1004935-US-1.0
Issue 2008-11-13
11
5.3.7
Lock Output
The Lock Output is short circuit proof and can source a lock with 24V, 375 mA.
The output can be locked with power or locked without power. It can be selected
through the Function Selector FS4 (Locked w. / w.o. power).
The lock activation time can be either 1,5 s + opening delay or until closing. It can be
selected through the function selector FS5 (Lock time 1,5 s/until closing).
“Opening Delay” for lock, the time that will pass before the motor starts, can be
adjusted from 0 to 3 s.
If a home switch is installed, the lock opening time will first start when the home
switch is deactivated. This prevents the door from jamming in the lock if the presence
detection is activated.
5.3.8
Double Door
The CSDB on the Slave Unit must be configured as a slave. This can be selected
through the function selector FS7 (Master / Slave).
To prevent the thicker door panels from jamming, a delay of 0,5 sec. can be selected
through Function Selector FS6 (Slave Delay). A Home Switch is recommended to
prevent an open delay, if a activation impulse should be received while closing.
5.3.9
Push to Go
A push or pull on the door from Closed Position will start an automatic opening cycle
if the program selection is AUTO or EXIT, and remain open during the hold open
time “Outer HOT” (0 to 30 s).
A home switch on the operator is needed to achieve Push to Go and the Function
Selector FS8 (Push to Go) must be set to ON.
The LED indicates when the Home Switch is active.
5.3.10
Error Messages
The LED indicates sensor error; 1 flash of 0,2 sec. and then 1 sec. pause etc.
5.3.11
Program Selector
Program Selector PS-3B, having three positions (OFF-AUTO-OPEN) can be con-
nected to the CSDB.
Note!
If the MVI-input is used for 6-24 V, the PS-3B can not be used.
The key impulse will work even in program selection OFF position.
Presence sensors are enabled in all Program Selector settings, unless in the Kill Mode
of operation.