Intelligent Power System

Quick Start Guide

Overview

AC Voltage Select Jumper

 – Leave INTACT 

for 120 V input. CUT for 230 V input.

Failure to cut this jumper when using the Securitron AQL 

with a 230 VAC input will result in damage to the system.

AC Input primary AC connection.

AC On LED

 (GREEN)  – Indicates a valid 

AC input voltage is present. Missing AC is 

indicated by this LED extinguishing.

WARNING:

 Always confirm the absence of AC power 

with a meter before servicing to prevent electric shock.

Voltage Selection Jumper

  – Selects the 

output voltage between 12 V and 24 VDC. 

WARNING:

 Remove AC input power before changing 

the voltage select switch to avoid damaging 

the power supply or connected equipment.

FAI LED

 (RED)  – Indicates activation 

of the Fire Alarm Input.

FlexIO Connector

  – Supplies FAI status 

to any accessory boards. Receives fault 

signal from accessory boards.

FAI & Charge Current Configuration Switches

SWITCH 1

FAI Selection

SWITCH 2

Charge Current

OFF

 = Constant Output

OFF

 = High Charge Current

ON

 = Output switches on FAI

ON

 = Low Charge Current

System Fault Contact

 – Contact labeling 

is adjacent to the terminals and shown in 

the unpowered (FAULT) condition.

AC Fault Contact

 – Contact labeling is 

adjacent to the terminals and shown in the 

unpowered (FAULT) condition. AC fault is 

indicated on a missing AC Input voltage.

10 

Auxiliary

 

Voltage

  – A fixed Class 2 DC output.

11 

FAI Input

  – The input from the FACP. Can be wired to 

accept a NO, NC, Open Collector, or Voltage input.

12 

Battery

 

Terminal

 

Connection

  – For the 

optional battery backup. Battery set voltage 

must match the DC output voltage setting.

13 

Main DC Output

  – Of the power supply. The 

output can either be constant or switched based 

on the configuration setting of Switch 1.

NOTE:

 The DC ON LED will be green with voltage 

present, if set to 12 VDC or blue if set to 24 VDC.

14 

DataLink Connection

 – This connector allows 

optional programming and monitoring of the 

Securitron AQL power supply via an optional 

NetLink network module. 

See the instructions 

for the Netlink module for more information.

AC Select

12 V
24 V

1

2

3

6

4

5

7

11

8

9

10

12

13

14

Observe battery 

polarity or damage 

may result

For UL compliance, the AC fault contact must 

be monitored by a listed control panel

Specifications and more details  

found in the full manual here.  

(Downloadable pdf)