background image

RS485 MODBUS Module 8AI

User Manual

7.  Modules Registers

7.1.  Registered access

Modbus  Dec 

Hex 

Register Name

Access

Description

30001

0

0x00 Version/Type

Read

Version and Type of the device

30002

1

0x01 Address

Read

Module Address

40003

2

0x02 Baud rate

Read & Write

RS485 baud rate

40004

3

0x03 Stop Bits & Data Bits

Read & Write

No of Stop bits & Data Bits (see 3.4.2)

40005

4

0x04 Parity

Read & Write

Parity bit

40006

5

0x05 Response Delay

Read & Write

Response delay in ms

40007

6

0x06 Modbus Mode

Read & Write

Modbus Mode (ASCII or RTU)

40010

9

0x09 Filter

Read & Write

Measurement filtering, value from 1 to 10

40033

32

0x20 Received packets MSB

Read & Write

No of received packets

40034

33

0x21 Received packets LSB

Read & Write

40035

34

0x22 Incorrect packets MSB

Read & Write

No of received packets with error

40036

35

0x23 Incorrect packets LSB

Read & Write

40037

36

0x24 Sent packets MSB

Read & Write

No of sent packets

40038

37

0x25 Sent packets LSB

Read & Write

30051

50

0x32 Inputs

Read 

Connected inputs

Bit in high state → signal is connected

40052

51

0x33 Outputs

Read & Write

Alarms state

bit  no. 3 digital output

30053

52

0x34 Voltage

Read 

Voltage in μV

30054

53

0x35 Current

Read 

Current in 

μA or 

30055

54

0x36 Alarm – max voltage

Read & Write

Maximum value of voltage excess which causes set

bit no 1 in the register 40052 

30056

55

0x37 Alarm – min voltage

Read & Write

Minimum value of voltage. If voltage drops below

this voltage bit no 1 in the register 40052 is set.

30057

56

0x38 Alarm – max current

Read & Write

Maximum value of current excess which causes set

bit no 1 in the register 40052 

30058

57

0x39 Alarm – min current

Read & Write

Minimum value of current. If current drops below

this voltage bit no 1 in the register 40052 is set.

30059

58

0x3A Voltage alarm configuration Read & Write

Alarms configuration

0 – alarms state depends on actual values

1 – alarms state need to clear by master

30060

59

0x3B Current alarm configuration Read & Write

30061

60

0x3C Voltage input configuration

Read & Write

0 – OFF
1 – 0 .. 10V
2 – -10 .. 10V
3 – 0 .. 1V
4 – -1 .. 1V

40062

61

0x3D Current input configuration

Read & Write

0 – OFF
1 – 0 .. 20mA (in 

μA)

2 – 4 .. 20mA (in 

‰)

3 – -20mA .. 20mA (in μA

)

40063

62

0x3E Digital output configuration

Read & Write

Digital output configuration

0 – output controlled by master
1 – output state depends voltage
2 – output state depends current

Expansion Module  – 1 analog input, 1 digital output

User Manual

Version 1.3

9 / 12

Summary of Contents for Mini Modbus 1AI

Page 1: ...Mini Modbus 1AI Expansion Module 1 analog input 1 digital output Version 1 3 User Manual Manufactured for...

Page 2: ...ncurring any liability for the purposes of commercial law This information does not release you from the obligation of own judgement and verification We reserve the right to change product specificati...

Page 3: ...age measurement and 1 input for current measurement both inputs can be used in this same time In addition the module is equipped with 1 configurable digital output PNP or NPN type This module is conne...

Page 4: ...processing time 70ms channel Voltage measurement error Max 1 7 Current measurement error Max 0 1 Digital outputs Maximum current and voltage 250mA 50V Temperature Work 20 C 65 C Storage 40 C 85 C Conn...

Page 5: ...ould be taken at the installation stage to prevent these effects These protective steps include control cabinet grounding module grounding cable shield grounding protective elements for electromagneti...

Page 6: ...3 30001 Input Registers Registered Read 3 4 40001 Output Registers Registered Read Write 4 6 16 3 4 Communication settings The data stored in the modules memory are in 16 bit registers Access to regi...

Page 7: ...bit 2 two stop bits 40004 3 0x03 Data Bits MSB 7 7 data bits 8 8 data bits 40006 5 0x05 Response delay Time in ms 40007 6 0x06 Modbus Mode 0 RTU 1 ASCII 4 Indicators Indicator Description ON LED indi...

Page 8: ...5 MODBUS Module 8AI User Manual 5 Block diagram 6 Module Connection Expansion Module 1 analog input 1 digital output User Manual Version 1 3 8 12 MUX ADC VIN IIN 100 COM V OUT C RS485 VCC GND GND 485...

Page 9: ...igital output 30053 52 0x34 Voltage Read Voltage in V 30054 53 0x35 Current Read Current in A or 30055 54 0x36 Alarm max voltage Read Write Maximum value of voltage excess which causes set bit no 1 in...

Page 10: ...arm hysteresis Read Write Hysteresis for alarm 7 2 Bit access Modbus Address Dec Address Hex Address Register name Access Description 801 800 0x320 Voltage input Read Voltage input state 802 801 0x321...

Page 11: ...ent value of other registers of the module This program can be a convenient way to test the system as well as to observe real time changes in the registers Communication with the module is done via th...

Page 12: ...5 3 3 Types of Modbus Registers 6 3 4 Communication settings 6 3 4 1 Default settings 6 3 4 2 Configuration registers 7 4 Indicators 7 5 Block diagram 8 6 Module Connection 8 7 Modules Registers 9 7...

Reviews: