Aspar 8AI User Manual Download Page 6

RS485 MODBUS Module 8AI

User Manual

3.  Communication configuration

3.1.  Grounding and shielding

In most cases, IO modules will be installed in an enclosure along with other

devices which generate electromagnetic radiation. Examples of these devices are relays
and contactors, transformers, motor controllers etc. This electromagnetic radiation can
induce electrical noise into both power and signal lines, as well as direct radiation into
the module causing negative effects on the system. Appropriate grounding, shielding
and other protective steps should be taken at the installation stage to prevent these
effects. These protective steps include control cabinet grounding, module grounding,
cable   shield   grounding,   protective   elements   for   electromagnetic   switching   devices,
correct wiring as well as consideration of cable types and their cross sections.

3.2.  Network Termination

Transmission   line   effects   often   present   a   problem   on   data   communication

networks. These problems include reflections and signal attenuation.

To eliminate the presence of reflections from the end of the cable, the cable must

be terminated at both ends with a resistor across the line equal to its characteristic
impedance.  Both   ends  must  be  terminated  since   the  direction   of  propagation  is  bi-
directional. In the case of an RS485 twisted pair cable this termination is typically
120 Ω.

3.3.  Setting Module Address in RS485 Modbus Network

The following table shows how to set switch to determine the address of the

module. The module address is set with the switches in the range of 0 to 31. Addresses
From 32 to 255 can by set via RS485 or USB.

Addr SW5 SW4 SW3 SW2 SW1

0

OFF OFF OFF OFF OFF

1

OFF OFF OFF OFF ON

2

OFF OFF OFF ON OFF

3

OFF OFF OFF ON

ON

4

OFF OFF

ON OFF OFF

5

OFF OFF

ON OFF ON

6

OFF OFF

ON

ON OFF

7

OFF OFF

ON

ON

ON

8

OFF ON

OFF OFF OFF

9

OFF ON

OFF OFF ON

10

OFF ON

OFF ON OFF

Addr SW5 SW4 SW3 SW2 SW1

11

OFF ON

OFF ON

ON

12

OFF ON

ON OFF OFF

13

OFF ON

ON OFF ON

14

OFF ON

ON

ON OFF

15

OFF ON

ON

ON

ON

16

ON OFF OFF OFF OFF

17

ON OFF OFF OFF ON

18

ON OFF OFF ON OFF

19

ON OFF OFF ON

ON

20

ON OFF

ON OFF OFF

21

ON OFF

ON OFF ON

Addr SW5 SW4 SW3 SW2 SW1

22

ON OFF

ON

ON OFF

23

ON OFF

ON

ON

ON

24

ON

ON

OFF OFF OFF

25

ON

ON

OFF OFF ON

26

ON

ON

OFF ON OFF

27

ON

ON

OFF ON

ON

28

ON

ON

ON OFF OFF

29

ON

ON

ON OFF ON

30

ON

ON

ON

ON OFF

31

ON

ON

ON

ON

ON

Expansion Module  – 8 analog inputs

User Manual

Version 1.5

6 / 15

Summary of Contents for 8AI

Page 1: ...RS485 MODBUS Module 8AI Expansion Module 8 analog inputs Version 1 5 User Manual Manufactured for...

Page 2: ...ithout incurring any liability for the purposes of commercial law This information does not release you from the obligation of own judgement and verification We reserve the right to change product spe...

Page 3: ...te adapter The device has a set of 8 analog input measurements In addition the module is equipped with 2 configurable digital outputs This module is connected to the RS485 bus with twisted pair wire C...

Page 4: ...4mA to 20mA resolution 3 75 A Current input 0mA to 20mA resolution 3 75 A Current input 20mA to 20mA resolution 3 75 A Measurement resolution 14 bits ADC processing time 16ms channel Digital outputs M...

Page 5: ...shown below The module is mounted directly to the rail in the DIN industry standard Power connectors communication and IOs are at the bottom and top of the module USB connector configuration and indi...

Page 6: ...terminated at both ends with a resistor across the line equal to its characteristic impedance Both ends must be terminated since the direction of propagation is bi directional In the case of an RS485...

Page 7: ...rs Access to registers is via MODBUS RTU or MODBUS ASCII 3 5 1 Default settings You can restore the default configuration by the switch SW6 see 3 5 2 Restore the default configuration Baud rate 19200...

Page 8: ...bits 8 8 data bits 40006 5 0x05 Response delay Time in ms 40007 6 0x06 Modbus Mode 0 RTU 1 ASCII 4 Indicators Indicator Description Power supply LED indicates that the module is correctly powered Comm...

Page 9: ...RS485 MODBUS Module 8AI User Manual 5 Module Connection Expansion Module 8 analog inputs User Manual Version 1 5 9 15...

Page 10: ...odule as shown below Jumper Description off Voltage measurement shorted Current measurement 7 Switches Switch Function Description 1 Module address 1 Setting module address from 0 to 31 2 Module addre...

Page 11: ...uts Read Write Alarms state bit 8 and 9 alarm outputs 30053 52 0x34 Analog 1 Read Value of analog input in mV for voltage inputs in A for current inputs 30054 53 0x35 Analog 2 Read 30055 54 0x36 Analo...

Page 12: ...ion and 6 Selecting the input mode 40088 87 0x57 Input 2 settings Read Write 40089 88 0x58 Input 3 settings Read Write 40090 89 0x59 Input 4 settings Read Write 40091 90 0x5A Input 5 settings Read Wri...

Page 13: ...ut is connected 807 806 0x326 Input 7 Read Set when the input is connected 808 807 0x327 Input 8 Read Set when the input is connected 817 816 0x330 Alarm 1 Read Alarm state 1 818 817 0x331 Alarm 2 Rea...

Page 14: ...the current value of other registers of the module This program can be a convenient way to test the system as well as to observe real time changes in the registers Communication with the module is don...

Page 15: ...Modbus Network 6 3 4 Types of Modbus Registers 7 3 5 Communication settings 7 3 5 1 Default settings 7 3 5 2 Restore the default configuration 7 3 5 3 Configuration registers 8 4 Indicators 8 5 Modul...

Page 16: ...Input No Voltage input default Current input 1 2 3 4 5 6 7 8...

Reviews: