MODEL CXLdp DIFFERENTIAL 

PRESSURE TRANSDUCER 

INSTALLATION & MAINTENANCE SHEET

© 2022 Ashcroft Inc. 250 East Main Street 06614, Tel: 203-378-8281 • Fax: 203-378-0499, all specifications are subject to change without notice.  
All sales subject to standard terms and conditions. www.ashcroft.com All rights reserved.  (cxldp_transducer_i&m_(011-10130)_RevF_12-16-22

Follow the terminal block label markings on the 

CXLdp to identify the terminals;

  •   4-20 mA Ouput:

 The left, negative (-), and 

right, positive (+) terminals are used, ignore 

the center terminal which is not used. Connect 

the power supply positive lead to the CXLdp 

Reverse Wiring Protected
Electrical Connection:

 Euro-style terminal block 

accepts 12-26 AWG

Operating Temperature: 

0-160 °F (-18-71 °C)

Enclosure:

  

NEMA 1 Fire-retardant ABS Meets UL 94-5VA

Weight:

 Approx. 2.5 oz.

Pressure Connection Options: 

1

4

˝ Brass Barbs or  

1

8

 NPT Female Brass 

Optional: 

1

2

˝ conduit 

or plenum mount-

ing bracket and 

cover available as 

separately ordered 

kit – part number 

101A213-01.  

(see Figure 2) 
INSTALLATION
Mounting:

 

The transducer 

can be mounted 

on a 35 mm DIN 

rail or with #8 or 

#10 screws using 

the 4 mounting 

holes provided. 

Torque limits on 

the mounting 

holes provided is 

6 inch-pounds.  

(see Figure 3) 
Electrical Wiring:

1.  The use of shielded cable is recommended for 

optimum performance. Connect the shield to the 

guard terminal on the reading instrument (meter, 

etc.) if available or to ground.

2.  Remove the terminal block on the front of the 

transducer . 

3.  Available electrical versions  are:  

a.) CURRENT 4-20 mA; black terminal block. 

b.) VOLTAGE 0-5 Vdc/0-10 Vdc; green terminal 

block. 

Vmin = 12V+ [.022A*(RL)]

*includes a 10% safety factor
RL  = RS + RW

RL  =  Loop Resistance (ohms)

RS  =  Sense Resistance (ohms)

RW =  Wire Resistance (ohms)

 

Figure 1

 

    Load Limitations 4-20 mA Output 

TING

Loop Resistance (Ω)

 

Loop Supply Voltage (Vdc)

* F.S. pressure is equivalnt to the span of the transducer (16 mA).

Figure 3

Green LED

Use 

#10 

screw

Use #8 
screw

or

Zero Pot

Figure 2

WARNING! READ  

BEFORE INSTALLATION

1.    GENERAL: 

A failure resulting in injury or damage may be 

caused by  excessive overpressure, excessive 

vibration or pressure pulsation, excessive  

instrument temperature, corrosion of the pres-

sure containing parts, or other misuse. Consult 

Ashcroft Inc., Stratford, Connecticut, USA before 

installing if there are any questions or concerns.

2.    OVERPRESSURE: 

Pressure spikes in excess of the rated overpres-

sure capability of the transducer may cause irre-

versible electrical and/or mechanical  damage to 

the pressure measuring and containing elements.

3.   STATIC ELECTRICAL CHARGES: 

Any electrical device may be susceptible to dam-

age when exposed to static electrical charges.  

To avoid damage to the transducer the operator/

installer should follow proper ESD (electrostatic 

discharge) protection procedures before handling 

the pressure transducer.

DESCRIPTION

The Ashcroft

®

 Model CXLdp is a low differential 

pressure transducer to be used on clean, dry,  

non-corrosive gases. It is available in multiple  

accuracy classes. Both unidirectional  

(e.g. 0 to +1.0 IW) or bi-directional (e.g. ±2.0 IW) 

models are available. A green LED located on the 

front of the transducer  indicates power and  

operational status. The LED light intensity increases 

as pressure increases. 

SPECIFICATIONS 
Accuracy: (4) options,specified at time of order.

•  ±1.0% of Span 

(±0.16 mA for 4-20 mA output units) 

(±0.1V for 0-10 Vdc output units)

or

•   ±0.8% of Span 

- (±0.128 mA for 4-20 mA output units) 

- (±0.08V for 0-10 Vdc output units)

or

•  ±0.4% of Span 

- (±0.064 mA for 4-20 mA units) 

- (±0.04V for 0-10 Vdc output units)

or

•  ±0.25% of Span 

- (±0.04 mA for 4-20 mA units) 

   (±0.025V for 0-10 Vdc output units

)

Output Signal: 

Specified at time of order. 

•   4-20 mA (For symmetric bidirectional ranges 0IW 

= 12 mA

or 

•   0-10 Vdc; 0-5 Vdc User selectable option  

(For symmetric bidirectional ranges 0IW = 5 or 

2.5 Vdc respectively).

Supply Voltage: 

•   4-20 mA: 12-36 Vdc (no regulation required) 

(see Figure 1)

or

•  0-10 Vdc: 14-36 Vdc or 24 Vac (± 20%) or 0-5 

Vdc (user selectable options): 11.5-36 Vdc or 

24 Vac (±20%)

•  Supply Current: 6 mA for 10 Vdc output  

(4.5 mA for 5 Vdc output option)

positive terminal, connect the negative power 

supply lead to the negative terminal of the BCS 

4-20 mA input. Last, connect the (-) negative 

terminal on the CXLdp to the (+) positive BCS 

input.

–      +

+

+

POWER

SUPPLY

BCS

SPAN

ZERO

Zero adjust 

potentiometer

Span adjust 

potentiometer

  •   0-10 Vdc; 0-5 Vdc Output:

 Follow label mark-

ings for terminal assignments; COM is for 

Common (supply and output negative), V

IN

  

is for supply positive and V

OUT

 is for output sig-

nal. The CXLdp Voltage Output unit is supplied 

as standard with 0-10 V output, to convert to 

0-5 V output see following instructions.

    -  

0-10 Vdc Output

: Product is supplied as 

standard with 0-10 V output, see instruction 

below to access the Voltage Output jumper. 

   - 

 0-5 Vdc Output:

 See below for proper jumper 

selection. To convert the unit from a 0-10 V 

output to a 0-5 V output unit note the follow-

ing. Access the jumper by simultaneously 

pushing both housing tabs away from the 

housing, see drawings under “General  

Dimensions” for details. Change jumper  

(orange or red) 

into position as 

shown below, 

carefully reattach 

housing cover. 

When finished 

mark check box 

on front label 

indicating that the 

unit now provides 

a 0 – 5 Vdc output. 

4.  Firmly reinstall the ter-

minal block plug to its 

mating connector. 

0-10 Vdc

0-5 Vdc

Label Part No. 238A713-01

1.250˝

1.500˝

Figure 4

Jumper 
(orange 
  or red)

SPAN

ZERO

+

POWER SUPPLY

V

Out

Vin (V+, Supply)

Common (V

)

Zero adjust

potentiometer

Span adjust

potentiometer