Code 0000138008
rev. 1.0
7
Alarm
Display
Relay
Actions to do
Level
Level____7,2_ph
Alarm Relay
Close
- Push Enter Key to open
Alarm Relay
- Restore Product tank
OFA First Alarm (time >70%)
OFA_Alarm__7,2_ph
Alarm Relay
open
- Push Enter Key to reset
OFA Second Alarm (time =100%)
OFA_STOP___7,2_ph
Alarm Relay
Close
- Push Enter Key to reset
Flow Rate
Flow_______7,2_ph
Alarm Relay
open
- Restore Flow Rate
System Error
Parameter_Error
Alarm Relay
Open
- Press Enter Key to replace
Default parameter
Communication Watchdog alarm
Wdg_Alarm
Alarm Relay
Close
- Check the communication
network
Calibration Function
Error_7_ph
Error_4_ph
Error_465_mV
Alarm Relay
open
- Restore Probe or Buffer
solution and repeat calibration
function
To restore Default parameters run Following steps:
•
Power off Pool Basic unit
•
Keeping Press UP and DOWN Key switch on the
Power.
•
The unit will flash
Init.default__no
•
Press up
Init.default__Yes
•
Enter Key to restore Default parameters.
Default parameters:
•
Language =
UK
•
Set Point value=
7,4 pH; 750mV (Rx)
•
Dosing Method =
Acid; Low (Rx)
•
Time OFA =
OFF
•
Calibration =
7/4 (2 point); 465mV (Rx)
•
Flow Input =
OFF