background image

Rev.  A.1, 10/99 

Page- 8 

board.  The CCS board provides multiple, current limited two Amp outputs on terminals marked 
P1, P2 etc.  The advantage of using these individual outputs as shown on the right of Figure 2 is 
that any short circuit in the downstream wiring will take out only one of the breakers on the CCS 
board and the rest of the installation will continue to operate.  Use of a multiple output Securitron 
power suppy materially increases the reliability of the installation and is therefore recommended.  
Note however that you can always 

add in-line fuses or breakers

 to any single output power 

supply to create the effect of the Securitron supply with CCS board. 

 

FIG. 2:  POWER SUPPLY TO LCP BOARD WIRING 

 

+4

+3

+2

+1

POWER
SUPPLY

IF POWER SUPPLY HAS SINGLE
DC OUTPUTS, THE "+" TERMINALS
MUST BE JUMPED TOGETHER AS
SHOWN.

+4

+3

+2

+1

P1

P2

P3

P4

R1

SECURITRON POWER SUPPLY
WITH CCS BOARD PERMITS
INDIVIDUAL OPERATION OF "+"
TERMINALS

EACH "P" TERMINAL MAY OPERATE ONE OR
MORE "+" TERMINALS DEPENDING ON THE 
NUMBER OF ZONES IN THE PANEL.

P5

RED FLYING LEAD FROM
RESET TOGGLE

RE

F

L

Y

IN

G

 LE

A

D

 F

R

O

M

R

ESE

T

 T

O

G

G

L

E

NOTE: IF PB OPTION IS SUPPLIED, DC NEG
CONNECTS TO FLYING BLACK LEAD RATHER
THAN TO CIRCUIT BOARD "-" TERMINALS

 

 

On both examples shown in Figure 2, note that there is a 

red flying lead

 from the underside of 

the reset toggle.  This wire simply suV to the toggle common and then, when the spring 
loaded toggle is pressed, +V is input to the “R” terminal of the board which is used to reset the 
violation alarm function.  The red flying lead 

requires coV

 so that the panel violation 

alarm can always be reset.  The reason why the factory doesn’t connect this wire is that when 
individual breakered outputs or ‘upstream” switches are used to operate the “+” terminals on the 
board (shown on the right of Figure 2), coV cannot be guaranteed to any “+” terminal.  
Therefore, as Figure 2 shows, when you have only a single source of +V, connect the red flying 
lead to any of the “+” terminals (they will all get constant power).  When you can employ 
individually breV outputs (right side of Figure 2), connect one of the breakers 
separately to the red flying lead in order to guarantee that it will always have power on it.  
Supposing that you have to choose between putting two panel zones on one breakered “P” 
output terminal or sharing a breakered “P” terminal between a panel zone and the red flying 
lead, it is better to do the former.  The panel user will expect to always be able to reset a 
violation alarm even if one of the panel zones is de-powered from a short circuit or other 
condition. 

Note that often the number of panel zones exceeds the number of “P” terminals in the power 
supply.  Each “P” terminal can power multiple “+” input terminals so long as the current rating of 
the “P” terminal is not exceeded.  This in turn depends on the voltage and the type of lock being 

Summary of Contents for ELECTRIC LOCK

Page 1: ...ONS Page 4 Once you have determined the options present or desired on your panel read the corresponding section below to learn the function and operation of the supplied option SECTION 2 1 SILENCE LAT...

Page 2: ...SECTION 4 8 AC LOCK CONTROL Page 17 This section explains use of the panel with AC locks SECTION 5 OPTION WIRING Page 17 The following 5 sections explain the field wiring that relates to the options...

Page 3: ...sure F Flush mount pull box cover with back box R 19 Rack panel face A slope front desk mount is the standard panel enclosure SL Silence Latch PB Emergency all release for fail safe locks only AM Addi...

Page 4: ...with a much longer operating life The lamp within the HT push button operates just as the toggle bat yellow indicator 1 4 MONITORING Each zone toggle switch has a bicolor LED with green and red inter...

Page 5: ...f the keyswitch activates a release hold timer as is commonly done a long delay is not required The timer will shunt the panel violation condition allowing the door to reclose When the timer resecures...

Page 6: ...n switch In normal operation the red indicator in the switch is off When the switch is pressed it cuts off all DC power to the locks releasing them the PB option works with fail safe locks only The re...

Page 7: ...wer cannot be removed from the locks by the panel The KP2 and MK2 versions are for fail secure locks When they are in the bypass position power is removed from the panel boards so that the locks stay...

Page 8: ...ION V OUT WHEN SWITCH OFF FAIL SECURE LOCK V OUT WHEN SWITCH OFF FAIL SECURE LOCK V OUT WHEN SWITCH OFF FAIL SECURE LOCK V OUT WHEN SWITCH OFF FAIL SECURE LOCK L2 TERMINALS 1 2 3 4 They constitute the...

Page 9: ...tion condition of the zone is shunted While the lock is legally released toggle off bicolor off toggle bat yellow LED on the zone will not violate As the lock status input S terminals reports insecure...

Page 10: ...ply supplies V to the toggle common and then when the spring loaded toggle is pressed V is input to the R terminal of the board which is used to reset the violation alarm function The red flying lead...

Page 11: ...devices employed No lock or door status monitoring switch is used As the drawing shows lock power comes from the L terminal and the S terminal is connected to the power wire at the lock With this con...

Page 12: ...MONITORING AND VIOLATION ALARM FUNCTION FAIL SAFE LOCK CLOSED WHEN SECURE LOCK OR DOOR STATUS SWITCH REMOTE RELEASE SWITCH A REMOTE RELEASE SWITCH IS ADDED SUCH AS CARD READER KEYPAD PUSH BUTTON KEYS...

Page 13: ...witches are in series An example would be a card reader for entry and a push button for exit The SPDT contacts of each remote switch are connected in NC series as shown so that either switch can relea...

Page 14: ...S SWITCH IS ADDED TO PROVIDE MONITORING AND VIOLATION ALARM FUNCTION LOCK CLOSED WHEN SECURE LOCK OR DOOR STATUS SWITCH A REMOTE RELEASE SWITCH IS ADDED SUCH AS CARD READER KEYPAD PUSH BUTTON KEYSWITC...

Page 15: ...orts secure and the door is closed before the green indicator comes on In theory lock status can t report secure if the door is open However combining the 2 switches enhances security in case the lock...

Page 16: ...ith a powered switching device at the door such as a card reader or digital keypad This is to keep the drawings simple and also recognizes the fact that powered devices such as card readers will often...

Page 17: ...lease hold timer as it releases the lock and holds the release for an amount of time Such timers are also called off delay timers In selecting the timer the requirements are that it has an SPDT relay...

Page 18: ...imer s NO contact blue This also inputs V to the E terminal thereby annunciating legal release at the panel The timer s NC contact green breaks V to one side of the lock door status switch insuring th...

Page 19: ...rt will be on If indicators are present on more than one switch an example would be an entry keyswitch and exit button they should be wired in parallel so that the annunciation is the same from both s...

Page 20: ...e the entire system should be connected to this black wire When the button is pressed all DC power will be broken which will immediately release all the locks Make sure you terminate the lock negative...

Page 21: ...e rather than delayed exit mode We advise not using this option with delayed exit To simplify this process we advocate two different connection schemes which depend on whether the bypass function of t...

Page 22: ...number of reasons for the particular wiring method in Figure 9 Note first the connection to terminal FE on the XDT board Inputting V to this terminal places the XDT board in free egress mode which mea...

Page 23: ...elease switch is momentary The bypass input will release the lock without signalling any alarm for 5 seconds Use of the bypass input makes substantial changes in the entire wiring scheme The lock stat...

Page 24: ...he panel s monitoring functions are altered from the ones discussed in the previous wiring scheme without bypass In the normal secure condition the main LED is green and no alarm sounds During the nui...

Page 25: ...ors from the boards by clipping them off 5 4 SWITCH BYPASS WIRING OPTION KP1 OR MK1 FAIL SAFE LOCKS The option comes pre wired for whichever type of keyswitch has been chosen However if the panel has...

Page 26: ...The keyswitch removes power from all the terminal boards This bypasses the ability of the toggles to release the locks The panel s monitoring capability will also be disabled but the purpose of the k...

Page 27: ...zone toggle on each panel is up Either toggle can release the lock but the toggle that released the lock must be used to resecure it Note that this set up is well suited for momentary toggles Since t...

Page 28: ...red in series with the button on the master panel Switch bypass must be implemented on each panel FIG 15 CONNECTIONS BETWEEN STANDARD BOARD AND SLAVE BOARD TO POWER SUPPLY SLAVE BOARD CONNECTS TO LOCA...

Page 29: ...e to gain access to the disabled panel during that portion of the day To accomplish this each panel must be furnished with a DPDT alternate action keyswitch with contacts of sufficient capacity to han...

Page 30: ...C NO DPDT KEYSWITCH ON PANEL 2 ALTERNATE ACTION COM NC NO COM NC NO COM CONNECTS TO TERMINALS ON ALL BOARDS PANEL 1 PANEL 2 WIRES MUST BE ABLE TO CARRY FULL LOAD OF INSTALLATION CONNECT TERMINALS BETW...

Page 31: ...ows continued monitoring without alarm condition The toggle switch itself will illuminate yellow when the zone is disarmed Only certain of the panel options are usefull if the panel is used for monito...

Page 32: ...customer The replacement at SECURITRON s sole option may be the identical item or a newer unit which serves as a functional replacement In the event that the product type has become obsolete in SECURI...

Reviews: