7
FLOOR PROTECTOR
When the heater is used on a combustible floor, use an Underwriters Listed floor protector that conforms
to UL Standards (UL 1618) and CAN/ULC for Canada, that provides at minimum type 1 ember protection.
The floor protector should be under the stove, 16” (18” for Canadian Instillations)beyond the front and 8”
beyond each side of the fuel loading and ash removal opening. If there is a horizontal section of chimney
connector, the floor protector should go under it and 2 inches beyond each side
The floor protector should exceed the stove as follows:
8”
(204mm)
U.S. 52”
(1321mm)
CAN. 60”
(1524mm)
2”
(21mm)
2”
(21mm)
12
(305mm)
41.5”
(1055mm)
INCHES (METRIC)
NOTE: DASHED LINES SHOW
STRAIGHTUP AND DOWN THROUGH
THE WALL INSTALLATION.
*CANADIAN INSTALLATIONS REQUIRE
A MINIMUM OF 18” (450mm) ON THE
FUEL LOADING SIDE AND 8”(203mm)
ON ALL OTHER SIDES.
NON-COMBUSTIBLE CONSTRUCTION
IN ACCORDANCE WITH NFPA 211
AND CAN/CSA-B365-M91
Protecteur
de plancher