PHOENIX Talon - Operation and Service Manual
24
50'
100'
150'
200'
250'
300'
Burner
Model
Maximum
Air Flow
(SCFM)
Pipe
Size
Pipe
Size
Pipe
Size
Pipe
Size
Pipe
Size
Pipe
Size
PT-50
50
1/2"
1/2"
1/2"
3/4"
3/4"
3/4"
PT-75
85
3/4"
1"
1"
1"
1"
1"
PT-100
85
3/4"
1"
1"
1"
1"
1"
PT-125
120
1"
1"
1"
1"
1-1/4"
1-1/4"
PT-150
140
1"
1"
1-1/4"
1-1/4"
1-1/4"
1-1/4"
COMPRESSED AIR PIPE SIZES
100 PSIG Supply
Air Pressure
Length of Compressed Air Line
Illustration 11 – Typical Compressed Air Train
Table 8 – Recommended field pipe size for compressed air at various lengths.
WARNING!
Lock out power prior to working on high pressure piping.
Relieve pressure in the piping, in the valves, and solenoids, prior to working on the piping.
Remember that dangerous air pressure can also be trapped between valves or controllers.