3.4. Types of Modbus Registers
There are 4 types of variables available in the module
Type Beginning adress
Variable
Access
Modbus
Command
1
00001
Digital Outputs
Bit
Read & Write
1, 5, 15
2
10001
Digital Inputs
Bit
Read
2
3
30001
Input Registers
Registered
Read
3
4
40001
Output Registers
Registered
Read & Write
4, 6, 16
3.5. Communication settings
The data stored in the modules memory are in 16-bit registers. Access to registers is
via MODBUS RTU or MODBUS ASCII.
3.5.1. Default settings
You can restore the default configuration by the switch SW8 (see 3.5.2 - Restore the
Baud rate
19200
Parity
Nie
Data bits
8
Stop bits
1
Reply Delay [ms]
0
Modbus Type
RTU
3.5.2. Restore the default configuration
To restore the default configuration:
•
turn off the power
•
turn on the switch SW8
•
turn on the power
•
when power and communication LED start blinking alternately than turn off the
switch SW8
Caution!
After restoring the default configuration all values stored in the registers will
be cleared as well.