background image

2

1. Measurement Mode

is entered when applying power to the unit – LED displays

applied pressure.

2.

Available

“Measurement Mode”

functions:

A.

Zero Adjustment:

Press MODE /

#

keys together

3 seconds. This initiates

automatic zero adjustment;

ADJ

briefly appears on LED display and then returns

to Measurement Mode.

B.

Peak / Bottom (Min. Max.) Hold Display:

Displayed as

$

or

#

keys are held

for more than 3 seconds and display shows

PE+

. Values are reset when power

is restored to the unit, or:
Reset Peak: Hold

$

key, then press

#

key

Reset Bottom: Hold

#

key, then press

$

key

C.

Key Lock:

Prevents overwriting values / tampering – can not be reset by restor-

ing power.
Lock: Press MODE and

$

keys together;

Lo(

appears on LED display for 1 second.

Unlock: Press MODE and

$

keys together;

UnL

appears on LED display for 1

second.

3. Function Setting Mode:

Used for product settings, except comparator-switch set-

ting. Accessed by pressing MODE key for more than 3 seconds (complete menu
attached).

A.

Comparator Selection:

Select ‘Hysteresis’ (

kYS

) or ‘Window Comparator’ (

Yn

).

Hysteresis: Switch remains activated until reset point has been achieved.
Window Comparator: Switch activates each time pressure enters a set ‘pres-
sure band’ determined by the A and B settings.

B.

Comparator Operation Selection:

Select

nPn

or

PnP

. Note: LED ring is Blue

with

nPn

and Green with

PnP

.

C.

Filter Dampening Setting:

This is based upon a moving average of pressure

data to reduce display “bounce” and smooth analog output due to system pres-
sure fluctuations. User configurable with five selections:
25ms, 250ms, 2.5s, 5s and 10s.
Filter will not be applied if

0

is selected.

D.

Power-Save (Energy-Saving) Setting:

Product is equipped with automatic

LED display turn-off feature. User may elect to turn-on display when reading
pressure or using as an indicating instrument.

E.

LED Ring Feature Setting:

Turns Red when comparator-switch is ON and Blue

(

nPn

) or Green (

PnP

) when comparator-switch is OFF.

F.

Display Unit Setting:

User may alter unit of measures from standard to arbitrary.

G.

Display Settings:

Allows for decimal point adjustment.

H.

Analog Output Scaling:

Available with only 1 comparator; function sets analog

output for pressures corresponding to Zero (4mA) and Span (20mA) adjustment
in percentage figures.
Analog output under zero point pressure: After

A-L

is displayed, select the per-

centage corresponding with the current analog output value under Zero (4mA)
using

#

or

$

keys – when pressure range displayed is set to 0.0-100.0% FS.

Analog output under span point pressure: After

A-K

is displayed, select the per-

centage corresponding with the current analog output value under Span (20mA)
using

#

or

$

keys – when pressure range displayed is set to 0.0-100.0% FS.

Example 1)

Example 2)

PRESSURE RANGE (%F.S.)

A

N

A

L

O

G

O

U

P

U

T

(m

A

d

c

)

-100

-50

0

50

100

150

20

16

12

8

4

PRESSURE RANGE (%F.S.)

A

N

A

L

O

G

O

U

P

U

T

(m

A

d

c

)

-100

-50

0

50

100

150

20

16

12

8

4