Inst253 Astral Heat Pumps V07.13 

12 

sensor is under “setting temperature 

 Auto mode temperature difference”, and it stops heating when 

the temperature is over “setting temperature”.(Attention:when set F17<F12, F17=F12 admited) 

$

Compressor delay time

 

The compressor delay time is set by F21, for example, 3 minutes. The controller contains 

a“compressor halt calculagraph”, and it begins to time when compressor stops, the program first check 
the calculagraph before booting the compressor next time, the program will immediately boot the 
compressor if the calculagraph reach 3 minutes ,if the calculagraph doesn’t reach 3 minutes ,it will boot 
again when the calculagraph reaches 3 minutes. Thus you can ensure that the boot alternation is over 3 
minutes after halt, so it can prevent to breaking the compressor as a result of frequent boot. In addition, 
the controller doesn’t boot the compressor within 3 minutes after turning on the power supply, thus the 
compressor can also be protected in the state of power cut and then power on. 

$

Auto defrosting principle

 

The controller will supervise the temperature of outdoor machine when heating normally, and 

decide whether need to defrost according to the time of the outdoor machine in the continuous low 
temperature state. In other words, the defrosting calculagraph begins to time when the outdoor machine 
temperature is lower than “defrost start temperature”, and turns on the defrosting when the value of time 
reaches “defrost start time”. The calculagraph will be cleared if the outdoor machine temperature is 
higher than “defrost start temperature” when timing, and it begins to time again when the outdoor 
machine temperature is lower than “defrost start temperature” next time. In other words, the value of 
defrosting calculagraph shows the continuous low temperature time of the outdoor machine. 

The controller can check the defrosting effect with the temperature of outdoor machine, if the 

temperature of outdoor machine goes up to the “defrost end temperature”, the controller will turn off the 
function of defrosting. If the defrosting time is above “max defrost time”, the controller will turn off 
defrosting forcibly. 

The process above can only run in heating state, in other words, the controller will not turn on 

defrosting in non-heating state.  

Air defrost mode:when start defrost,the compressor stop running ,the fan continue running;when 

stop defrost the compressor and fan continue running; 

4 way valve defrost mode: when start defrost,the compressor and fan continue running,the four-

way valve energized;when stop defrosting the compressor and fan continue running, the four-way valve 

powered off. 

$

Water pump control

 

The controller can choose whether to use water pump or not (F40),0 means no water pump function, 

1 means use water pump. When  water pump runs, the compressor start up ahead of the time of F41, 

delaying  turn off the compressor of the time of F42.When external alarm and probation time over 

alarm,cut off water pump  output  immediately.The compressor won’t start up until the water pump 

achieve the working time of F41.  

When the machine unit stop running,the water pump follow the below request: F43stop, F44 run,and 

circle. 

$

External alarm 

 

The controller can connect 3 switching values as external alarm source (Pin 4, 5), (Pin 13, 14), (Pin 

14, 15), Only when the compressor is running ,and the external alarm occurs, the controller stops, 
displays the alarm code “A11”, “A12” “A15”. External alarm signal: always closed, unlocked. 

 

$

 Running in different period of time 

   The controller contains real time clock, and can time accurately. In “Econ Mode”, the controller will 
ensure that whether need to heat according to water temperature, otherwise the current time is in or not in 
the setting period of time, if it is not in the setting period of time, then the controller will not heat whether 
the water temperature is high or low. 

The controller can be set 3 heat periods of time at most, if you don’t need some periods of time, you 

can set the starting time and ending time which you don’t need as “OFF”. 

    In addition, if the ending time is earlier than starting time, the controller considers this ending time is 
next day. For example, the period of time is “22:00”to“03:30”, the controller considers it as 22:00 at 
night to 03:30 next day. 

Summary of Contents for BPM400A

Page 1: ...t 07 5552 2600 Perth 08 9350 2600 Sydney 02 9853 2100 Townsville 07 4750 3100 sales astralpool com au Brisbane 07 3308 5400 Adelaide 08 8152 7600 www astralpool com au Bolero ND Cleaner INSTALLATION AND OPERATING INSTRUCTIONS I INSTALLATION AND OPERATING INSTRUCTIONS Astral Heat Pumps ...

Page 2: ...Inst253 Astral Heat Pumps V07 13 2 ...

Page 3: ...echnical Specifications 6 Digital Thermostat Operation 7 Fault Indication 8 Maintenance Maintenance Instructions 8 Energy saving Tips 8 Winter Operation 9 Installation Flow Rates 10 Water Connections 10 Clearances 11 Electrical Connection 11 Guide to Heat Pump Noise 12 Troubleshooting Fault Finding and Remedies 16 Wiring Diagrams 17 Warranty Terms and Conditions 20 ...

Page 4: ...o ensure an adequate supply of air and to avoid recirculation of the cooled air exiting the top of the unit For this reason the heat pump should not be installed in confined spaces and must have a minimum of 1000 mm clearance above it and 500 mm clearance to the sides and rear A clearance of 1000mm is required to the front of the unit to allow air flow out of the unit Although the unit is weatherp...

Page 5: ...or hot tub the user should check the water temperature with an accurate thermometer spa or hot tub thermostats may be inaccurate by as much as 2 C 5 Persons with a medical history of heart disease circulatory problems diabetes or blood pressure problems should obtain their physician s advice before using spas or hot tubs 6 Persons taking medications which induce drowsiness such as tranquillisers a...

Page 6: ...LANCE It is imperative that correct chemical balance be maintained in your pool and spa water otherwise corrosion of your heater may occur Corrosion due to chemically imbalanced water or excessive sanitiser is detectable and will void warranty Your local pool shop specialist or spa retailer can advise correct chemical balance Your water should be checked and maintained regularly by a pool water pr...

Page 7: ...ATE SPEED RPM 850 850 850 850 850 BLOWER STYLE NOISE LEVEL dB A 51 58 58 58 58 WATER CONNECTION mm 50 50 50 50 50 WATER FLOW m3 h 5 0 7 5 8 0 9 0 10 0 WATER PRESSURE LOSS kPa 10 12 12 12 12 NET DIMENSION mm 860 310 920 860 310 920 950 340 1300 950 340 1300 950 340 1300 GROSS DIMENSION mm 930 430 1080 930 430 1080 1030 460 1450 1030 460 1450 1030 460 1450 WOODEN PLATE mm 920 420 100 920 420 100 102...

Page 8: ... or forbidden F Real Time Clock RTC Internal RTC it is still running when power off and it supplies accurate time used for real time defrost function etc F Others Temperature upper and lower limit can be set direction of four way valve can be set compressor start delay protection temperature sensor error alarm and so on Main Technique Index O Temperature display range 50 150 The resolution is 0 1 ...

Page 9: ... to look over and adjust the real clock time Press the key Set to enter the state of displaying time when in the state of displaying temperature Press the key Set for some time to enter the state of adjusting time and press the key Set to return to the state of displaying temperature In the state of adjusting time the hour part of the LED flashes and you can adjust the hour by using the key and th...

Page 10: ...EAT COOL refrigeration mode HEAT Heat mode C H Auto mode Defrosting F31 Defrost start temperature 20 80 2 F32 Defrost end temperature 0 100 10 F33 Defrost start time 1 999 30 min F34 Max defrost time Off 1 99 10 min Off means no defrost F37 Defrost mode 0 1 0 0 air defrost 1 4 way valve defrost Water Pump F40 Water Pump Select 0 1 1 0 water pump is not enable 1 water pump is enable F41 Water pump ...

Page 11: ...int is controlled by setting temperature F11 or press the set key for some time to set temperature difference F12 and Auto mode temperature difference In refrigeration mode 4 way Valve is enable and follow compressor the controller begins to refrigerate when the temperature of the temperature sensor is over setting temperature temperature difference and it stops refrigerating when the temperature ...

Page 12: ... the function of defrosting If the defrosting time is above max defrost time the controller will turn off defrosting forcibly The process above can only run in heating state in other words the controller will not turn on defrosting in non heating state Air defrost mode when start defrost the compressor stop running the fan continue running when stop defrost the compressor and fan continue running ...

Page 13: ...hour Password In order to prevent irrespective persons from changing the parameters you can set a password F80 and if you have set a password the controller will hint you to enter the password after you press the key M for 5 seconds you must enter the correct password and then you can set the parameters If you don t need the password you can set F80 to OFF Notice that you must remember the passwor...

Page 14: ...s accepted as a comfortable and healthy swimming temperature 3 Use an accurate thermometer 4 Set timeclock to start filtration and circulation system no earlier than daybreak The pool loses less heat at this time and the heat pump operates more efficiently during the warmer times of the day 5 If your filtration pump is large consider installing a small pump for circulating water through the heat p...

Page 15: ...until reading is approximately 1 5MPa With the unit turned off the gauge should settle at approximately 0 8MPa If these readings are not achieved please contact Astral Pool service WATER CONNECTIONS Where the heat pump is installed in the filtration circuit the heater should always be installed after the pump and filter The water connections are located on the right hand side of the heater The inl...

Page 16: ...all pool or spa equipment connected to mains power should be protected by an RCD circuit breaker Refer to heater data plate for specifications of operating voltage and current This appliance must be installed in accordance with local regulations and the National Wiring Rules A multi pole isolating switch must be installed that operates in all live conductors so that it isolates the entire equipmen...

Page 17: ...ich the noise is emitted Criteria for noise emissions generally take into account back ground noise at the time of day but the most stringent criteria applies at night and take into account the Heat Pump will most likely need to operate at night during cooler months of the year to maintain the pool temperature This guide provides an estimate only and should not be taken as definite advice on the l...

Page 18: ...t Pump from noise sensitive location eg Typical paling fence with small gaps due to warping 5 4 The fence barrier blocks line of sight of the Heat Pump from noise sensitive location e g Colorbond fencing concrete block masonary brick Fibre cement sheeting 10 Reflection Factor Noise can reflect from walls roofs sheds etc This can have the effect of making the noise seem louder that what it is Put t...

Page 19: ...refore your equation will now look like this 64 db A 5 3 62 Heat Pump Sound Barrier Factor Reflective Surface Distance Factor Pressure Level Factor The distance factor is 62 which should be written in Box 3 The final step is to mark 64 on Column 2 below and draw a straight line through the middle X to reach Column 1 Column 1 is the minimum distance the Heat Pump should be installed from a noise se...

Page 20: ... a plant room garage etc Allow a minimum of 500mm clearance from the sides and rear of the heat pump and a minimum of 1000mm service access from the front of the Heat Pump Ensure an electrical isolation switch is located nearby the Heat Pump On Three Phase models ensure the phase rotation of the compressor is checked before commissioning of the unit Ensure the water pressure switch operation is ch...

Page 21: ...et temperature higher than water temperature Decrease set temperature to cool Water too hot fault condition displayed Refer to fault indication table HEATER SHORT CYCLING RAPID ON AND OFF OPERATION Possible cause Remedy Insufficient water flow Clean filter and pump strainer Defective wiring Repair or replace wiring Defective high limit or thermostat Repair or replace If the heater cannot be made t...

Page 22: ...Inst253 Astral Heat Pumps V07 13 22 WIRING DIAGRAMS BPM400 BPM600 ...

Page 23: ...Inst253 Astral Heat Pumps V07 13 23 WIRING DIAGRAMS BPM700 BPM800 ...

Page 24: ...Inst253 Astral Heat Pumps V07 13 24 WIRING DIAGRAMS BPT900 ...

Page 25: ...ponents 12 months If a defect appears in the Product before the end of the warranty period and AstralPool finds the Product to be defective in materials or workmanship AstralPool will in its sole discretion either a replace or repair the Product or the defective part of the Product free of charge or b Cause the Product or the defective part of the Product to be replaced or repaired by an Authorise...

Page 26: ...rating instructions and any instructions by AstralPool e the Product has been subject to accident negligence alteration abuse or misuse The warranty does not extend to a normal wear and tear b weather and other environmental conditions including but not limited to storm flood and or heat wave damage or c service and maintenance items Examples of exclusions include but are not limited to incorrect ...

Page 27: ...Inst253 Astral Heat Pumps V07 13 27 ...

Page 28: ...ictoria New South Wales Queensland South Australia Western Australia Gold Coast Townsville Ph 03 8796 8600 Ph 02 9853 2100 Ph 07 3308 5400 Ph 08 8152 7600 Ph 08 9350 2600 Ph 07 5552 2600 Ph 07 4750 3100 Fax 03 8796 8670 Fax 02 98532170 Fax 07 3308 5470 Fax 08 81527670 Fax 08 9350 2670 Fax 07 5552 2670 Fax 07 4750 3170 INSTALLATION AND OPERATING INSTRUCTIONS I INSTALLATION AND OPERATING INSTRUCTION...

Reviews: