71682 71683 9 9 9 Exploded Exploded Exploded Diagram Diagram Diagram...

Page 62: ...filter pipe 19 132000015 Fan blade 59 112100021 1 Water flow switch 20 108010024 Fan shaft cover 60 117110011 Water outlet temp sensor T2 TH5 21 133250004 Left side panel 61 108010025 Exchanger temper...

Page 63: ...filter pipe 19 132000015 Fan blade 59 112100021 1 Water flow switch 20 108010024 Fan shaft cover 60 117110011 Water outlet temp sensor T2 TH5 21 133250004 Left side panel 61 108010025 Exchanger temper...

Page 64: ...60 9 13 Model 68821 68822 68823 9 9 9 Exploded Exploded Exploded Diagram Diagram Diagram...

Page 65: ...panel 59 133020011 Red rubber ring 20 108010014 Fan grill 60 133020026 Rubber ring on water connection 21 108550009 Pillar 61 112100021 1 Water flow switch 22 108550005 Base tray 62 116000001 2 Sealin...

Page 66: ...50001 Front panel 59 133020011 Red rubber ring 20 108010014 Fan grill 60 133020026 Rubber ring on water connection 21 108550009 Pillar 61 112100021 1 Water flow switch 22 108550005 Base tray 62 116000...

Page 67: ...nt panel 59 133020011 Red rubber ring 20 108010014 Fan grill 60 133020026 Rubber ring on water connection 21 108550009 Pillar 61 112100021 1 Water flow switch 22 108550005 Base tray 62 116000001 2 Sea...

Page 68: ...sure You should drain the water from the heat pump if it will stop running for a long time especially during the winter season or when the ambient temperature drops below 0 C 4 Check the water levels...

Page 69: ...65 Pompe chaleur pour piscine PRO ELYO INVERBOOST NN Manuel d installation et d utilisation...

Page 70: ...NN pour votre piscine Elle va chauffer l eau de votre piscine et la maintenir une temp rature constante lorsque la temp rature ambiante varie de 20 50 C Nous avons accord notre plus grande attention l...

Page 71: ...ques sortie entr e en 50 mm Qt 2 Manuel d installation et d utilisation Raccords d vacuation des condensats C ble de 10 m tres pour d porter la commande Capot de protection pour la protection de la co...

Page 72: ...68 Modes 71677 71678 71679 Modes 71680 71681 1 1 1 Descriptif Descriptif Descriptif...

Page 73: ...69 Modes 71682 71683 68821 68822 68823 1 1 1 Descriptif Descriptif Descriptif...

Page 74: ...ce d incendie Une pompe chaleur doit tre stock e et d plac e en position verticale dans son emballage d origine Si ce n est pas le cas elle ne peut tre mise en marche imm diatement Un d lai minimum de...

Page 75: ...35 1 42 0 53 1 76 0 69 2 32 0 81 C O P 4 3 2 3 8 2 2 3 9 2 2 3 9 2 2 Donn es g n rales Marque du compresseur MITSUBISHI INVERTER COMPRESSOR Alimentation lectrique V 220 240V 50Hz or 60Hz 1PH Courant M...

Page 76: ...sommation d nergie Kw 2 64 0 92 3 45 1 1 4 73 1 51 5 79 1 95 C O P 3 9 2 2 3 9 2 2 3 9 2 2 3 8 2 2 Donn es g n rales Marque du compresseur MITSUBISHI INVERTER COMPRESSOR Alimentation lectrique V 220 2...

Page 77: ...0 6 C O P 3 9 2 2 5 2 2 45 5 2 2 45 Donn es g n rales Marque du compresseur MITSUBISHI INVERTOR COMPRESSOR Alimentation lectrique V 380V 50Hz or 60Hz 3PH 220 240V 50Hz or 60Hz 1PH 380V 50Hz or 60Hz 3P...

Page 78: ...optimiser le d bit d eau et gr ce au manom tre de s assurer du bon fonctionnement du compresseur voir paragraphe 5 6 contr le de la pression Patin caoutchouc anti vibration qt 4 Connecteur d vacuation...

Page 79: ...connecteurs d admission et de sortie d eau dans la pompe chaleur 2 Installez les raccords comme sur la photo ci contre 3 Vissez sur l entr e et la sortie d eau C ble alimentation 1 Otez le couvercle...

Page 80: ...ntinue de l air Il faut s assurer que l entr e d air ne puisse jamais tre obstru e Les feuilles et autres d bris peuvent se coller sur l vaporateur ce qui r duira son efficacit mais aussi affectera la...

Page 81: ...es produits chimiques concentration trop lev e qui pourraient corroder l changeur thermique Pour cette raison ce type d quipement doit tre install en aval de la pompe chaleur Il est recommand d instal...

Page 82: ...ad quat 5 3 Installation Ce montage est un exemple illustratif NOTE Seule la pompe chaleur est fournie Les l ments n cessaires son installation y compris le by pass doivent tre fournis par l utilisat...

Page 83: ...la piscine et de la temp rature de l air il est n cessaire de faire fonctionner l installation pendant plusieurs jours pour chauffer l eau la temp rature souhait e Une bonne protection de la piscine c...

Page 84: ...s consid r tort comme une fuite d eau 5 6 Contr le de la pression R32 Examinez l indicateur de pression du gaz de refroidissement qui indique les conditions de travail de l unit Unit Condition Arr t c...

Page 85: ...81 6 1 Sch ma de c blage de la pompe chaleur de piscine Ref 71676 71677 71678 71679 71680 6 6 6 C C C blage blage blage lectrique lectrique lectrique...

Page 86: ...82 6 2 Sch ma de c blage de la pompe chaleur de piscine Ref 71681 6 6 6 C C C blage blage blage lectrique lectrique lectrique...

Page 87: ...83 6 3 Sch ma de c blage de la pompe chaleur de piscine Ref 71682 71683 6 6 6 C C C blage blage blage lectrique lectrique lectrique...

Page 88: ...84 6 4 Sch ma de c blage de la pompe chaleur de piscine Ref 68822 R410A 6 6 6 C C C blage blage blage lectrique lectrique lectrique...

Page 89: ...age de la pompe chaleur de piscine Ref 68821 68823 R410A Les sch mas lectriques ci dessus sont pour votre r f rence merci de se r f rer ceux appos sur la machine 6 6 6 C C C blage blage blage lectriqu...

Page 90: ...fonctionnement Les raccordements doivent tre dimensionn s en fonction de la puissance de l appareil et de l tat de l installation Modes Protection t te de ligne Longueur maximum de c ble 2 5 mm 4 mm 6...

Page 91: ...ation 6 7 Installation de la commande d port e Photo 1 Photo 2 Photo 3 Photo 4 Photo 5 1 Raccordez le fil du signal avec le contr leur sur les broches photos 1 et 2 2 Passez le fil au travers du bloc...

Page 92: ...clencher l horloge de la filtration mode priorit chauffage Minuteur Bornier Raccordement direct pour le pilotage de la pompe de filtration mode priorit chauffage 6 6 6 C C C blage blage blage lectriq...

Page 93: ...z sur pour arr ter la pompe chaleur l unit s arr te et l cran affiche OFF Attention Apr s toute mise jour appuyez sur pour sauvegarder la consigne et sortir du Mode r glage Appuyez sur pour arr ter d...

Page 94: ...rature d chappement du gaz 0 C5 125 Valeur test exact par d faut d7 Position du moteur pas pas 0 99 N 5 d8 Fr quences de fonctionnement du compresseur 0 99Hz Valeur test exact par d faut d9 Intensit d...

Page 95: ...loge d arr t et de Marche sont programm Mode 0 l horloge et hors fonction les param tres P5 P6 ne sont pas actifs P3 Pilotage de la pompe filtration 0 1 0 Mode 1 toujours en fonctionnement Mode 0 d pe...

Page 96: ...f 7 2 9 Mode Powerful Appuyez sur ce bouton la LED s claire et le mode Powerful est actif Si vous choisissez Power la pompe chaleur fonctionne en Powerful 7 2 10 Mode Smart Appuyez sur ce bouton la LE...

Page 97: ...t seul Vous pouvez changer le mode de fonctionnement en appuyant sur pendant 5 secondes peu importe si l appareil est allum ou teint Logique de fonctionnement du mode Auto mode Fonctionnement du mode...

Page 98: ...apr s que la pompe de filtration a quitt le mode veille pour d tecter nouveau la temp rature de l eau T1 Mode de refroidiss ement T1 Tset 1 dure 30 minutes T1 29 dure 30 minutes La pompe de filtration...

Page 99: ...e l eau atteigne une temp rature inf rieure 28 8 Lorsque vous s lectionnez le mode Powerful T1 Tset 1 T1 29 Mode Powerful fr quence F10 F9 9 T1 Tset 1 T1 29 La pompe chaleur sera en veille et cessera...

Page 100: ...T1 Tset T1 28 Mode Smart fr quence F5 8 Lorsque vous s lectionnez le mode Powerful T1 Tset 1 T1 27 Mode Powerful fr quence F10 F9 9 T1 Tset 1 T1 27 Pr t fonctionner 10 Red marrage pour refroidir de l...

Page 101: ...refroidissement T6 TH3 PP06 Le capteur est en circuit ouvert ou en court circuit V rifiez ou remplacez le capteur Protection antigel du premier niveau en hiver PP07 La temp rature ambiante ou la temp...

Page 102: ...r le d tecteur de d bit et la sonde T2 TH5 Protection temp rature d chappement T6 TH3 EE05 1 R frig rant ne suffit pas 2 Le d bit d eau n est pas suffisant 3 Filtre ou vanne lectronique bloqu 4 D faut...

Page 103: ...nt 3 Accumulation liquide et gaz 4 Compresseur ou la carte est d faillante 1 Erreur de programmation couper l alimentation lectrique et d marrer apr s 3 minutes 2 Changer la carte 3 V rifier les phase...

Page 104: ...r DC EE17 1 Le moteur du ventilateur est d fectueux 2 La carte lectronique est d fectueuse 3 Les h lices sont d fectueuses 1 V rifiez le moteur du ventilateur 2 Changer la carte lectronique 3 V rifier...

Page 105: ...nger le compresseur Temp rature ambiante ou carte lectronique EE24 La temp rature ambiante ou la temp rature d eau arriv e est trop faible V rifier et changer la carte lectronique D faut alimentation...

Page 106: ...ement excessif de l eau EE04 En mode chauffage d faut surchauffe temp rature T2 PP11 T2 Temp rature de l eau trop froide protection en mode refroidissement Par exemple comme ci dessous Mode Temp ratur...

Page 107: ...2 Les chiffres montrent des d faillances 3 D faillance du contr leur 1 R glez le mode la bonne fonction 2 Remplacez le contr leur LED en panne puis v rifiez l tat apr s avoir chang le mode de fonctio...

Page 108: ...104 9 1 Sch ma clat Mode 71676 9 Sch ma clat et entretien...

Page 109: ...113060123 Tube vanne 4 voies vers changeur 16 1330900261 Panneau c t gauche 49 121000006 Sonde haute pression 17 132000015 P le ventilateur 50 150000110 Tube 18 1330900251 Panneau avant 51 117110012...

Page 110: ...106 9 3 Mod le 71677 71678 71679 9 Sch ma clat et entretien...

Page 111: ...tribution 16 1330900261 Panneau c t gauche 50 113070044 Echangeur EEV 17 108010024 Cache de tube de moteur courant continu 51 113900082 Raccord visser 18 132000015 P le ventilateur 52 112100021 1 D te...

Page 112: ...16 1330900261 Panneau c t gauche 50 113070044 Tube changeur vers EEV 17 108010024 Commande d tenteur lectronique 51 113900082 Raccord visser 18 132000015 P le ventilateur 52 112100021 1 D tecteur de d...

Page 113: ...tion gaz 16 1330900261 Panneau c t gauche 50 113070041 Tube changeur vers EEV 17 108010024 Commande d tenteur lectronique 51 113900082 Raccord visser 18 132000015 P le ventilateur 52 112100021 1 D tec...

Page 114: ...110 9 7 Mod le 71680 71681 9 Sch ma clat et entretien...

Page 115: ...vers changeur 17 1332600051 Panneau c t gauche 53 119000021 D tenteur lectronique 18 1332600031 Panneau avant 54 113080056 EEV la tuyauterie de distribution 19 108170017 Grille de protection ventilate...

Page 116: ...vers changeur 17 1332600051 Panneau c t gauche 53 119000021 D tenteur lectronique 18 1332600031 Panneau avant 54 113080056 EEV la tuyauterie de distribution 19 108170017 Grille de protection ventilate...

Page 117: ...113 9 10 Mod le 71682 71683 9 Sch ma clat et entretien...

Page 118: ...ube changeur vers filtre 19 132000015 P le ventilateur 59 112100021 1 D tecteur de d bit 20 108010024 Cache de tube de moteur courant continu 60 117110011 Sonde de temp rature de sortie d eau T2 TH5 2...

Page 119: ...ube changeur vers filtre 19 132000015 P le ventilateur 59 112100021 1 D tecteur de d bit 20 108010024 Cache de tube de moteur courant continu 60 117110011 Sonde de temp rature de sortie d eau T2 TH5 2...

Page 120: ...116 9 13 Mod le 68821 68822 68823 9 Sch ma clat et entretien...

Page 121: ...Panneau avant 59 133020011 Joint rouge 20 108010014 Grille de protection ventilateur 60 133020026 Joint raccord d eau 21 108550009 Pilier arri re gauche 61 112100021 1 D tecteur de d bit 22 108550005...

Page 122: ...9 133250001 Panneau avant 59 133020011 Joint rouge 20 108010014 Grille de protection ventilateur 60 133020026 Joint raccord d eau 21 108550009 Pilier arri re gauche 61 112100021 1 D tecteur de d bit 2...

Page 123: ...au avant 59 133020011 Joint rouge 20 108010014 Grille de protection ventilateur 60 133020026 Joint raccord d eau 21 108550009 Pilier arri re gauche 61 112100021 D tecteur de d bit 22 108550005 Base 62...

Page 124: ...haleur pour emp cher des dommages du gel au cours de l hiver et ou pendant une longue p riode d inactivit 4 Remplir enti rement le circuit d eau avant de faire fonctionner l unit nouveau 5 Lorsque l u...

Page 125: ...121 Zwembad warmtepomp PRO ELYO INVERBOOST NN Installatie Instructie Handleiding...

Page 126: ...iagram Dank u voor het gebruiken van de zwembad warmtepomp voor uw zwembad verwarming het zal uw zwembadwater verwarmen en het op een constante temperatuur houden wanneer de omgevingstemperatuur 20 to...

Page 127: ...omponenten vinden Hydraulische overgangen IN OUT in 50 mm 2 stuks Installatie en Instructie Handleiding Waterdrainage flexibel buizen Kabel van 10 meters om de bedieningspaneel te deporteren Watervast...

Page 128: ...124 Model 71677 71678 71679 Model 71680 71681 1 Afmetingen...

Page 129: ...125 Model 71682 71683 68821 68822 68823 1 Afmetingen...

Page 130: ...48 UUR TE BEVESTIGEN 2 2 Opslag Het magazijn moet helder ruim open goed geventileerd zijn ventilatie apparatuur hebben en geen vuurbron Warmtepomp moet worden opgeslagen en in verticale positie in de...

Page 131: ...et water 26 luchtvochtigheid 78 Verwarmingscapaciteit Kw 2 41 1 5 3 13 2 0 3 87 2 7 5 1 3 15 Energieverbruik Kw 1 21 0 35 1 42 0 53 1 76 0 69 2 32 0 81 C O P 4 3 2 3 8 2 2 3 9 2 2 3 9 2 2 Algemene dat...

Page 132: ...eit Kw 5 8 3 6 7 58 4 3 10 4 5 9 12 74 7 4 Energieverbruik Kw 2 64 0 92 3 45 1 1 4 73 1 51 5 79 1 95 C O P 3 9 2 2 3 9 2 2 3 9 2 2 3 8 2 2 Algemene data Compressor MITSUBISHI INVERTER COMPRESSOR Spann...

Page 133: ...mingscapaciteit Kw 10 4 5 9 11 6 3 1 11 6 3 1 Energieverbruik Kw 4 73 1 51 4 77 0 6 4 77 0 6 C O P 3 9 2 2 5 2 2 45 5 2 2 45 Algemene data Compressor MITSUBISHI INVERTOR COMPRESSOR Voltage V 380V 50Hz...

Page 134: ...4 1 Toebehoren Anti vibratie schaatsen 4 stuks Aftap buis 2 stuks Watervaste kist 1 stuk 10M Signaal draad 1 stuk Modbus signaaldraad 1 st Water drainagebuizen 2 pcs Winter Cover 1 st 4 Toebehoren li...

Page 135: ...r beschadigen Water invoer uitvoer verbinding 1 Gebruik de buis tape om de water invoer uitvoer verbinding op de warmtepomp te verbinden 2 Installeer de twee verbindingen zoals op het plaatje getoond...

Page 136: ...met het starten van de warmtepomp 5 2 Warmtepomp plaatsing Het apparaat zal goed werken in elke gewenste locatie zolang de volgende drie onderdelen aanwezig zijn 1 Frisse lucht 2 Elektriciteit 3 Zwemb...

Page 137: ...emperatuur van de grond die de muis omringd Dit verhoogt de werktijd met 3 tot 5 5 4 Controle klep installatie Opmerking als een automatische dosering apparaat voor chloor en zuur pH gebruikt wordt is...

Page 138: ...en gecontroleerd voer dan de volgende procedure uit 1 Zet de filterpomp aan Controleer op lekkage en verifieer dat het water stroomt van en naar het zwembad 2 Sluit de stroom aan de waterpomp aan en...

Page 139: ...oopt Zelfs een korte stroomonderbreking zal deze tijdvertraging starten en voorkomen dat het apparaat onmiddellijk herstart Meerdere stroomonderbrekingen tijdens deze vertraging periode hebben geen ef...

Page 140: ...136 6 Elektrische bedrading 6 1 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA R f 71676 71677 71678 71679 71680 6 Elektrische schema...

Page 141: ...137 6 2 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA R f 71681 6 Elektrische schema...

Page 142: ...138 6 3 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA R f 71682 71683 6 Elektrische schema...

Page 143: ...139 6 4 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Ref 68822 R410A 6 Elektrische schema...

Page 144: ...140 6 5 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Ref 68821 68823 R410A 6 6 6 Electrical Electrical Electrical Wiring Wiring Wiring...

Page 145: ...land van installatie Het warmtepompcircuit moet worden aangesloten op een veiligheidscircuit op het klemmenblok De kabels moeten correct zijn ge nstalleerd om interferentie te voorkomen De pomp is be...

Page 146: ...n met het doorvoerpakket foto 4 5 en beiden direct te verbinden 6 6 Installatie van de Modbus Fluidra Connect signaaldraad Foto 6 Foto 7 Foto 8 Foto 9 Open het klepje van de aansluitingen foto6 Pak de...

Page 147: ...143 Droog contact timer verbinding Timer Dry contact pomp aansluiting 6 Elektrische schema...

Page 148: ...het water en van de werking mode Druk op om de warmtepomp te stoppen en te laten zien OFF Opmerking Tijdens de parameter controle en instelling druk op de snel exit en sla de huidige instelling Druk...

Page 149: ...rde d7 Stap van EEV 0 99 N 5 d8 Compressor loopt frequentie 0 99Hz Real testen waarde d9 compressor huidige 0 30A Real testen waarde d10 Huidige ventilatorsnelheid 0 1200 rpm Real testen waarde d11 Er...

Page 150: ...meter P instelling alleen MOBUS Druk gedurende 5 seconden op het eerste digitale nummer knippert druk op of om het doelnummer uit 0 F te kiezen en druk vervolgens op Go om het tweede nummer aan te pas...

Page 151: ...wanneer het in werking is 7 2 9 Op deze knop drukt zal de lichtflits zal de warmtepomp werken in Full output alleen 7 2 10 Terwijl u de Smart kiest zal de warmtepomp net opereren in Medium output en...

Page 152: ...omatische modus verwarmings en koelingschakelaar alleen koeling U kunt de verwarmingsmodus en de automatische modus inschakelen door gedurende 5 seconden op te drukken ongeacht of het apparaat aan of...

Page 153: ...n en opnieuw opstarten De warmtepomp start 3 minuten nadat de waterpomp de stand bymodus heeft verlaten om de watertemperatuur te detecteren T1 opnieuw Koelmodus T1 Tset 1 duurt 30 minuten T1 29 duurt...

Page 154: ...and by zijn stoppen met werken totdat het water op temperatuur zakt tot minder dan 28 8 Wanneer u de Krachtige werkmodus selecteert T1 Tset 1 T1 29 Krachtige modus frequentie F10 F9 9 T1 Tset 1 T1 29...

Page 155: ...ille modus Frequentie F2 F1 7 T1 Tset T1 28 Smart modus frequency F5 8 Wanneer u de Krachtige werkmodus selecteert T1 Tset 1 T1 27 Krachtige modus frequentie F10 F9 9 T1 Tset 1 T1 27 Standby 10 Start...

Page 156: ...r T5 TH1 PP05 1 De sensor in open of kortsluiting 2 De bedrading van de sensor zit los 1 Controleer of verander de sensor 2 Re fix de bedrading van de sensoren Uitlaatpijpsensor defect T6 TH3 PP06 1 D...

Page 157: ...pomp of het vaarwegsysteem Oververhittingsbeve iliging voor watertemperatuur T2 TH5 in verwarmingsmodus EE04 1 Lage waterstroom 2 Waterstroomschakelaar zit vast en de watertoevoer is afgesneden 3 T2 T...

Page 158: ...ad is beschadigd 1 Controleer de draadverbinding 2 Verander een nieuwe draad VDC voltage te hoge beveiliging EE10 1 Moeder lijnspanning is te hoog 2 Driver board is beschadigd 1 Controleer of het verm...

Page 159: ...ontroleer of het motortoerental te laag is of dat de ventilatormotor beschadigd is verander een andere 3 Een ander ventilatorblad verwisselen 4 Controleer de ingangsspanning Storing DC ventilatormotor...

Page 160: ...compressor of wijzig een nieuwe Apparaatstoring in omgevingstemperatu ur op stuurkaart EE24 Apparaatstoring bij omgevingstemperatuur Wijzig driverbord of hoofdbord Defect compressorfase EE25 Compresso...

Page 161: ...roller defect 1 Stel de goede modus in 2 Vervang de defecte LED draad controller en controleer dan de status na het veranderen van de werkende modus controleer de water inlaat en uitlaattemperatuur 3...

Page 162: ...ingestelde temperatuur boven 7 geeft LED controller PP11 weer voor bescherming tegen overkoeling van water EE04 Bescherming tegen oververhitting van water PP11 Bescherming tegen overcooling van water...

Page 163: ...159 9 1 Opengeklapt diagram Model 71676 9 Open geklapt diagram...

Page 164: ...48 113060123 Gasbuis 16 1330900261 Linkerkant paneel 49 121000006 4 weg klep 17 132000015 Waaierblad 50 150000110 Drainage plug 18 1330900251 Voorpaneel 51 117110012 Water in temp sensor T1 TH6 19 108...

Page 165: ...161 Model 71677 71678 71679 9 Open geklapt diagram...

Page 166: ...ieleidingen 16 1330900261 Linkerkant paneel 50 113070044 Uitwisselaar van EEV 17 108010024 DC motorafdekking 51 113900082 Wateraansluitsets 18 132000015 Waaierblad 52 112100021 1 Waterstroomschakelaar...

Page 167: ...butieleidingen 16 1330900261 Linkerkant paneel 50 113070044 Uitwisselaar van eev 17 108010024 Dc motorafdekking 51 113900082 Wateraansluitsets 18 132000015 Waaierblad 52 112100021 1 Waterstroomschakel...

Page 168: ...80054 EEV naar distributieleidingen 16 1330900261 Linkerkant paneel 50 113070041 Uitwisselaar van EEV 17 108010024 DC motorafdekking 51 113900082 Wateraansluitsets 18 132000015 Waaierblad 52 112100021...

Page 169: ...165 Model 71680 71681 9 Open geklapt diagram...

Page 170: ...r wisselaar 17 1332600051 Linkerkant paneel 53 119000021 EEV 18 1332600031 Voorpaneel 54 113080056 EEV naar distributieleidingen 19 108170017 Grill aan de voorkant 55 150000110 Drainage plug 20 108560...

Page 171: ...r wisselaar 17 1332600051 Linkerkant paneel 53 119000021 EEV 18 1332600031 Voorpaneel 54 113080056 EEV naar distributieleidingen 19 108170017 Grill aan de voorkant 55 150000110 Drainage plug 20 108560...

Page 172: ...168 Model 71682 71683 9 Open geklapt diagram...

Page 173: ...teren 19 132000015 Waaierblad 59 112100021 1 Waterstroomschakelaar 20 108010024 DC motor afdekking 60 117110011 Water uit temp sensor T2 TH5 21 133250004 Linkerkant paneel 61 108010025 Wisselaar senso...

Page 174: ...teren 19 132000015 Waaierblad 59 112100021 1 Waterstroomschakelaar 20 108010024 DC motor afdekking 60 117110011 Water uit temp sensor T2 TH5 21 133250004 Linkerkant paneel 61 108010025 Wisselaar senso...

Page 175: ...171 Model 68821 68822 68823 9 Open geklapt diagram...

Page 176: ...001 Voorpaneel 59 133020011 Rode rubberen ring 20 108010014 Grill aan de voorkant 60 133020026 Rubberring op wateraansluiting 21 108550009 Pijler 61 112100021 1 Waterstroomschakelaar 22 108550005 Basi...

Page 177: ...luitsets 19 133250001 Voorpaneel 59 133020011 Rode rubberen ring 20 108010014 Grill aan de voorkant 60 133020026 Rubberring op wateraansluiting 21 108550009 Pijler 61 112100021 1 Waterstroomschakelaar...

Page 178: ...001 Voorpaneel 59 133020011 Rode rubberen ring 20 108010014 Grill aan de voorkant 60 133020026 Rubberring op wateraansluiting 21 108550009 Pijler 61 112100021 1 Waterstroomschakelaar 22 108550005 Basi...

Page 179: ...appen als het apparaat niet wordt gebruikt voor een langere periode speciaal tijdens het winterseizoen 4 In omgekeerde manier moet u controleren dat het apparaat volledig met water gevuld is voordat u...

Page 180: ...176 Bomba de calor para Piscina PRO ELYO INVERBOOST NN Manual del usuario y de servicio...

Page 181: ...uando est parada durante el invierno o cuando la temperatura ambiente descienda por debajo de 0 o de lo contrario el intercambiador de titanio se da ar por congelaci n en tal caso se perder la garant...

Page 182: ...r se suministra Conexi n agua de 50 mm pcs 2 Manual de instrucciones y servicio Conexi n condensados 10 metros de cable de se al Caja estanca Cubierta invernal Base de anti vibraci n pcs 4 1 2 Dimensi...

Page 183: ...179 Modelo 71677 71678 71679 Modelo 71680 71681 1 Descripci n...

Page 184: ...180 Modelo 71682 71683 68821 68822 68823 1 Descripci n...

Page 185: ...espacioso abierto bien ventilado con equipo de ventilaci n y sin fuente de fuego La bomba de calor debe almacenarse y transportarse en posici n vertical en su embalaje original Si no es el caso no se...

Page 186: ...7 5 1 3 15 Consumo de energ a Kw 1 21 0 35 1 42 0 53 1 76 0 69 2 32 0 81 C O P 4 3 2 3 8 2 2 3 9 2 2 3 9 2 2 Informacion General Tipo de compresor MITSUBISHI INVERTER COMPRESSOR Voltaje V 220 240V 50H...

Page 187: ...5 8 3 6 7 58 4 3 10 4 5 9 12 74 7 4 Consumo de energ a Kw 2 64 0 92 3 45 1 1 4 73 1 51 5 79 1 95 C O P 3 9 2 2 3 9 2 2 3 9 2 2 3 8 2 2 Informacion General Tipo de compresor MITSUBISHI INVERTER COMPRES...

Page 188: ...agua 26 humedad 78 Potencia Calor Kw 10 4 5 9 11 6 3 1 11 6 3 1 Consumo de energ a Kw 4 73 1 51 4 77 0 6 4 77 0 6 C O P 3 9 2 2 5 2 2 45 5 2 2 45 Informacion General Tipo de compresor MITSUBISHI INVER...

Page 189: ...agua 2 set Cubierta de invierno 1 pc 4 2 Kit By Pass El kit de By Pass es el accesorio indispensable para la instalaci n de la bomba de calor tambi n es una herramienta para la optimizaci n de la cal...

Page 190: ...omba de calor podr a da ar el compresor Entrada y salida de agua 1 Instale las dos juntas como muestra la imagen 2 Enrosquelas en las tomas de agua Juntas de entrada y salida Cableado 1 Abra la caja d...

Page 191: ...d o cerca de arbustos que podr an bloquear la entrada de aire Tales ubicaciones perjudican el suministro continuo de aire fresco lo que implicar una reducci n de la eficiencia y posiblemente reducci n...

Page 192: ...amente altas que puedan corroer el intercambiador de calor Por esta raz n un equipo de este tipo siempre debe instalarse en la tuber a aguas abajo de la bomba de calor y se recomienda instalar una v l...

Page 193: ...n t pica NOTA De f brica nicamente se suministra la bomba de calor Todos los dem s componentes incluyendo una derivaci n si es necesaria deben ser proporcionados por el usuario o el instalador 5 4 Pue...

Page 194: ...deseada Una cubierta para la piscina puede reducir dr sticamente el tiempo requerido NOTA La unidad esta equipada con un interruptor de flujo para la protecci n de la BdC con velocidad de flujo de ag...

Page 195: ...del gas R32 cuando la m quina est apagada o encendida Unidad condici n Apagada Temp ambiente C 5 5 5 15 15 25 25 35 Temp agua Presi n man metro MPa 0 59 0 85 0 85 1 18 1 18 1 59 1 59 2 1 Unidad condic...

Page 196: ...192 6 1 Esquema de cableado bomba de calor inverter Ref 71676 71677 71678 71679 71680 6 Cableado El ctrico...

Page 197: ...193 6 2 Esquema de cableado bomba de calor inverter Ref 78681 6 Cableado El ctrico...

Page 198: ...194 6 3 Esquema de cableado bomba de calor inverter Ref 71682 71683 6 Cableado El ctrico...

Page 199: ...195 6 4 Esquema de cableado bomba de calor inverter Ref 68822 R410A 6 Cableado El ctrico...

Page 200: ...6 5 Esquema de cableado bomba de calor inverter Ref 68821 68823 R410A Arriba diagrama de cableado el ctrico para su referencia por favor consulte en la m quina el diagrama de cableado 6 Cableado El ct...

Page 201: ...s necesidades y condiciones de uso La tolerancia de la variaci n de voltaje aceptable es 10 durante la operaci n Las conexiones se deben dimensionar seg n la potencia del dispositivo y el estado de in...

Page 202: ...el enchufe se conecta con el panel de control foto1 El otro lado del cable de se al foto2 Abra la tapa del cuadro de conexi n el ctrica y pase a trav s de ella el cable de la pantalla remota foto3 4...

Page 203: ...199 Temporizador de conexi n de contacto libre de tensi n Temporizador Conexi n de la bomba de contacto libre de tensi n 6 Cableado El ctrico...

Page 204: ...e LED muestra la temperatura del agua deseada durante 5 segundos luego muestra la temperatura del agua de entrada y el modo de operaci n Pulse para detener la bomba de calor y muestre OFF Aviso Durant...

Page 205: ...a descarga de gas T6 0 C5 125 Valor de prueba real d7 Paso de EEV 0 99 N 5 d8 Frecuencia de funcionamiento del compresor 0 99Hz Valor de prueba real d9 Corriente del compresor 0 30A Valor de prueba re...

Page 206: ...predeterminado despu s del restablecimiento Par metro de c digo de producto P Ajuste s lo MOBUS Presione durante 5 segundos el primer n mero digital parpadear presione o para seleccionar el n mero de...

Page 207: ...co la luz se encender cuando est en funcionamiento 7 2 9 Pulse este bot n la luz parpadear y la bomba de calor funcionar en Salida completa solamente 7 2 10 Mientras este en Smart la bomba de calor s...

Page 208: ...facci n y enfriamiento solo enfriamiento Puede cambiar el modo solo calefacci n y el modo autom tico presionando durante 5 segundos sin importar si la unidad est encendida o apagada L gica de operaci...

Page 209: ...ie La bomba de calor se reiniciar 3 minutos despu s de que la bomba de agua salga del modo de espera para detectar nuevamente la temperatura del agua T1 Modo de enfriamiento T1 Tset 1 dura 30 minutos...

Page 210: ...de espera y dejar de funcionar hasta que la temperatura del agua caiga a menos de 28 8 Cuando seleccionas el Modo Powerful T1 Tset 1 T1 29 Modo Powerfu frecuencia F10 F9 9 T1 Tset 1 T1 29 Bomba de ca...

Page 211: ...et 27 T1 28 Modo Silent frecuencia F2 F1 7 T1 Tset T1 28 Modo Smart frecuencia F5 8 Cuando seleccionas el Modo Powerful T1 Tset 1 T1 27 Modo Powerful frecuencia F10 F9 9 T1 Tset 1 T1 27 En espera 10 R...

Page 212: ...to abierto o cortocircuito 2 El cableado del sensor est suelto 1 Verifique o cambie el sensor 2 Reparar el cableado de los sensores Fallo del sensor de temperatura de descarga del compresor T6 TH3 PP0...

Page 213: ...omprobar el valor de la presi n 4 Comprobar el sistema de refrigeraci n No hay flujo de agua o fallo del interruptor de flujo de agua TS1 EE03 Or ON 1 El interruptor de flujo de agua est mal conectado...

Page 214: ...de energia principal Error de comunicaci n entre el controlador y la placa principal EE08 1 Conexi n de cable de se al d bil o cable de se al da ado 2 Mal funcionamiento del controlador 1 Compruebe y...

Page 215: ...l m dulo IPM demasiado alta EE15 1 Excepci n de salida del circuito t rmico del m dulo IPM 2 Motor es anormal o da ado 3 La hoja de ventilador est rota 1 Cambiar una tarjeta de conductor 2 Compruebe s...

Page 216: ...contacto deficiente o desconectado 3 Acumulaci n de l quido dentro 4 Conexi n de fase incorrecta para el compresor 1 Compruebe o cambie el controlador 2 Compruebe el cableado del compresor de acuerdo...

Page 217: ...de 7 C el controlador LED muestra PP11 para la protecci n de sobrecalentamiento del agua Protecci n contra sobrecalentamiento de agua EE04 Protecci n de sobreenfriamiento de agua PP11 Por ejemplo como...

Page 218: ...ma 3 Fallo del controlador 1 Ajuste el modo para un buen funcionamiento 2 Reemplace el controlador LED de fallo y luego chequee el estado despu s de haber cambiado el modo de funcionamiento verifique...

Page 219: ...215 9 1 Diagrama de despiece Modelo 71676 9 Diagrama de despiece y mantenimiento...

Page 220: ...6 V lvula de 4 v as 17 132000015 Aspa del ventilador 50 150000110 Tap n de drenaje 18 1330900251 Panel frontal 51 117110012 Sonda T de entrada de agua sensor T1 TH6 19 108010014 Rejilla ventilador 52...

Page 221: ...217 9 3 Modelo 71677 71678 71679 9 Diagrama de despiece y mantenimiento...

Page 222: ...erdo 50 113070044 Intercambiador a EEV 17 108010024 Tapa del eje del ventilador 51 113900082 Conjuntos de conexi n de agua 18 132000015 Aspa del ventilador 52 112100021 1 Interruptor de flujo de agua...

Page 223: ...erdo 50 113070044 Intercambiador a EEV 17 108010024 Tapa del eje del ventilador 51 113900082 Conjuntos de conexi n de agua 18 132000015 Aspa del ventilador 52 112100021 1 Interruptor de flujo de agua...

Page 224: ...rdo 50 113070041 Intercambiador a EEV 17 108010024 Tapa del eje del ventilador 51 113900082 Conjuntos de conexi n de agua 18 132000015 Aspa del ventilador 52 112100021 1 Interruptor de flujo de agua 1...

Page 225: ...221 9 7 Modelo 71680 71681 9 Diagrama de despiece y mantenimiento...

Page 226: ...lateral izquierdo 53 119000021 EEV 18 1332600031 Panel frontal 54 113080056 EEV a la tuber a de distribuci n 19 108170017 Rejilla ventilador 55 150000110 Tap n de drenaje 20 108560036 Bandeja de base...

Page 227: ...lateral izquierdo 53 119000021 EEV 18 1332600031 Panel frontal 54 113080056 EEV a la tuber a de distribuci n 19 108170017 Rejilla ventilador 55 150000110 Tap n de drenaje 20 108560036 Bandeja de base...

Page 228: ...224 9 10 Modelo 71682 71683 9 Diagrama de despiece y mantenimiento...

Page 229: ...ventilador 59 112100021 1 Interruptor de flujo de agua 20 108010024 Tapa del eje del ventilador 60 117110011 Sonda de T salida agua T2 TH5 21 133250004 Panel lateral izquierdo 61 108010025 Clip del se...

Page 230: ...l ventilador 59 112100021 1 Interruptor de flujo de agua 20 108010024 Tapa del eje del ventilador 60 117110011 Sonda de T salida agua T2 TH5 21 133250004 Panel lateral izquierdo 61 108010025 Clip del...

Page 231: ...227 9 13 Modelo 68821 68822 68823 9 Diagrama de despiece y mantenimiento...

Page 232: ...020011 Anillo de goma roja 20 108010014 Rejilla ventilador 60 133020026 Junta de goma en la conexi n de agua 21 108550009 Pilar 61 112100021 1 Interruptor de flujo de agua 22 108550005 Bandeja de base...

Page 233: ...1 Panel frontal 59 133020011 Anillo de goma roja 20 108010014 Rejilla ventilador 60 133020026 Junta de goma en la conexi n de agua 21 108550009 Pilar 61 112100021 1 Interruptor de flujo de agua 22 108...

Page 234: ...0011 Anillo de goma roja 20 108010014 Rejilla ventilador 60 133020026 Junta de goma en la conexi n de agua 21 108550009 Pilar 61 112100021 1 Interruptor de flujo de agua 22 108550005 Bandeja de base 6...

Page 235: ...g a 4 S lo un t cnico calificado est autorizado a operar la presi n del sistema de refrigeraci n 5 Verifique la conexi n del cable de potencia si la bomba de calor comienza a funcionar de manera anorm...

Page 236: ...232 Schwimmbad W rmepumpe PRO ELYO INVERBOOST NN Benutzer und Wartungshandbuch...

Page 237: ...ung die bei der Herstellung nicht vorgesehen war wird als gef hrlich eingestuft 1 Beschreibung 2 Transportinformationen 3 Spezifikationen 4 Zubeh r und Optionen 5 Standort und Verbindung 6 Elektronisc...

Page 238: ...pe ist enthalten Wasseranschluss 50 mm St ck 2 Benutzer und Service Handbuch Druckminderer 10 m Verl ngerungskabel f r das Display Wasserdichter Kasten Winterabdeckung Schwingungsd mpfer St ck 4 1 2 A...

Page 239: ...235 Modelle 71677 71678 71679 Modelle 71680 71681 1 Beschreibung...

Page 240: ...236 Modelle 71682 71683 68821 68822 68823 1 Beschreibung...

Page 241: ...ollte hell ger umig offen gut bel ftet mit L ftungsanlagen und ohne Feuerquelle ausgestattet sein Die W rmepumpe muss gelagert und in der Originalverpackung vertikal transportiert werden Wenn dies nic...

Page 242: ...eizleistung Kw 2 41 1 5 3 13 2 0 3 87 2 7 5 1 3 15 Energieverbrauch Kw 1 21 0 35 1 42 0 53 1 76 0 69 2 32 0 81 C O P 4 3 2 3 8 2 2 3 9 2 2 3 9 2 2 Allgemeine Daten Kompressortyp MITSUBISHI INVERTER KO...

Page 243: ...58 4 3 10 4 5 9 12 74 7 4 Energieverbrauch Kw 2 64 0 92 3 45 1 1 4 73 1 51 5 79 1 95 C O P 3 9 2 2 3 9 2 2 3 9 2 2 3 8 2 2 Allgemeine Daten Kompressortyp GMCC TOSHIBA MITSUBISHI Netzspannung V 220 24...

Page 244: ...ng Kw 10 4 5 9 11 6 3 1 11 6 3 1 Energieverbrauch Kw 4 73 1 51 4 77 0 6 4 77 0 6 C O P 3 9 2 2 5 2 2 45 5 2 2 45 Allgemeine Daten Kompressortyp MITSUBISHI INVERTOR COMPRESSOR Netzspannung V 380V 50Hz...

Page 245: ...und Auslass von Wasser Anzahl 2 Winter Abdeckung 1 stk 4 2 Das Bypass Kit Das Kit By Pass ist das unentbehrliche Zubeh r f r die Installation Ihrer W rmepumpe es ist auch ein Instrument f r die Optim...

Page 246: ...pe umkippen sie k nnte den Kompressor besch digen Wasserzulauf R cklauf 1 Montieren Sie die die Verscgraubung wie im Bild gezeigt 2 Schrauben Sie sie auf den Wasserzulauf und R cklauf Netzanschluss 1...

Page 247: ...ckieren k nnten Solche Stellen beeintr chtigen die kontinuierliche Frischluftzufuhr was zu einem verminderten Wirkungsgrad f hrt und m glicherweise eine ausreichende W rmeleistung verhindert 5 1 Posit...

Page 248: ...her korrodieren k nnten zu sch tzen Aus diesem Grund m ssen Impfventile einer MSR Anlage stets in der D senleitung nach der W rmepumpe montiert werden Ferner wird empfohlen ein R ckschlagventil zu ins...

Page 249: ...epumpe l uft nicht an wenn das Wasser nicht zirkuliert 5 3 Typische Anordnung Diese Anordnung ist nur ein veranschaulichendes Beispiel HINWEIS Die Fabrik liefert nur die W rmepumpe Alle anderen Kompon...

Page 250: ...tellen stoppt die W rmepumpe bei einer Temperatur von 29 C Sie l uft wieder an wenn die Wassertemperatur auf 27 C sinkt Je nach Ausgangstemperatur des Wassers im Schwimmbad und der Lufttemperatur kann...

Page 251: ...lgende Tabelle zeigt den Normalwert des Gasdrucks R32 wenn das Ger t im ausgeschalteten oder Laufbedingungen ist Ger tezustand Ausgeschaltet Umgebung 5 5 5 15 15 25 25 35 Wasser Manometer Mpa 0 59 0 8...

Page 252: ...248 6 1 Inverter Schwimmbad W rmepumpe Schaltplan Ref 71676 71677 71678 71679 71680 6 Elektronische Anschl sse...

Page 253: ...249 6 2 Inverter Schwimmbad W rmepumpe Schaltplan Ref 71681 6 Elektronische Anschl sse...

Page 254: ...250 6 3 Inverter Schwimmbad W rmepumpe Schaltplan Ref 71682 71683 6 Elektronische Anschl sse...

Page 255: ...251 6 4 Inverter Schwimmbad W rmepumpe Schaltplan Ref 68822 R410A 6 Elektronische Anschl sse...

Page 256: ...erter Schwimmbad W rmepumpe Schaltplan Ref 68821 68823 R410A Der obige Schaltplan dient lediglich zur Information bitte beachten Sie den jeweiligen Schaltplan f r die einzelne Maschine 6 Elektronische...

Page 257: ...werden Die Toleranz der zul ssigen Spannungsschwankung betr gt w hrend des Betriebs 10 Die Anschl sse sind entsprechend der Leistung des Ger tes und des Installationszustandes zu dimensionieren Modell...

Page 258: ...eld Foto3 4 Stecken Sie die Verdrahtung in die daf r vorgesehene Position auf dem Modbus oder die Platine ohne Modbus Foto 5 6 8 Installation des Modbus Fluidra Connect Signalkabels 6 7 8 9 ffnen Sie...

Page 259: ...255 6 Elektronische Anschl sse Trockenkontakt Timeranschluss Timer Anschluss des Pumpentrockenkontakts...

Page 260: ...emperatur und den Betriebsmodus an Dr cken Sie um die W rmepumpe zu stoppen und OFF Achtung Dr cken Sie w hrend der berpr fung und Einstellung des Parameters die Taste um die aktuelle Einstellung zu b...

Page 261: ...EEV 0 99 N 5 d8 Betriebsfrequenz des Verdichters 0 99Hz Realer Pr fwert d9 Verdichterstrom 0 30A Realer Pr fwert d10 Aktuelle L fterdrehzahl 0 1200 rpm Realer Pr fwert d11 Fehlercode f r das letzte M...

Page 262: ...1 Timer ein aus ist unter Funktion 0 Timer ein aus ist au er Funktion Die Einstellung von P5 und P6 funktioniert nicht P3 Wasserpumpe 0 1 0 1 Immer laufend 0 Abh ngig vom Betrieb des Kompressors P4 Ak...

Page 263: ...as Licht leuchtet wenn es in Betrieb ist 7 2 9 Bet tigen Sie diesen Knopf die Lampe blinkt die W rmepumpe arbeitet nur im vollen Ausgang 7 2 10 W hrend Sie den Smart ausw hlen wird die W rmepumpe nur...

Page 264: ...odus Heiz und K hlschalter Nur K hlen Sie k nnen den Heizmodus und den Automatikmodus durch Dr cken von f r 5 Sekunden umschalten unabh ngig davon ob das Ger t ein oder ausgeschaltet ist Betriebslogik...

Page 265: ...starten Die W rmepumpe startet 3 Minuten nach dem Verlassen der Wasserpumpe aus dem Standby Modus um die Wassertemperatur T1 erneut zu ermitteln K hlmodus T1 Tset 1 30 Minuten dauern T1 29 30 Minuten...

Page 266: ...ode Frequenz F2 F1 7 T1 Tset 1 T1 29 HP wird Standby sein aufh ren zu arbeiten bis die Wassertemperatur auf weniger als 28 C f llt 8 Wenn Sie den Leistungsf higen Arbeitsmodus ausw hlen T1 Tset 1 T1 2...

Page 267: ...1 27 Standby 6 Tset 1 T1 Tset 27 T1 28 Silent mode frequenz F2 F1 7 T1 Tset T1 28 Smart mode frequenz F5 8 Wenn Sie den Leistungsf higen Arbeitsmodus ausw hlen T1 Tset 1 T1 27 Powerful mode frequenz...

Page 268: ...TH1 PP 05 1 Sensorfehler oder Kurzschluss 2 Die Verdrahtung des Sensors ist lose 1 Die Verdrahtung der Sensoren reparieren 2 Schalten Sie den Sensor Ausfall des AuspuffrohrsensorsT6 TH3 PP 06 1 Sensor...

Page 269: ...r fung des DrucKwertes Kein Wasserfluss oder Wasserflussschalterau sfall TS1 EE 03 1 Wasser Flow Schalter hat keinen Kontak 2 Wasserstromschalter ist besch digt 3 Kein bzw Unzureichender 1 Die Verdrah...

Page 270: ...en der Steuerung und der Hauptplatine EE 08 1 Poor Signalleitung oder besch digte Signalleitung 2 Controller St rung 1 berpr fen und wieder anschlie en der Signalleitung 2 Montieren Sie ein neues Sign...

Page 271: ...r besch digt ist ndern Sie einen anderen 3 Montieren Sie ein neues L fterrad Die Temperatur des IPM Moduls ist zu hoch EE 15 1 Ausfahrt Ausnahme des IPM Modul Thermo Schaltkreises 2 Motor ist abnormal...

Page 272: ...ist Der Eingangsstromausfall EE 20 Die Versorgungsspannung schwankt zu stark berpr fen Sie ob die Spannung stabil ist Software Steuerausnahme EE 21 1 Kompressor l uft aus dem Schritt 2 Wrong Programm...

Page 273: ...ne Erkennung wenn T3 TH2 oder T5 TH1 St rung 1 Schalten Sie den K hlmodus um das 4 Wege Ventil zu berpr fen wenn es richtig umgekehrt wurde 2 Montieren Sie ein neues 4 Wege Ventil 3 F llen Sie das Sys...

Page 274: ...atur niedriger als die eingestellte Temperatur ber 7 C ist zeigt der LED Controller PP11 f r den Wasser berk hlungsschutz an EE04 Wasser berhitzungsschutz PP11 Wasser berk hlung Schutz Zum Beispiel wi...

Page 275: ...ekt 1 Stellen Sie den Modus richtig ein 2 Ersetzen Sie die defekte LED Kabelsteuerung und berpr fen Sie den Status nachdem Sie in den Betriebsmodus bergegangen sind schlie lich berpr fen Sie die Wasse...

Page 276: ...272 9 1 Explosionszeichnung Modell 71676 9 Explosionszeichnung und Wartung...

Page 277: ...0123 Rohr 16 1330900261 Linke Seitenverkleidung 49 121000006 4 Wege Ventil 17 132000015 Ventilatorfl gel 50 150000110 Abflussstopfen 18 1330900251 Frontblende 51 117110012 Wasser in Temp Sensor T1 TH6...

Page 278: ...274 9 3 Modell 71677 71678 71679 9 Explosionszeichnung und Wartung...

Page 279: ...16 1330900261 Linke Seitenwand 50 113070044 Austauscher zu EEV 17 108010024 DC Motorrohrabdeckung 51 113900082 Wasseranschluss Sets 18 132000015 Ventilatorfl gel 52 112100021 1 Wasserstromschalter 19...

Page 280: ...en 16 1330900261 Linke Seitenverkleidung 50 113070044 Austauscher zu EEV 17 108010024 DC Motorrohrabdeckung 51 113900082 Wasseranschluss Sets 18 132000015 L fterklinge 52 112100021 1 Wasserflussschalt...

Page 281: ...ungsrohrleitungen 16 1330900261 Linke Seitenverkleidung 50 113070041 Austauscher zu EEV 17 108010024 DC Motorabdeckung 51 113900082 Wasseranschluss Sets 18 132000015 L fterklinge 52 112100021 1 Wasser...

Page 282: ...278 9 7 Model 71680 71681 9 Explosionszeichnung und Wartung...

Page 283: ...zum Austauscher 17 1332600051 Linke Seitenwand 53 119000021 EEV 18 1332600031 Frontblende 54 113080056 EEV zu Verteilerleitungen 19 108170017 K hlergrill 55 150000110 Ablassschraube 20 108560036 Boden...

Page 284: ...zum Austauscher 17 1332600051 Linke Seitenwand 53 119000021 EEV 18 1332600031 Frontblende 54 113080056 EEV zu Verteilerleitungen 19 108170017 K hlergrill 55 150000110 Ablassschraube 20 108560036 Boden...

Page 285: ...281 9 10 Modell 71682 71683 9 Explosionszeichnung und Wartung...

Page 286: ...lter 19 132000015 Ventilatorfl gel 59 112100021 1 Wasserstromschalter 20 108010024 DC Motorrohrabdeckung 60 117110011 Wasser aus Temp Sensor T2 TH5 21 133250004 Linke Seitenwand 61 108010025 Temperatu...

Page 287: ...lter 19 132000015 Ventilatorfl gel 59 112100021 1 Wasserstromschalter 20 108010024 DC Motorrohrabdeckung 60 117110011 Wasser aus Temp Sensor T2 TH5 21 133250004 Linke Seitenwand 61 108010025 Temperatu...

Page 288: ...284 9 13 Modell 68821 68822 68823 9 Explosionszeichnung und Wartung...

Page 289: ...enwand 58 113900082 Wasseranschluss Sets 19 133250001 Frontblende 59 133020011 Roter Gummiring 20 108010014 K hlergrill 60 133020026 Gummiring am Wasseranschluss 21 108550009 S ule 61 112100021 1 Wass...

Page 290: ...Wasseranschluss Sets 19 133250001 Frontblende 59 133020011 Roter Gummiring 20 108010014 K hlergrill 60 133020026 Gummiring am Wasseranschluss 21 108550009 S ule 61 112100021 1 Wasserstromschalter 22 1...

Page 291: ...Sets 19 133250001 Frontblende 59 133020011 Roter Gummiring 20 108010014 K hlergrill 60 133020026 Gummiring am Wasseranschluss 21 108550009 S ule 61 112100021 1 Wasserstromschalter 22 108550005 Bodenw...

Page 292: ...asserpumpe auslassen wenn die HP Einheit f r l ngere Zeit unbenutzt bleiben soll besonders im Winter 4 Ansonsten sollten Sie berpr fen ob die Einheit mit Wasser gef llt ist bevor Sie diese einschalten...

Page 293: ...289 POMPA DI CALORE PER PISCINE PRO ELYO INVERBOOST NN Manuale di Installazione e Uso...

Page 294: ...e causa di incendio Non operare saldature sui tubi se vi ancora del gas refrigerante all interno dell apparecchiatura Si prega di non effettuare una ricarica di gas in luoghi angusti Svuotare sempre l...

Page 295: ...ollegamento acqua da 50 mm 2 pezzi Manuale d uso e manutenzione Collegamento condensati Cavo di segnale da 10 metri Scatola impermeabile Copertura invernale Base anti vibrazione 4 pezzi 1 2 Dimensioni...

Page 296: ...292 Modelli 71677 71678 71679 Modelli 71680 71681 1 1 1 Descrizione Descrizione Descrizione...

Page 297: ...293 Modelli 71682 71683 68821 68822 68823 1 1 1 Descrizione Descrizione Descrizione...

Page 298: ...onsigli per lo stoccaggio Il magazzino deve essere luminoso spazioso aperto ben ventilato provvisto di impianto di ventilazione e privo di fonti di combustibile Le pompe di calore devono essere immaga...

Page 299: ...pacit di riscaldamento Kw 2 41 1 5 3 13 2 0 3 87 2 7 5 1 3 15 Consumo energetico Kw 1 21 0 35 1 42 0 53 1 76 0 69 2 32 0 81 C O P 4 3 2 3 8 2 2 3 9 2 2 3 9 2 2 Dati generali Tipo di compressore MITSUB...

Page 300: ...scaldamento Kw 5 8 3 6 7 58 4 3 10 4 5 9 12 74 7 4 Consumo energetico Kw 2 64 0 92 3 45 1 1 4 73 1 51 5 79 1 95 C O P 3 9 2 2 3 9 2 2 3 9 2 2 3 8 2 2 Dati generali Tipo di compressore MITSUBISHI INVER...

Page 301: ...formance con Aria a 10 Acqua a 26 Umidit al 78 Capacit di Kw 10 4 5 9 11 6 3 1 11 6 3 1 Consumo energetico Kw 4 73 1 51 4 77 0 6 4 77 0 6 C O P 3 9 2 2 5 2 2 45 5 2 2 45 Dati generali Tipo di compress...

Page 302: ...invernale 1 pezzo 4 2 Il Kit By Pass Il Kit By Pass Kit l accessorio indispensabile per l installazione della vostra pompa di calore nonch uno strumento che consente di ottimizzare il riscaldamento d...

Page 303: ...trata e uscita dell acqua 1 Installare i due giunti come mostrato nell immagine 2 Avvitarli sulle prese dell acqua giunti di entrata e uscita Cablaggio 1 Aprite il coperchio della morsettiera contrass...

Page 304: ...uenti tre fattori 1 Aria pulita 2 Energia elettrica 3 Filtri per piscina l unit pu essere installata in qualsiasi luogo all esterno purch si mantengano le distanze minime stabilite rispetto ad altri o...

Page 305: ...di calore non si avvier se l acqua non sta circolando 5 3 Disposizione tipica Questa disposizione solo un esempio a titolo indicativo NOTA La fabbrica fornisce solo la pompa di calore Tutti gli altri...

Page 306: ...a per esempio se fissate la temperatura a 28 C la pompa di calore si arrester quando la temperatura sar a 29 C Mentre si riavvier quando la temperatura dell acqua scender a 27 C A seconda della temper...

Page 307: ...a pressione del gas refrigerante presente nell unit la tabell a sottostante mostra il normale valore di pressione del gas R32 ad apparecchiatura spenta e ad apparecchiatura in funzionamento Condizione...

Page 308: ...304 6 1 Schema elettrico di una pompa di calore inverter Rif 71676 71677 71678 71679 71680 6 6 6 Cablaggio Cablaggio Cablaggio elettrico elettrico elettrico...

Page 309: ...305 6 2 Schema elettrico di una pompa di calore inverter Rif 71681 6 6 6 Cablaggio Cablaggio Cablaggio elettrico elettrico elettrico...

Page 310: ...306 6 3 Schema elettrico di una pompa di calore inverter Rif 71682 71683 6 6 6 Cablaggio Cablaggio Cablaggio elettrico elettrico elettrico...

Page 311: ...307 6 4 Schema elettrico di una pompa di calore inverter Rif 68822 R410A 6 6 6 Cablaggio Cablaggio Cablaggio elettrico elettrico elettrico...

Page 312: ...re inverter Rif 68821 68823 R410A Lo schema elettrico di cui sopra solo vuol essere un semplice riferimento Consultare sempre lo schema di cablaggio riportato sull apparecchiatura 6 6 6 Cablaggio Cabl...

Page 313: ...ze e le condizioni di uso La tolleranza di un accettabile variazione di voltaggio di 10 in corso di funzionamento I collegamenti devono essere dimensionati a seconda della potenza del dispositivo e de...

Page 314: ...6 Prendere il cavo di segnale Modbus Fluidra Connect degli accessori foto7 e inserire il terminale arrotondato del cavo di segnale nel cavo di segnale Modulo Modbus Fluidra Connect foto 8 Terminali tr...

Page 315: ...311 Timer di collegamento con contatto privo di tensione Timer Collegamento della pompa con contatto privo di tensione 6 6 6 Cablaggi Cablaggi Cablaggi elettrici elettrici elettrici...

Page 316: ...OFF Avvertenza Nel corso della verifica e dell impostazione dei parametri premere il tasto per uscire rapidamente e salvare le impostazioni correnti Premere nuovamente il tasto per accendere spegnere...

Page 317: ...tazione della frequenza 0 Nessun limite di frequenza 1 Limite di temperatura del tubo della bobina 2 Limite di frequenza di surriscaldamento o sovra raffreddamento 4 Corrente limite di frequenza dell...

Page 318: ...cos anche per il terzo e il quarto numero Infine premere per salvare le impostazioni e uscire o si uscir automaticamente dopo 15 secondi Dopo aver effettuato l impostazione il parametro P del codice p...

Page 319: ...Medium output e Small output Quando in modalit Small output la spia Silent lampeggia Quando in modalit Medium output la spia Silent accesa mentre la spia Smart lampeggia 7 2 12 Modalit automatica L u...

Page 320: ...pa di calore si riavvier 3 minuti dopo che la pompa di filtrazione uscita dalla modalit stand by per rilevare nuovamente la temperatura dell acqua T1 Modalit raffredda mento T1 Tset 1 durata di 30 min...

Page 321: ...rimarr in modalit Standby e non funzioner fino a quando l acqua non scende sotto i 28 C 8 Quando si seleziona la modalit di funzionamento Powerful T1 Tset 1 T1 29 C Modalit Powerful frequenza F10 F9 9...

Page 322: ...7 C T1 28 C Modalit Silent frequenza F2 F1 7 T1 Tset T1 28 C Modalit Smart frequenza F5 8 Quando si seleziona la modalit di funzionamento Powerful T1 Tset 1 T1 27 C Modalit Powerful frequenza F10 F9 9...

Page 323: ...o 2 Il cablaggio della sonda allentato 1 Verificare o sostituire la sonda 2 Riparare il cablaggio delle sonde Protezione antigelo in inverno PP07 La temperatura ambiente o dell acqua in entrata troppo...

Page 324: ...e troppo alta T6 TH3 EE05 1 Mancanza di gas 2 Portata dell acqua ridotta 3 Il sistema di tubazioni bloccato 4 Guasto della sonda T6 TH3 1 Controllare il manometro di alta pressione se ha un livello in...

Page 325: ...l alimentazione e riavviare dopo 3 minuti 2 Sostituire il controller 3 Verificare la connessione di sequenza del compressore Protezione di bassa tensione di VDC EE12 1 La tensione della tensione madre...

Page 326: ...ggiato 2 Il controller danneggiato 3 La pala della ventola bloccata 1 Individuare il motore DC e sostituirlo 2 Sostituire il controller 3 Individuare l ostacolo ed eliminarlo Anomalia nel funzionament...

Page 327: ...temperatura ambiente nella scheda elettronica EE24 Errore del dispositivo di temperatura ambiente Sostituire la scheda del controller o la scheda principale Errore nella fase del compressore EE25 Conn...

Page 328: ...PP11 per protezione da sovraraffreddamento dell acqua EE04 Protezione da surriscaldamento dell acqua in uscita PP11 Protezione da sovra raffreddamento dell acqua in uscita Per un esempio si veda a se...

Page 329: ...ler 1 Regolare la modalit per un adeguato funzionamento 2 sostituire il controller LED difettoso e verificare lo stato dopo aver cambiato modalit di funzionamento controllando la temperatura dell acqu...

Page 330: ...326 9 1 Esploso e manutenzione Modello 71676 9 9 9 Esploso Esploso Esploso e e e manutenzione manutenzione manutenzione...

Page 331: ...e 50 150000110 Tappo di drenaggio 18 1330900251 Pannello frontale 51 117110012 Sonda temperatura acqua entrata T1 TH6 19 108010014 Griglia ventilatore 52 108010025 Clip sonda di temperatura dello scam...

Page 332: ...328 9 3 Modello 71677 71678 71679 9 9 9 Esploso Esploso Esploso e e e manutenzione manutenzione manutenzione...

Page 333: ...erchio asse ventilatore 51 113900082 Set di collegamento dell acqua 18 132000015 Pala del ventilatore 52 112100021 1 Flussostato dell acqua 19 1330900251 Pannello frontale 53 133020012 Guarnizione in...

Page 334: ...108010024 Coperchio asse ventilatore 50 113070044 Scambiatore per EEV 18 132000015 Pala del ventilatore 51 113900082 Set di collegamento dell acqua 19 133090025 Pannello frontale 52 112100021 1 Flusso...

Page 335: ...Coperchio asse ventilatore 51 113900082 Set di collegamento dell acqua 18 132000015 Pala del ventilatore 52 112100021 1 Flussostato dell acqua 19 1330900251 Pannello frontale 53 133020012 Guarnizione...

Page 336: ...332 9 7 Modello 71680 71681 9 9 9 Esploso Esploso Esploso e e e manutenzione manutenzione manutenzione...

Page 337: ...frontale 54 113080056 EEV per tubi di distribuzione 19 108170017 Griglia ventilatore 55 150000110 Tappo di drenaggio 20 108560036 Vaschetta base 56 108010025 Clip sonda di temperatura dello scambiato...

Page 338: ...1 Pannello frontale 54 113080056 EEV per tubi di distribuzione 19 108170017 Griglia ventilatore 55 150000110 Tappo di drenaggio 20 108560036 Vaschetta base 56 108010025 Clip sonda temperatura scambiat...

Page 339: ...335 9 10 Modello 71682 71683 9 9 9 Esploso Esploso Esploso e e e manutenzione manutenzione manutenzione...

Page 340: ...108010024 Coperchio asse ventilatore 60 117110011 Sonda temperatura acqua in uscita T2 TH5 21 133250004 Pannello laterale sinistro 61 108010025 Clip sonda di temperatura dello scambiatore 22 133250001...

Page 341: ...108010024 Coperchio asse ventilatore 60 117110011 Sonda temperatura acqua in uscita T2 TH5 21 133250004 Pannello laterale sinistro 61 108010025 Clip sonda di temperatura dello scambiatore 22 133250001...

Page 342: ...338 9 13 Modello 68821 68822 68823 9 9 9 Esploso Esploso Esploso e e e manutenzione manutenzione manutenzione...

Page 343: ...108010014 Griglia ventilatore 60 133020026 Guarnizione di gomma su collegamento per l acqua 21 108550009 Colonna 61 112100021 1 Flussostato dell acqua 22 108550005 Vaschetta base 62 116000001 2 Guarni...

Page 344: ...108010014 Griglia ventilatore 60 133020026 Guarnizione di gomma su collegamento per l acqua 21 108550009 Colonna 61 112100021 1 Flussostato dell acqua 22 108550005 Vaschetta base 62 116000001 2 Guarn...

Page 345: ...ventilatore 60 133020026 Guarnizione di gomma su collegamento per l acqua 21 108550009 Colonna 61 112100021 1 Flussostato dell acqua 22 108550005 Vaschetta base 62 116000001 2 Guarnizione di tenuta f...

Page 346: ...bio dicalore senza problemi e un buon risparmio energetico 4 Solo un tecnico qualificato autorizzato a intervenire sulla pressione delsistema direfrigerazione 5 Verificare la connessione del cavo di p...

Page 347: ...343 BOMBA DE CALOR DE PISCINA PRO ELYO INVERBOOST NN Manual do utilizador e servi o...

Page 348: ...ocados pela presen a de humidade IND IND IND CE CE CE Not cia importante Por favor mantenha sempre a bomba de calor num local com ventila o e longe de qualquer objecto que possa provocar inc ndio N o...

Page 349: ...njunto de conex o de gua 50 mm unid 2 Manual do utilizador e servi o Conex o condensados Cabo de sinal com 10 metros Caixa imperme vel Capa de inverno Base anti vibra o pe as 4 1 2 Dimens o Modelos 71...

Page 350: ...346 Modelos 71677 71678 71679 Modelos 71677 71678 71679 Models 71680 71681 1 1 1 Dimens Dimens Dimens o o o...

Page 351: ...347 Modelos 71682 71683 68821 68822 68823 1 1 1 Dimens Dimens Dimens o o o...

Page 352: ...az m deve ser iluminado espa oso aberto bem ventilado com equipamento de ventila o e sem fonte de inc ndio A bomba de calor deve ser armazenada e movimentada na posi o vertical dentro da sua embalagem...

Page 353: ...3 13 2 0 3 87 2 7 5 1 3 15 Pot ncia consumida Kw 1 21 0 35 1 42 0 53 1 76 0 69 2 32 0 81 COP 4 3 2 3 8 2 2 3 9 2 2 3 9 2 2 Dados gerais Tipo de compressor MITSUBISHI INVERTER COMPRESSOR Voltagem V 220...

Page 354: ...5 9 12 74 7 4 Pot ncia consumida Kw 2 64 0 92 3 45 1 1 4 73 1 51 5 79 1 95 COP 3 9 2 2 3 9 2 2 3 9 2 2 3 8 2 2 Dados gerais Tipo de compressor MITSUBISHI INVERTER COMPRESSOR Voltagem V 220V 240V 50Hz...

Page 355: ...1 11 6 3 1 Pot ncia consumida Kw 4 73 1 51 4 77 0 6 4 77 0 6 COP 3 9 2 2 5 2 2 45 5 2 2 45 Dados gerais Tipo de compressor MITSUBISHI INVERTOR COMPRESSOR Voltagem V 380V 50Hz or 60Hz 3PH 220 240V 50Hz...

Page 356: ...Capa de inverno 1 pc 4 2 O Kit By Pass O kit By Pass o acess rio essencial para a instala o da sua bomba de calor tamb m uma ferramenta para a optimiza o do aquecimento da gua A regula o das v lvulas...

Page 357: ...rada de gua e jun o de sa da 1 Use a fita de tubo para conectar a jun o de entrada e sa da de gua na bomba de calor 2 Instale as duas juntas como mostra a imagem 3 Aparafus los na entrada de gua e jun...

Page 358: ...ntrada de ar Tais locais prejudicam o fornecimento cont nuo de ar fresco resultando em efici ncia reduzida e possivelmente impedindo a produ o de calor suficiente 5 1 Localiza o da bomba de calor A un...

Page 359: ...a es qu micas excessivamente elevadas que possam corroer o permutador de calor Por este motivo equipamentos deste tipo devem sempre ser instalados na tubula o no lado a jusante da bomba de calor e rec...

Page 360: ...lor A bomba de calor n o iniciar se a gua n o estiver circulando 5 3 Arranjo t pico Este arranjo apenas um exemplo ilustrativo NOTE A f brica fornece apenas a bomba de calor Todos os outros componente...

Page 361: ...ias para aquecer a gua at temperatura desejada Uma boa cobertura de piscina pode reduzir drasticamente o tempo necess rio NOTA Interruptor de fluxo de gua Bomba de calor vem equipada com interruptor d...

Page 362: ...gua 5 6 Visor do man metro R32 Examine o man metro que indica a press o do g s refrigerante da unidade a tabela abaixo mostra o valor normal da press o do g s R32 quando a m quina est desligada ou em...

Page 363: ...359 6 1 Diagrama el ctrico da bomba de calor de piscina Inverter Ref 71676 71677 71678 71679 71680 6 6 6 Cablagem Cablagem Cablagem el el el ctrica ctrica ctrica...

Page 364: ...360 6 2 Diagrama el ctrico da bomba de calor de piscina Inverter Ref 71681 6 6 6 Cablagem Cablagem Cablagem el el el ctrica ctrica ctrica...

Page 365: ...361 6 3 Diagrama el ctrico da bomba de calor de piscina Inverter Ref 71682 71683 6 6 6 Cablagtem Cablagtem Cablagtem el el el ctrica ctrica ctrica...

Page 366: ...362 6 4 Diagrama el ctrico da bomba de calor de piscina Inverter Ref 68822 R410A 6 6 6 Cablagem Cablagem Cablagem el el el ctrica ctrica ctrica...

Page 367: ...or de piscina Inverter Ref 68821 68823 R410A Os diagramas de cablagem el ctrica indicados acima s o apenas a t tulo indicativo Por favor verificar sempre o diagrama que est afixado na m quina 6 6 6 Fi...

Page 368: ...idades e condi es de uso A toler ncia da varia o de tens o aceit vel de 10 durante o funcionamento As conex es devem ser dimensionadas de acordo com a pot ncia do dispositivo e o estado do instala o M...

Page 369: ...posi o designada na placa de circuito impresso M dulo Modbus ou PCB sem Modbus foto5 6 8 Instala o do Modbus Cabo de conex o Fluidra Connect Photo 6 Photo 7 Photo 8 Photo 9 Abra a tampa dos terminais...

Page 370: ...366 Conex o do temporizador de contacto seco Timer Conex o da bomba de contacto seco 6 6 6 Electrical Electrical Electrical Wiring Wiring Wiring...

Page 371: ...ra o Pressione para parar a unidade de bomba de calor e mostrar OFF Aviso Durante a verifica o e configura o de par metros pressione para sair rapidamente e salvar a configura o actual Pressione novam...

Page 372: ...do EEV 0 99 N 5 d8 Frequ ncia de funcionamento do compressor 0 99Hz Valor real do teste d9 Corrente do compressor 0 30A Valor real do teste d10 Velocidade actual do ventilador 0 1200 rpm Valor real d...

Page 373: ...o n mero O mesmo acontece com o terceiro e o quarto n mero Por fim pressione para salvar a configura o e sair ou sair automaticamente ap s 15 segundos C digo Nome Range Padr o Observa o P0 Degelo manu...

Page 374: ...pera o 7 2 8 S mbolo de partida autom tica a luz estar acesa quando estiver em opera o 7 2 9 Pressione o bot o Powerfull a luz ficar a piscar a bomba de calor operar somente em Full output 7 2 10 Se e...

Page 375: ...fecimento e apenas arrefecimento Pode se alternar o modo apenas aquecimento e Auto pressionando por 5 segundos independentemente de a unidade estar ligada ou desligada L gica de opera o do modo Autom...

Page 376: ...s ap s a bomba de gua sair do modo de espera para detectar a temperatura T1 da gua novamente Modo de refrigera o T1 Tset 1 durar 30 minutos T1 29 durar 30 minutos A bomba de gua entrar no modo de espe...

Page 377: ...t F2 F1 7 T1 set 1 T1 9 BC estar em modo standby parada at que a temperatura da gua caia para menos de 28 8 POWERFUL T1 Tset 1 T1 29 Modo Powerful frequ ncia F10 F9 9 T1 Tset 1 T1 29 BC estar em modo...

Page 378: ...equ ncia F2 F1 7 T1 Tset T1 28 C Smart frequ ncia F5 8 POWERFUL T1 Tset 1 T1 27 C Powerful frequ ncia F10 F9 9 T1 Tset 1 T1 27 C Standby 10 Reiniciar para arrefecer desde status standby SMART T1 Tset...

Page 379: ...ou em c circ 2 O cabo do sensor est solto 1 Verifique ou mude o sensor 2 Reajuste a fia o dos sensores Protec o anti congelamento no inverno PP07 Temperatura ambiente ou temperatura de entrada de gua...

Page 380: ...e descarga T6 TH3 muito alta EE05 1 Falta de g s 2 Baixo fluxo de gua 3 Pipingsystem foi bloqueado 4 Falha do sensor de Temp de descarga 1 Verificar o man metro de alta press o Se estiver muito baixo...

Page 381: ...da 1 Erro de programa desligue o fornecimento de electricidade e reinicie ap s 3 minutos 2 Trocar a placa de controlo 3 Verifique a conex o sequ ncia das fases ao compressor Protec o VDC muito baixa E...

Page 382: ...motor DC est danificado 2 A placa principal est danificada 3 As p s do ventilador est o presas 1 Verificar o motor DC substituir se necess rio 2 Trocar placa principal 3 Eliminar o bloqueio das p s F...

Page 383: ...necess rio Erro placa de controlo temperatura ambiente EE24 Falha do dispositivo de temperatura ambiente Trocar placa de controlo ou placa principal Falha de fase do compressor EE25 U V W conectados...

Page 384: ...C o controlador exibir PP11 para protec o contra arrefecimento excessivo da gua EE04 Protec o Contra Sobreaquecimento da gua PP11 Protec o contra arrefecimento excessivo da gua Por exemplo Modo Agua...

Page 385: ...to do controlador 1 Ajustar o modo para o funcionamento correto 2 Substituir o controlador e em seguida verifique o status ap s alterar o modo de opera o verificando a temperatura de entrada e sa da d...

Page 386: ...382 9 1 Diagrama explodido Mod 71676 9 9 9 Diagrama Diagrama Diagrama Explodido Explodido Explodido e e e manuten manuten manuten o o o...

Page 387: ...ado esquerdo 49 121000006 V lvula de 4 vias 17 132000015 L mina da vento nha 50 150000110 Plugue de drenagem 18 1330900251 Painel frontal 51 117110012 gua em temp sensor T1 TH6 19 108010014 Grelha fro...

Page 388: ...384 9 3 Model 71677 71678 71679 9 9 9 Diagrama Diagrama Diagrama Explodido Explodido Explodido e e e manuten manuten manuten o o o...

Page 389: ...istribui o 16 1330900261 Painel do lado esquerdo 50 113070044 Trocador para EEV 17 108010024 Tampa do tubo do motor DC 51 113900082 Conjuntos de conex o de gua 18 132000015 L mina da vento nha 52 1121...

Page 390: ...o 49 113080054 EEV para encanamento de distribui o 17 108010024 Tampa do tubo do motor DC 50 113070044 Trocador para EEV 18 132000015 L mina da vento nha 51 113900082 Conjuntos de conex o de gua 19 13...

Page 391: ...bui o 16 1330900261 Painel do lado esquerdo 50 113070041 Trocador para EEV 17 108010024 Tampa do motor DC 51 113900082 Conjuntos de conex o de gua 18 132000015 L mina da vento nha 52 112100021 1 Inter...

Page 392: ...388 9 7 Modelo 71680 71681 9 9 9 Diagrama Diagrama Diagrama Explodido Explodido Explodido e e e manuten manuten manuten o o o...

Page 393: ...lvula de 4 vias para trocador 17 1332600051 Painel do lado esquerdo 53 119000021 EEV 18 1332600031 Painel frontal 54 113080056 EEV para encanamento de distribui o 19 108170017 Grelha frontal 55 15000...

Page 394: ...V lvula de 4 vias para trocador 17 1332600051 Painel do lado esquerdo 53 119000021 EEV 18 1332600031 Painel frontal 54 113080056 EEV para encanamento de distribui o 19 108170017 Grelha frontal 55 1500...

Page 395: ...391 9 10 Modelo 71682 71683 9 9 9 Diagrama Diagrama Diagrama Explodido Explodido Explodido e e e manuten manuten manuten o o o...

Page 396: ...filtrar 19 132000015 L mina da vento nha 59 112100021 1 Interruptor de fluxo de gua 20 108010024 Tampa do tubo do motor DC 60 117110011 gua fora temp sensor T2 TH5 21 133250004 Painel do lado esquerd...

Page 397: ...filtrar 19 132000015 L mina da vento nha 59 112100021 1 Interruptor de fluxo de gua 20 108010024 Tampa do tubo do motor DC 60 117110011 gua fora temp sensor T2 TH5 21 133250004 Painel do lado esquerd...

Page 398: ...394 9 13 Modelo 68821 68822 68823 9 9 9 Diagrama Diagrama Diagrama Explodido Explodido Explodido e e e manuten manuten manuten o o o...

Page 399: ...001 Painel frontal 59 133020011 Anel de borracha vermelha 20 108010014 Grelha frontal 60 133020026 Anel de borracha na conex o de gua 21 108550009 Pilar 61 112100021 Interruptor de fluxo de gua 22 108...

Page 400: ...untos de conex o de gua 19 133250001 Painel frontal 59 133020011 Anel de borracha vermelha 20 108010014 Grelha frontal 60 133020026 Anel de borracha na conex o de gua 21 108550009 Pilar 61 112100021 1...

Page 401: ...1 Painel frontal 59 133020011 Anel de borracha vermelha 20 108010014 Grelha frontal 60 133020026 Anel de borracha na conex o de gua 21 108550009 Pilar 61 112100021 1 Interruptor de fluxo de gua 22 108...

Page 402: ...nar durante um longo per odo de tempo especialmente durante a poca de Inverno 4 Verificar se a unidade est cheia de gua antes de come ar a funcionar novamente 5 Depois de acondicionar a unidade para a...

Page 403: ...ional regulations 2 INDIVIDUAL TERMS 2 1 This guarantee covers the products referred to in this manual 2 2 This Guarantee Certificate will only be applicable in European Union countries 2 3 For this g...

Page 404: ...de car cter imperativo 2CONDICIONES PARTICULARES 2 1 La presente garant a cubre los productos a que hace referencia este manual 2 2 El presente Certificado de Garant a ser de aplicaci n nicamente en l...

Page 405: ...cat de Garantie ne limite pas ni pr juge les droits correspondant aux consommateurs en vertu des normes nationales de nature imp rative 2CONDITIONS PARTICULI RES 2 1 La pr sente garantie couvre les pr...

Page 406: ...irksam werden zu lassen muss der K ufer das Kaufdatum und das Lieferdatum des Produktes belegen 1 7 Nach Ablauf von sechs Monaten ab Lieferung des Produktes an den K ufer muss im Falle eines Mangels d...

Page 407: ...ranno un prolungamento della scadenza della garanzia del Prodotto originale quantunque disporranno di una loro propria garanzia 1 6 Affinch la presente possa essere valida l acquirente dovr attestare...

Page 408: ...dit onmogelijk of buitensporig zou zijn 1 4 Indien het Produkt niet gerepareerd of vervangen kan worden dan kan de koper na verhouding prijsreduktie aanvragen of indien het defekt belangrijk genoeg is...

Page 409: ...a ao comprador 1 3 Se durante o per odo de garantia o comprador notificar ao vendedor alguma falta de conformidade do Produto o vendedor dever reparar ou substituir o Produto por sua conta no lugar on...

Page 410: ...tment when these products become waste 1 2 It is also intended to improve the environmental practices of all agents involved in electrical and electronic goods including manufacturers distributors use...

Page 411: ...hets et de d terminer une gestion appropri e de ceux ci en essayant d am liorer l efficacit de la protection environnementale ont t tablies de nombreuses normes applicables la fabrication du produit e...

Page 412: ...oder recycelt werden k nnen Dennoch sind die verschiedenen Teile aus denen dieses Produkt besteht nicht biologisch abbaubar deshalb k nnen sie nicht einfach weggeworfen werden Um dieser Produkt korre...

Page 413: ...naar de afvalverwerking brengen volgens de voorschriften van de lokale overheid 1 6 Wij zullen de kosten van deze handelingen op ons nemen 1 7 De apparaten zijn voorzien van een etiket met het symboo...

Page 414: ...articles or contents of this document without prior notice Nos reservamos el derecho de cambiar total o parcialmente las caracter sticas de nuestros art culos oel contenido de este documento sin previ...

Page 415: ...che Vertr glichkeit EMC Richtlinie 2014 35 EU ber die Sicherheit von elektrischen Betriebsmitteln Niederspannungsrichtlinie LVD Europ ischen Richtlinie 2011 65 EU RoHS REACH Verordnung 1907 2006 2012...

Page 416: ......

Page 417: ......

Page 418: ...Fluidra Global Distribution Ametllers n 6 Polinya Barcelona Spain www astralpool com A0142PIP09...

Reviews: