2.3 AERAULIC CONNECTION SET-UP
CORRUGATED PIPE CONNECTION TOWARDS INDOOR ROOMS
Inside the cabinet kit there are the connections for air distribution inside the building;
It is possible to install up to 6 corrugated pipes with diam. of 75 mm for both supply and return;
The body allows 6+6 corrugated pipes to pass through the bottom where the bottom insulation is installed;
On the other hand, the starting fittings are installed at the bottom of the plenum inside the body;
- Proceed with installation of the starting fitting in the desired position;
- Carefully cut the insulation with a cutter or mill with a diameter of 80mm;
- Then put the pipe in place and fit it to the starting fitting;
Room air supply and exhaust pipe positioning
SUPPLY
DUCTS
EXHAUST
DUCTS