Clean boiler chambers from smoke-black and pitch scurf once or twice a month. Clean the
boiler when the fuel is completely burned and the boiler is cooled down to at least +40 °C.
Clean smoke-black and scurf from combustion chambers and flue walls using a scraper
and metal hog. Clean after the doors of the combustion chambers are open and caps of flue upper
openings unscrewed . When finished, check, whether no ashes or smoke-black fell into the ventilator
opening and tightly screw the caps of the flue openings.
Control water pressure in the heating system at least every two weeks. If necessary, fill it
up. If the boiler is not being heated, drain the water off the system when air temperature is below 0
°
C!
Emergency extinction of the boiler
If due to any reasons you must immediately extinct the heated boiler, by any means don’t
pour water on the kindling wood! The boiler can burst.
It is very convenient to use dry sand for emergency extinction. There should be ~50 kg of
dry sand in the boiler room. Sand not only well isolates burning firewood from the air oxygen but also
cools down the burning zone. Then, when the boiler cools down, sand can be easily cleaned and
removed.
7. POSSIBLE DAMAGES
Damage
Cause
Ways of elimination
1. The set temperature
(power) cannot be
reached
-
Not enough water in the heating
system;
-
Thermo regulator or ventilator is
broken;
-
Bad quality fuel (high moisture
content, very large firewood);
-
Heating surfaces of the boiler are
very impure;
-
No traction in the chimney (impure) –
the upper ignition is congested;
-
Ceramic burner is foul.
Fill up
Replace
Use dry fuel, split firewood
Clean
Clean
Clean
Clean
2. Smoke breaks through
the doors
-
Tightening rope is damaged;
-
Doors are leaky along the whole
perimeter.
-
No traction in the chimney
Replace with a new one
Adjust hinge supports and door
lock (regulated screwing or
unscrewing door hinge or lock
screws)
Clean.
3. Ventilator isn’t
operating
-
Emergency thermostat went off
(switch light of ventilator is off);
-
Thermo regulator or ventilator is
broken;
-
Disconnection of electricity supply.
Call representatives of the service
company; turn on after indication of
the causes (see section 5)
Replace
Check electric fuses of the building,
call the electrician