A special situation arises if a momentary bypass switch is used during the release delay period.  
The lock releases immediately for as long as the bypass switch is closed.  The 15 or 30 second 

release delay countdown continues "in the background" as by code, this process is irrevocable.  
If the bypass switch reopens before the release delay expires, the lock will resecure and 
correctly release again when the underlying release delay times out.  The bypass switch, 
therefore can be used for momentary immediate exit or entry during the release delay period 
without affecting code legal operation of the board. 

 
7.3  FREE EGRESS FUNCTION 
The free egress function puts the board in a different operating mode.  When +V is switched to 
terminal FE by an alternate action switch, the board goes into free egress mode.  In this mode, 
use of the initiate device, immediately releases the door for egress.  When the initiate device is 
released, the door immediately relocks.  Often, a time clock such as Securitron's model DT-7 is 

used to put the door into free egress mode during the day and exit delay mode at night. 
 

FIG. 4:  OPTIONAL FREE EGRESS AND LOCKDOWN MODES 

NO

NC

C1

C2

C3

NC

NC

NO

NO

AN EXTERNAL ALTERNATE SWITCH IN PARALLEL WITH

INITIATE WILL PUT THE BOARD INTO LOCKDOWN.

WHEN +V IS SWITCHED TO "FE",
THE BOARD IS IN FREE EGRESS
MODE.  THE INITIATE SWITCH
IMMEDIATELY RELEASES THE  LOCK
WITH NO ALARM, EXCEPT
OPTIONALLY FROM THE LOCK STATUS MONITORING FUNCTION.

INITIATE (NC)

INITIATE CAN NOT BE READ

+

LS

BP

FE

IN

RS

DC

 

The free egress mode differs from the bypass mode as follows:  When the door is bypassed, the 
fail safe lock is released so that both entry and exit is freely possible.  Also, during bypass mode, 
the board performs no monitoring functions.  In the free egress mode, the lock remains secure 

so that entry is blocked, but egress without alarm signaling occurs immediately when the initiate 
device is pressed.  If lock status monitoring is in use, the remote alarm relay will still report a 
door that doesn't resecure within 5 seconds after a free egress event. 
 
The free egress function is most successfully used with a switched exit device such as 

Securitron's Touch Sense Bar.  Free egress occurs with a single motion.  If a push button is 
being employed, the button will have to be held and the door pushed open with the other hand. 
 
7.4  LOCKDOWN MODE 
It may be desired that exit delay be employed during the day but at night and weekends, when 

the building is empty, the door should be locked with no unauthorized egress or entry possible.  
This is most easily accomplished by the use of a time clock switch, such as Securitron's model 
DT-7, which will close across terminals "+" and IN to put the board into lockdown.  This simply 
shunts out the initiate device so that the board cannot respond to its use.  If authorized entry or 
exit is desired, the bypass function will still release the door for 5 seconds.  If lock status 
monitoring has been implemented, an alarm signal will still be created in the event of a forced 

door or a bypassed door that doesn't relock.  We recommend that use of lockdown mode be 
checked with the local approving authority in advance. 
 
7.5  LOCK POWERED AFTER RELEASE DELAY MODE (DELAY CONTROL) 

Summary of Contents for SECURITRON XDT-12

Page 1: ...evice is one that relies on no special knowledge for operation Securitron s Touch Sense Bar is an excellent choice for non fire rated doors A switch equipped fire rated panic bar is appropriate for fire rated doors Push buttons are also used but they may not be acceptable to local building officials on the grounds of requiring special knowledge Other initiate devices include mats curtain detectors...

Page 2: ...inning of the release delay period until the door is relocked The remote alarm relay is intended to signal to a security office that a security violation is occurring at the door It ignores the nuisance delay period as this should be seen as a false alarm unless the delay becomes irrevocable It also continues to signal until the door is relocked correcting the security violation The remote alarm r...

Page 3: ... with the local authority 3 3 UNIFORM BUILDING CODE NUISANCE DELAY Required and must be set at 2 seconds RELEASE DELAY 15 seconds only RELOCKING Must be manual and must be located at the door This is generally interpreted to mean that a doorswitch can t be used for relocking A keyswitch is typical POWER The door must release when power to it is cut off The door must also release if power to the sm...

Page 4: ...local authorities may require a 45 second delayed BOCA relocking The standard XDT board does not support this Contact the factory to order a modified board with the 45 second feature See section 3 4 for a description of BOCA relocking 5 POWER Two versions of the XDT exist which operate respectively on 12 or 24 VDC Voltage can vary from 10 to 20 and must be filtered or regulated Pulsating DC transf...

Page 5: ...ke 2 wire component packed with the XDT board It is installed in parallel with the fail safe lock and its function is to absorb the inductive kickback which is generated when the lock is switched off If the MOV is omitted electronic noise from the lock may interfere with proper operation of the board and relay life will be shortened If you are used Securitron s Magnalock in the installation the MO...

Page 6: ...D TO BP THE LOCK WILL RELEASE AND ALL ALARMS WILL BE SUPPRESSED USE WITH AN ALTERNATE SWITCH ALLOWS RELEASE OF THE LOCK FOR A PERIOD OF TIME USE OF A MOMENTARY SWITCH RELEASES THE LOCK FOR 5 SECONDS TO PERMIT AUTHORIZED USE OF THE DOOR NO DC 7 2 BYPASS FUNCTION The optional bypass function has two purposes door release for extended periods and authorized entry or exit through the door Release for ...

Page 7: ...S BP FE IN RS DC The free egress mode differs from the bypass mode as follows When the door is bypassed the fail safe lock is released so that both entry and exit is freely possible Also during bypass mode the board performs no monitoring functions In the free egress mode the lock remains secure so that entry is blocked but egress without alarm signaling occurs immediately when the initiate device...

Page 8: ...equipped initiate device such as Securitron s Touch Sense Bar Also any door which combines delayed exit with controlled entry such as from a card reader must depend only on the fail safe lock for entry security The XDT can be set so that after the release delay expires the fail safe lock remains engaged so long as the initiate device is not being pressed When the initiate device is pressed the loc...

Reviews: