2.3 Configuring the TCP/IP Settings
In the orange menu bar at the top of the browser screen,
click the "Configure" link. Figure 7 shows the Configure page.
At the top left of the Configure page is the “TCP/IP Setting”
area. The settings in this area include:
Site ID
Entered by user. ENTER any meaningful name to identify
the AQE midspan unit. This name will be displayed on
the HOME page.
IP Address
The factory default IP address is set to 192.168.1.9. This
address may be changed to any valid IP address. SET the
first three values of the IP address to match the domain
of the network to which the AQE will be connected. SET
the final value to a number between 0 and 255 which is
not being used by any other device on the subnet. In the
event the IP address is later forgotten, PRESS the “Reset”
button on the front panel of the AQE for 6 seconds and the
IP address, default user name, and default password will be
reset to factory default values.
Net Mask
Should typically be set to 255.255.255.0
MAC address
The MAC Address is factory set and is not programmable
by the user.
Gateway IP
The default gateway is 192.168.1.1. This value may be
changed by the user - consult with your IT department
for more information.
DNS0, DNS1
The default value for DNS0 and DNS1 are 192.168.1.1.
These values may be changed by the user - consult with
your IT department for more information.