Instruction Manual of AW-D302 Addressable Heat Detector
------ Please read this Manual carefully before installing and using the product. -----
II. Product features
✓
It can realize electronic coding and rewrite the address via coder in situ.
✓
Within a single-chip microcomputer, it can realize real-time data acquisition and processing,
realize a curve tracing for the field situation.
✓
It has a temperature compensation function and a sensor fault detection function (fault reporting
to fire alarm control panel).
✓
Non-polarity, two-bus connection that ensures convenient installation and maintenance.
✓
Designed with an upper cover and a lower cover and installed on an independent base, it can be
installed, debugged and maintained conveniently.
✓
Built-in remote indicator output terminal, drive remote indicator lit when fire alarm
。
III. Technical parameters
1.
Executive standard: EN54-5
2.
Operating voltage: 24V (pulse modulation)
3.
Product class: A2
4.
Standby current:
<
0.3mA;
5.
Alarm current: no remote indicator
<
1.5mA , has remote indicator
<
3.5mA
6.
Work indication: The red indicator will blink in the monitoring status or remain lit in the alarm
status.
7.
Weight: about 115g(with the base)
8.
External dimensions: diameter: 100mm, height: 60mm (with the base)
I. Product overview
AW-D302 Addressable Heat Detector (Detector hereunder) is a mated
product of the AW-FP300 fire alarm control panel. It uses a two-bus work
mode. With an internal microprocessor, it supports electronic coding. The
detector realizes real-time acquisition of the in situ temperature data and
sends back the data to a fire alarm control panel. It can also receive and
execute the control commands given by a fire alarm control panel. When in a
routing inspection, the detector indicator will blink. When there is a fire in the
monitored area and the temperature has reached the alarm threshold, the fire
alarm control panel will confirm a fire alarm according to the received message
sent from the detector, and the detector indicator will light at the same time to
indicate a fire alarm.
The detector is suitable for such industrial and civil buildings that have a great
deal of heat when fire takes place, such as kitchens, boiler rooms, generator
rooms, drying workshops and smoking rooms and is not suitable for places
with a great deal of smoke but little heat.