ALASKA / SIBERIA / BERING SERIES · Cooler EF
AIR/WATER
–
WATER/WATER
© FLUIDRA 2019 ALL RIGHTS RESERVED. PROPRIETARY DOCUMENT.
Pag: 30
ENGLISH
6.6
TROUBLESHOOTING GUIDE SYSTEM FAULTS AND LIST OF ERROR
CODES
ERROR
LCD
CODE
REASON
SOLUTION
Low pressure Malfunction of
system 1
A11
Gas change too low. Possible system
blockage
Check pressure switch and gas circuit;
thermostatic valve closed, evaporator
clogged, fan stopped.
High pressure Malfunction of
system 1
A12
Gas change too high. Possible system
blockage
Check pressure switch and gas circuit,
refrigerant circuit. Insufficient water flow,
stop pump
Low pressure Malfunction of
system 2
A13
Gas change too low. Possible system
blockage
Check pressure switch and gas circuit;
thermostatic valve closed, evaporator
clogged, fan stopped.
High pressure Malfunction of
system 2
A14
Gas change too high. Possible system
blockage
Check pressure switch and gas circuit,
refrigerant circuit. Insufficient water flow
Flow switch failure
A15
No water/litter water in water system.
Check the water flow volume. Check water
pump
Water inlet temp. sensor
failure
A21
The sensor is open or short circuit
Check or change the sensor
Cool1 sensor 1 failure
A22
The sensor is open or short circuit
Check or change the sensor
Cool2 sensor 2 failure
A23
The sensor is open or short circuit
Check or change the sensor
Exhaust sensor 1 failure
A24
The sensor is open or short circuit
Check or change the sensor
Exhaust sensor 2 failure
A25
The sensor is open or short circuit
Check or change the sensor
Fault probe aspiration circuit 1
A26
The sensor is open or short circuit
Check or change the sensor
Fault probe aspiration circuit 2
A27
The sensor is open or short circuit
Check or change the sensor
Outdoor air temperature fault
A28
The sensor is open or short circuit
Check or change the sensor
Water outlet
temp.sensor.failure
A29
The sensor is open or short circuit
Check or change the sensor
Low pressure transducer
failure (Optional)
A31
1#
The sensor is open or short circuit
Check or change the sensor
High pressure transducer fault
(Optional)
A33
2#
The sensor is open or short circuit
Check or change the sensor
Exhaust temperature switch 1
failure
A42
Gas temperature (outlet) too high.
Possible system blockage
Check sensor and gas circuit
Exhaust temperature switch 2
failure
A43
Gas temperature (outlet) too high.
Possible system blockage
Check sensor and gas circuit
Temp. differential between
water-in and water-out is too
large
A44
Water flow volume not enough. Water
pressure is too low
Check the water flow volume or water
pipes blocked
External air temperature too
low
A46
The external air temperature is lower
than the limit fixed
Check sensor and external air temperature
Fan overload protection
A47
Fan overload
Check or change the fan motor