1
INTRODUCTION AND SPECIFICATIONS
1.1
Overview
ASHIDA has designed economical & reliable Multifunction ADR241B Protection & Control
System. The simple and compact construction of ADITYA series ADR241B relay provides
integrated Protection, Control and Monitoring functions for Over head Transmission
Lines, Underground cables, and Distributed Feeders.
1.2
Features
Key Protection & Control Functions:
•
Four Independent Settings Groups.
•
Phase & Ground Over Current Function (50/51/50N/51N).
•
Two Independent Stages for Phase Over Current Protection.
•
Internally Derived / Externally measured Ground Over Current (3Io>/IE>)
Protection.
•
Inverse & Definite time Over Current Protection (IEC & IEEE/ANSI curves
according to IEC60255).
•
High Impedance Restricted Earth Fault Protection (64R).
•
Inverse & Definite time Negative Sequence Over Current Protection (46).
•
Cold Load Protection (CLP).
•
Broken Conductor Protection (46BC)
•
Under Current (low load) detection.
•
Thermal Overload function.
•
Multi shots (4-shots) Auto-reclosing function.
•
Breaker Failure detection (50BF).
•
Trip circuit supervision function (TCS).
•
Programmable Inputs & Outputs.
•
CB Close / Trip from HMI.
•
Programmable Target LEDs for indication with dual colours (8 nos.).
•
Self Supervision of relay.
•
Metering function.
•
Disturbance Recording (10 nos.).
•
Event Recording (512 nos.).
•
Fault Recording on HMI display (10nos.).
•
Non-Volatile memory.
•
Fully communicable with IEC standard open protocol IEC60870-5-103 ,
MODBUS & IEC61850.
•
Rear communication port for SCADA Communication.
Summary of Contents for ADR241B
Page 10: ...Page intentionally Left Blank...
Page 20: ...Page intentionally Left Blank...
Page 34: ...Page intentionally Left Blank...
Page 50: ...Page intentionally Left Blank...
Page 87: ...Page intentionally Left Blank...
Page 111: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 129: ...Page intentionally Left Blank...
Page 145: ...Page intentionally Left Blank...
Page 217: ...Page intentionally Left Blank...
Page 255: ...Page intentionally Left Blank...
Page 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Page 262: ...Page intentionally Left Blank...